5121817-TIM-A-0515
20
Johnson Controls Unitary Products
ZKT03 Thru T05 Without Powered Convenience Outlet (Direct Drive)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max
Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
T03
(3.0)
208-3-60 10.4
73
16.3
2.3
6
0
NONE
-
-
-
21.3
30
E05
4
1
11.1
21.4
30
E07
5.6
1
15.5
26.9
30
E10
8
1
22.2
35.3
40
E15
11.9
2
33
48.8
50
E20
15.9
2
44.1
62.7
70
230-3-60 10.4
73
16.3
2.3
6
0
NONE
-
-
-
21.3
30
E05
5.3
1
12.7
23.4
30
E07
7.5
1
18
30.1
35
E10
10.6
1
25.5
39.4
40
E15
15.9
2
38.2
55.3
60
E20
21.2
2
51
71.2
80
T04
(4.0)
208-3-60 13.7 83.1
21.4
2.3
7.6
0
NONE
-
-
-
27
35
E05
4
1
11.1
27
35
E07
5.6
1
15.5
28.9
35
E10
8
1
22.2
37.3
40
E15
11.9
2
33
50.8
60
E20
15.9
2
44.1
64.7
70
230-3-60 13.7 83.1
21.4
2.3
7.6
0
NONE
-
-
-
27
35
E05
5.3
1
12.7
27
35
E07
7.5
1
18
32.1
40
E10
10.6
1
25.5
41.4
45
E15
15.9
2
38.2
57.3
60
E20
21.2
2
51
73.2
80
T05
(5.0)
208-3-60
16
110
24.9
2.3
7.6
0
NONE
-
-
-
29.9
40
E05
4
1
11.1
29.9
40
E07
5.6
1
15.5
29.9
40
E10
8
1
22.2
37.3
45
E15
11.9
2
33
50.8
60
E20
15.9
2
44.1
64.7
70
E30
22.2
2
61.6
86.5
90
230-3-60
16
110
24.9
2.3
7.6
0
NONE
-
-
-
29.9
40
E05
5.3
1
12.7
29.9
40
E07
7.5
1
18
32.1
40
E10
10.6
1
25.5
41.4
45
E15
15.9
2
38.2
57.3
60
E20
21.2
2
51
73.2
80
E30
29.6
2
71.2
98.5
100