5121817-TIM-A-0515
60
Johnson Controls Unitary Products
Optional communication sub-board at center of UCB
Terminal FC BUS connections on left edge of the communication board
FC+
FC (“Field Connected”) BUS BACnet MSTP
communication
Positive of the VDC (typically, a fluctuating 1.5 to 3.5 volts
reading to COM; at least 0.25 volts higher than
–
) FC bus
BACnet MSTP communication circuit
FC–
FC (“Field Connected”) BUS BACnet MSTP
communication
Positive of the VDC (typically, a fluctuating 1.5 to 3.5 volts
reading to COM; at least 0.25 volts lower than +) FC bus
BACnet MSTP communication circuit
COM
Common for the FC (“Field Connected”) BUS
BACnet MSTP communication circuit
Negative of the VDC FC bus BACnet MSTP communication
circuit
SHLD
Shield for the FC (“Field Connected”) BUS
BACnet MSTP communication circuit
Earth ground reference of the cable to prevent interference on
the FC bus BACnet MSTP communication circuit
Item Selector in red housing at left on top edge of the communication board
EOL
switch
End Of Line selector switch for the FC BUS
BACnet MSTP communication circuit
ON selected only for the UCB that is the terminus of the FC bus
BACnet MSTP communication cable to prevent signal “bounce-
back”
LEDs on the communication board
EOL
Green End Of Line indicator
Lit indicates the EOL switch is selected ON
FC BUS
Green FC bus communication transmission
indicator
Lit/flickering indicates outgoing UCB FC bus communication is
currently active, off indicates the UCB is awaiting incoming FC
bus communication
ISO PWR
Green communication board Isolated Power
indicator
Lit indicates the UCB is supplying power to the communication
sub-board
Table 29: Simplicity SE UCB Details (Continued)
Description
Function & Comments
Table 30: Ignition Control Board Flash Codes
Flash Code
Description
Heart Beat
Normal Operation
1 Flash
Not Applicable
2 Flashes
Pressure / Centrifugal Switch Open with Inducer On
3 Flashes
Pressure / Centrifugal Switch Closed with Inducer Off
4 Flashes
Not Applicable
5 Flashes
Lock Out From Too Many Flame Losses
6 Flashes
High Temperature Switch Open (Primary or Aux.)
7 Flashes
Roll-out Switch Open
8 Flashes
Flame Present With Gas Off
9 Flashes
Gas Valve Stuck Off or On
10 Flashes
Flame Sense Circuit Failure