![York International ZM Series Installation Manual Download Page 32](http://html.mh-extra.com/html/york-international/zm-series/zm-series_installation-manual_913860032.webp)
5703827-XIM-A-0319
32
Johnson Controls Ducted Systems
Table 20: ZM10-12 standard motor bottom duct application
ZM10 (10.0 ton) bottom duct - imperial units
CFM
Available external static (IWG
1
)
1. The blower performance includes 2-inch filters. See the static resistance table for additional applications.
Note:
See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP
0.2
0.4
0.6
0.8
1
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2600
663
0.73
724
0.90
793
1.08
865
1.23
935
1.33
2800
682
0.85
743
1.02
812
1.20
884
1.35
954
1.45
3000
704
0.99
765
1.16
834
1.34
906
1.49
976
1.59
3200
730
1.15
791
1.32
860
1.50
932
1.65
1002
1.75
3400
759
1.32
821
1.49
890
1.67
962
1.82
1031
1.92
3600
793
1.51
854
1.68
923
1.85
995
2.01
1065
2.11
3800
830
1.71
891
1.88
960
2.06
1032
2.21
1102
2.31
4000
870
1.92
932
2.09
1001
2.27
1073
2.42
1143
2.52
4200
915
2.15
976
2.32
1045
2.50
1117
2.66
1187
2.75
4400
963
2.40
1024
2.57
1093
2.75
1165
2.90
1235
3.00
4600
1015
2.66
1076
2.83
1145
3.01
1217
3.16
1287
3.26
4800
1070
2.93
1131
3.10
1200
3.28
1272
3.43
1342
3.53
5000
1128
3.21
1189
3.38
1258
3.56
1330
3.71
1400
3.81
Available Standard Static with BK72 x 1VP44 sheave combination with Motor rated at 3 HP
Field Supplied Sheave combination
ZM10 (35 kW) bottom duct - metric units
m³/s
Available external static (Pa
1
)
1. The blower performance includes 2-inch filters. See the static resistance table for additional applications.
Note:
See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP
50
100
149
199
249
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1.23
663
0.73
724
0.90
793
1.08
865
1.23
935
1.33
1.32
682
0.85
743
1.02
812
1.20
884
1.35
954
1.45
1.42
704
0.99
765
1.16
834
1.34
906
1.49
976
1.59
1.51
730
1.15
791
1.32
860
1.50
932
1.65
1002
1.75
1.60
759
1.32
821
1.49
890
1.67
962
1.82
1031
1.92
1.70
793
1.51
854
1.68
923
1.85
995
2.01
1065
2.11
1.79
830
1.71
891
1.88
960
2.06
1032
2.21
1102
2.31
1.89
870
1.92
932
2.09
1001
2.27
1073
2.42
1143
2.52
1.98
915
2.15
976
2.32
1045
2.50
1117
2.66
1187
2.75
2.08
963
2.40
1024
2.57
1093
2.75
1165
2.90
1235
3.00
2.17
1015
2.66
1076
2.83
1145
3.01
1217
3.16
1287
3.26
2.27
1070
2.93
1131
3.10
1200
3.28
1272
3.43
1342
3.53
2.36
1128
3.21
1189
3.38
1258
3.56
1330
3.71
1400
3.81
Available Standard Static with BK72 x 1VP44 sheave combination with Motor rated at 3 HP
Field Supplied Sheave combination