4

Unitary Products Group

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line

tubing.

2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for 

eva adder for line set.

5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.

Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 PHASE

ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS

Outdoor Unit 

HABA-

T,W036S

HABA-

T,W042S

HABA-

T,W048S

HABA-

T,W060S

HABA-

T,W076S

HABA-

T,W090S

Unit Orifice (s)

1

67, 71, 73

75, 78, 81

81

90

Factory R-22 Charge, lbs-oz

3 - 15

5 - 4

7 - 5

9 - 7

12 - 3

15 - 3

Indoor Coil

Coil Orifice

2

System O Additional Charge, Oz

G1NA036S17J

67

61 + 2

G1NA036S21C

67

61 + 2

G1NA048S21D

78

78 + 0

78 + 4

G1NA048S24P

78

78 + 0

78 + 4

G1NA060S24T

87

87 + 0

G1FA/G1UA03617/21

73

61 + 0

G1FA/G1UA048S17

84

78 + 5

G1FA/G1UA048S21

84

63 + 13

78 + 6

81 + 13

G1FA/G1UA060S24

90

78 + 16

90 + 5

G2FD036(S,H)17

75

61 + 3

G2FD036(S,H)21

75

61 + 5

G2FD042(S,H)21

78

78 + 0

G2FD046(S,H)17

78

78 + 5

G2FD048(S,H)21/24

78

78 + 9

81 + 15

G2FD060(S,H)24

90

90 + 5

F2RC036

75

61  +  0

F2RP042

78

78 + 0

702 + 0

F2FP048

84

78 + 9

81 + 15

F2FP060

90

90 + 5

KDBC090

TXV

3

0

0

Footnotes:

1. These orifices are packed in the instruction/warranty packet of each outdoor unit.
2. These orifices are factory mounted in the flow control device of each indoor coil.
3. The TXV is factory mounted in the coil or air handler.

Summary of Contents for 018-060

Page 1: ...ED COMPRESSOR The compressor is inter nally protected against high pressure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor wh...

Page 2: ...Oz 4 3 6 3 11 3 14 3 15 5 4 7 5 6 2 Charge Per Foot Oz 4 0 66 0 66 0 68 0 68 0 68 0 70 070 Operating Weight Lbs 118 123 135 137 161 176 188 Physical and Electrical Data 3 Phase MODEL HABA T036S HABA...

Page 3: ...G1NA036S17J 67 67 7 G1NA036S21C 67 67 7 G1NA048S21D 78 78 0 78 4 G1NA048S24P 78 78 0 78 4 G1NA060S24T 87 96 0 G1NF024SOF 63 57 0 3 63 4 3 G1NF036SOF 67 67 7 3 G1NF048SOF 78 78 03 78 4 3 G1NF060SOF 87...

Page 4: ...ADDITIONAL R 22 CHARGE ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS Outdoor Unit HABA T W036S HABA T W042S HABA T W048S HABA T W060S HABA T W076S HABA T W090S Unit Orifice s 1 67 71 73 75 78 81 81 90 Fac...

Page 5: ...5 10 00 9 10 HBBA F030S F2RP F2FP030 5 8 10 15 18 1000 28 4 21 0 10 00 9 50 F2RP F2FP036 5 8 10 15 19 21 1000 28 0 20 0 10 00 9 00 HBBA F036S F2RC F2FC036 5 8 10 15 21 1200 33 6 21 5 10 00 9 10 F2RP F...

Page 6: ...0 9 55 17 G2FD030 S H 17 850 25 0 18 5 10 60 9 65 14 G2FD035 S H 14 850 25 0 18 9 10 60 9 65 17 G2FD036 S H 17 850 25 6 18 9 10 70 9 70 HBBA F030S 875 1125 14 G1FA030S14 1000 28 0 20 7 10 00 9 30 14 G...

Page 7: ...9 2 10 00 9 00 17 G2FD046 S H 17 1380 40 0 29 6 10 00 9 05 21 24 G2FD048 S H 21 24 1450 41 0 30 3 10 10 9 15 HABA F048S 1400 1800 17 G1FA048S17 1500 44 5 33 5 10 00 9 15 21 24 G1FA048S21 1600 45 5 33...

Page 8: ...84 0 62 7 4 32 56 9 5 38 50 2 5 61 HBBA F030S 35 61 5 25 1 2 68 20 3 2 97 17 0 3 17 HABA T W 060S 35 61 5 54 4 4 46 50 5 4 74 46 3 5 08 40 68 5 27 4 2 70 23 1 3 04 19 7 3 30 40 68 5 60 1 4 44 56 0 4...

Page 9: ...ase for 1H 1C 1H 1C manual change over electronic non programmable thermostat 1H 1C auto manual changeover electronic programmable deluxe 7 day thermostat 1H 1C auto manual changeover electronic progr...

Page 10: ...LER TERMINAL BLOCK ROOM THERMOSTAT CONDENSING UNIT ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT ALL FIELD WIRING TO BE IN ACCORDA...

Page 11: ...1 54 1 53 1 62 1 59 1 58 1 65 1 63 1 62 95 T C 19 0 17 5 15 5 19 5 18 0 16 1 19 8 18 2 16 5 S C 12 8 12 4 11 5 13 7 13 3 12 8 14 5 14 1 13 6 K W 1 97 1 91 1 90 2 02 1 96 1 95 2 05 2 00 1 99 105 T C 1...

Page 12: ...7 5 18 5 17 6 17 9 18 8 18 1 19 0 18 3 18 4 K W 2 42 2 28 2 06 2 06 2 44 2 20 2 20 2 08 2 34 2 32 2 21 1 99 105 T C 24 7 22 4 19 5 18 3 24 8 21 6 20 9 18 6 23 8 22 8 21 1 17 9 S C 16 8 16 8 15 3 16 9...

Page 13: ...2 27 1 24 4 S C 20 3 20 4 19 5 20 8 21 5 21 5 20 7 21 6 22 4 22 5 21 7 22 7 K W 3 07 2 98 2 91 2 81 3 15 3 07 3 00 2 92 3 25 3 16 3 10 2 99 105 T C 29 3 26 7 24 6 22 0 29 5 27 0 25 0 22 4 29 7 27 2 2...

Page 14: ...84 3 71 4 02 3 91 3 77 4 06 3 96 3 81 115 T C 31 0 27 6 23 5 31 1 28 2 24 2 31 3 28 5 24 4 S C 23 1 21 3 19 6 23 9 22 6 20 7 24 8 23 7 21 6 K W 4 22 4 06 3 90 4 29 4 13 3 94 4 33 4 18 4 00 125 T C 28...

Page 15: ...8 8 27 2 31 7 30 9 29 3 K W 4 58 4 44 4 30 4 74 4 60 4 47 4 89 4 77 4 64 115 T C 37 1 32 3 28 3 38 2 33 3 28 9 39 2 34 2 29 6 S C 26 8 25 1 23 3 29 0 27 2 25 4 31 1 29 4 27 4 K W 4 81 4 62 4 45 4 96 4...

Page 16: ...33 5 33 7 32 4 33 8 34 9 35 0 33 7 35 6 K W 4 91 4 70 4 51 4 31 5 02 4 81 4 64 4 43 5 13 4 92 4 74 4 53 105 T C 45 6 41 6 38 4 34 3 46 0 42 2 39 0 35 0 46 2 42 5 39 3 36 2 S C 30 5 30 6 29 5 30 9 32...

Page 17: ...41 2 39 2 39 7 38 2 36 5 K W 4 94 4 86 4 77 5 58 5 50 5 40 5 48 5 40 5 28 95 T C 60 9 57 3 52 7 60 4 56 0 51 5 59 9 54 7 50 3 S C 45 7 43 5 40 8 42 4 40 2 38 0 39 2 37 0 35 2 K W 6 19 6 10 6 00 6 09...

Page 18: ...58 4 55 85 T C 60 6 58 0 55 0 61 2 58 6 55 8 61 9 59 3 56 7 S C 37 6 37 3 36 5 40 2 39 9 39 1 42 8 42 5 41 7 K W 5 26 5 13 5 08 5 27 5 14 5 10 5 28 5 15 5 11 95 T C 60 0 57 4 53 7 60 7 58 5 54 8 61 4...

Page 19: ...8 6 18 6 15 6 58 6 48 6 46 85 T C 76 4 73 7 70 6 79 1 76 3 73 4 81 7 79 0 76 2 S C 47 9 47 6 46 8 54 7 54 4 53 5 61 5 61 2 60 3 K W 6 53 6 42 6 37 6 86 6 74 6 70 7 18 7 07 7 04 95 T C 73 8 71 1 67 2 7...

Page 20: ...8 36 8 29 8 23 85 T C 99 1 92 4 85 8 102 0 94 7 87 5 104 8 97 0 89 1 S C 72 5 67 4 62 3 74 0 68 4 62 8 75 5 69 4 63 4 K W 8 97 8 86 8 75 9 01 8 90 8 79 9 04 8 94 8 84 95 T C 94 0 87 7 81 5 95 8 89 0...

Page 21: ...DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UNCASED UPFLOW G1FA FULL CASED UPFLOW G2FD090 is upflow only AIR HANDLERS FOR NON FURNACE APPL...

Page 22: ...036 21122 002 Rev B 0103 22 Unitary Products Group NOTES...

Page 23: ...036 21122 002 Rev B 0103 Unitary Products Group 23...

Page 24: ...nge without notice Printed in U S A 036 21122 002 Rev B 0103 Copyright by York International Corp 2003 All rights reserved Supersedes 036 21122 002 Rev A 0602 Unitary 5005 Norman Products York OK Grou...

Reviews: