5703827-XIM-A-0319
30
Johnson Controls Ducted Systems
Airflow performance
Table 19: ZM10-12 standard motor side duct application
ZM10 (10.0 ton) side duct - imperial units
CFM
Available external static (IWG
1
)
1. The blower performance includes 2-inch filters. See the static resistance table for additional applications.
Note:
See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP
0.2
0.4
0.6
0.8
1
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2600
632
0.70
687
0.85
737
0.98
791
1.10
854
1.24
2800
645
0.80
699
0.95
750
1.08
803
1.20
867
1.34
3000
660
0.91
714
1.06
764
1.19
818
1.32
881
1.46
3200
676
1.03
730
1.18
781
1.31
834
1.44
898
1.58
3400
694
1.16
749
1.31
799
1.44
853
1.57
916
1.71
3600
715
1.31
769
1.45
819
1.58
873
1.71
936
1.85
3800
736
1.46
791
1.61
841
1.74
895
1.86
958
2.00
4000
760
1.62
814
1.77
865
1.90
918
2.03
982
2.17
4200
786
1.79
840
1.94
890
2.07
944
2.20
1007
2.34
4400
813
1.98
867
2.12
917
2.25
971
2.38
1034
2.52
4600
841
2.17
895
2.31
946
2.45
999
2.57
1063
2.71
4800
871
2.37
926
2.51
976
2.65
1030
2.77
1093
2.91
5000
903
2.58
957
2.72
1008
2.85
1061
2.98
1124
3.12
Available Standard Static with BK72 x 1VP44 sheave combination with Motor rated at 3 HP
Field Supplied Sheave combination
ZM10 (35 kW) side duct - metric units
m³/s
Available external static (Pa
1
)
1. The blower performance includes 2-inch filters. See the static resistance table for additional applications.
Note:
See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP
50
100
149
199
249
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1.23
632
0.70
687
0.85
737
0.98
791
1.10
854
1.24
1.32
645
0.80
699
0.95
750
1.08
803
1.20
867
1.34
1.42
660
0.91
714
1.06
764
1.19
818
1.32
881
1.46
1.51
676
1.03
730
1.18
781
1.31
834
1.44
898
1.58
1.60
694
1.16
749
1.31
799
1.44
853
1.57
916
1.71
1.70
715
1.31
769
1.45
819
1.58
873
1.71
936
1.85
1.79
736
1.46
791
1.61
841
1.74
895
1.86
958
2.00
1.89
760
1.62
814
1.77
865
1.90
918
2.03
982
2.17
1.98
786
1.79
840
1.94
890
2.07
944
2.20
1007
2.34
2.08
813
1.98
867
2.12
917
2.25
971
2.38
1034
2.52
2.17
841
2.17
895
2.31
946
2.45
999
2.57
1063
2.71
2.27
871
2.37
926
2.51
976
2.65
1030
2.77
1093
2.91
2.36
903
2.58
957
2.72
1008
2.85
1061
2.98
1124
3.12
Available Standard Static with BK72 x 1VP44 sheave combination with Motor rated at 3 HP
Field Supplied Sheave combination