036-21122-002 Rev. B (0103)
Unitary Products Group
5
COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
AIR HANDLER
COIL
1
MODEL
COOLING
MODEL
ELECTRIC
2
HEAT KW
W
RATED
CFM
NET MBH
SEER
W/O TXV
SEER
+ TXV
3
EER
TOTAL SENS.
1 PH 10 SEER AC WITH N1AH / G2FD
HABA-F018S
N1AHB0806
2,5,8,10
17
G2FD024(S,H)17
650
19.0
14.1
10.50
-
9.80
HABA-F024S
N1AHB0806
2,5,8,10
17
G2FD024(S,H)17
800
24.4
18.1
10.50
-
9.55
N1AHB0806
2,5,8,10
17
G2FD030(S,H)17
850
25.0
18.5
10.60
-
9.65
HBBA-F030S
N1AHB1206
5,8,10,15,19
17
G2FD030(S,H)17
1000
29.0
21.5
10.30
-
9.45
N1AHB1206
5,8,10,15,19
17
G2FD036(S,H)17
1000
30.0
22.2
10.50
-
9.65
HBBA-F036S
N1AHB1206
5,8,10,15,19
17
G2FD036(S,H)17
1200
33.8
25.0
10.00
-
9.20
N1AHB1206
5,8,10,15,19
17
G2FD046(S,H)17
1200
34.4
25.5
10.15
-
9.30
HABA-F042S
N1AHC1606
5,8,10,15,20
21
G2FD042(S,H)21
1400
39.5
29.2
10.00
-
9.00
N1AHC1606
5,8,10,15,20
21
G2FD048(S,H)21
1450
41.0
30.3
10.10
-
9.15
HABA-F048S
N1AHC1606
5,8,10,15,20
21
G2FD048(S,H)21
1600
46.0
34.0
10.10
-
9.50
N1AHD2006
8,10,15,20,25,30
24
G2FD060(S,H)24
1600
47.0
34.8
10.40
-
9.70
HCBA-F060S
N1AHD2006
8,10,15,20,25,30
24
G2FD060(S,H)24
1800
56.0
40.2
10.50
-
9.35
3 PH 10 SEER AC WITH N1AH / G2FD
HABA-(T,W)036S
N1AHB1246
10,15
21
G2FD036(S,H)17
1200
33.8
25.0
10.00
-
9.20
N1AHB1246
10,15
21
G2FD042(S,H)21
1400
40.0
30.1
10.00
9.05
HABA-(T,W)042S
N1AHC1646
10,15
21
G2FD042(S,H)21
1400
39.5
29.2
10.00
-
9.00
N1AHC1646
10,15
24
G2FD048(S,H)21
1450
41.0
30.3
10.10
-
9.15
HABA-(T,W)048S
N1AHC1646
10,15
21
G2FD048(S,H)21
1600
46.0
34.0
10.10
-
9.50
N1AHD2046
10,15,29
24
G2FD048(S,H)24
1600
24.6
34.0
10.10
-
9.50
N1AHD2046
10,15,29
24
G2FD048(S,H)24
1600
46.0
34.0
10.10
-
9.50
HABA-(T,W)060S
N1AHD2046
10,15,29
24
G2FD060(S,H)24
1750
58.5
39.8
10.00
-
10.25
1 PH 10 SEER AC / F2RP / RC / FC
4
,
5
HABA-F018S
F2RC/F2FC024
5,8,10
18
-
650
17.4
12.9
10.00
-
9.00
F2RP/F2FP018
2,5,8
18
-
650
17.4
12.3
10.00
-
9.00
F2RP/F2FP024
5,8,10
18
-
650
17.4
12.9
10.00
-
9.00
HABA-F024S
F2RP/F2FP024
5,8,10
18
-
800
23.4
17.3
10.00
-
9.00
F2RP/F2FP030
5,8,10,15
18
-
800
23.6
17.5
10.00
-
9.10
HBBA-F030S
F2RP/F2FP030
5,8,10,15
18
-
1000
28.4
21.0
10.00
-
9.50
F2RP/F2FP036
5,8,10,15,19
21
-
1000
28.0
20.0
10.00
-
9.00
HBBA-F036S
F2RC/F2FC036
5,8,10,15
21
-
1200
33.6
21.5
10.00
-
9.10
F2RP/F2FP036
5,8,10,15,19
21
-
1200
34.4
25.2
10.20
-
9.30
F2RP/F2FP042
5,8,10,15
21
-
1200
34.4
25.2
10.15
-
9.20
HABA-F042S
F2RP/F2FP042
5,8,10,15
21
-
1400
39.5
28.9
10.00
-
9.00
F2FP048
5,8,10,15,20,25
24
-
1400
40.5
30.0
10.00
-
9.20
HABA-F048S
F2FP048
5,8,10,15,20,25
24
-
1600
45.5
33.7
10.00
-
9.15
F2FP060
5,8,10,15,20,25
24
-
1600
46.5
34.4
10.00
-
9.70
HCBA-F060S
F2FP060
5,8,10,15,20,25
24
-
1800
56.0
41.0
10.00
-
9.15
3 PH 10 seer AC with F2RP / FP
HABA-(T,W)036S
F2RC/F2FC036
5,8,10,15
21
-
1200
33.6
25.2
10.00
-
9.10
HABA-(T,W)042S
F2RP/F2FP042
5,8,10,15
21
-
1400
39.0
29.2
10.00
-
9.00
F2FP048
5,8,10,15,20,25
24
-
1400
40.5
30.4
10.00
-
9.00
HABA-(T,W)048S
F2FP048
5,8,10,15,20,25
24
-
1600
45.5
33.7
10.00
-
9.15
HABA-(T,W)060S
F2FP060
5,8,10,15,20,25
24
-
1750
58.5
39.8
10.00
-
9.80
3 PH 10 seer AC WITH KDBC
6
HABA-(T,W)076S
KDBC-S090
10,16,26,36
22
--
2600
73.5
--
--
--
10.00
HABA-(T,W)090S
KDBC-S090
10,16,26,36
22
--
3280
53.8/
89.0
--
--
--
9.63/
9.30
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240.
Cooling MBH based on 8
0
°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters. Three phase units require three phase 2HK heaters.
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC
.
models. All ratings remain the same.
5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.
6. H*BA-(T,W)090 is field convertible to two stage operation. Its IPLV = 11.2.
— = Not Applicable.