5052617-UIM-E-1116
12
Johnson Controls Unitary Products
SECTION V: ELECTRICAL POWER
ELECTRICAL POWER CONNECTIONS
Field wiring to the unit must be grounded. Electric wires that are field
installed shall conform to the temperature limitation for 63°F (35°C) rise
wire when installed in accordance with instructions. Refer to Table 7 in
these instructions for specific furnace electrical data.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
SUPPLY VOLTAGE CONNECTIONS
1.
Provide a power supply separate from all other circuits. Install over-
current protection and disconnect switch per local/national electrical
codes. The switch should be close to the unit for convenience in
servicing. With the disconnect or fused switch in the OFF position,
check all wiring against the unit wiring label. Refer to the wiring dia-
gram in this instruction.
2.
Remove the wiring box cover screws. Route all power wiring
through a conduit connector or other proper bushing that is field
installed into the unit opening and the junction box. In the junction
box there is a black wire, a white wire and a green ground screw.
Connect the power supply as shown on the unit’s wiring label
located on the inside of the blower compartment door, or the wiring
schematic in this section. Connect the black wire to L1 (hot) from
the power supply. Connect the white wire to neutral. Connect the
ground wire (installer-supplied) to the green (equipment ground)
screw. An alternate wiring method is to use a field-provided 2”
(5.1 cm) x 4” (10.2 cm) box and cover on the outside of the furnace.
Route the furnace leads into the box using a protective bushing
where the wires pass through the furnace panel. After making the
wiring connections replace the wiring box cover and screws. Refer
to Figure 17.
3.
The furnace's control system requires correct polarity of the power
supply and a proper ground connection. Refer to Figure 17.
LOW VOLTAGE CONTROL WIRING CONNECTIONS
Install the field-supplied 18ga minimum thermostat wiring by following
the instructions that come with the thermostat. With the thermostat set
in the OFF position and the main electrical source disconnected, con-
nect the thermostat wiring from the wiring connections on the thermo-
stat to the terminal board on the ignition module, as shown in Figures
18 or 19. Electronic thermostats require the common wire to be con-
nected. Do not use power stealing thermostats. Apply strain relief to
thermostat wires passing through cabinet. If air conditioning equipment
is installed, use thermostat wiring to connect the Y and C terminals on
the furnace control board to the proper wires on the condensing unit
(unit outside).
The 24-volt, 40 VA transformer is sized for the furnace components
only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an
air conditioning unit contactor.
CAUTION
Use copper conductors only.
!
Table 7:
Ratings & Physical / Electrical Data
Input
High/Low
Output
High/Low
Nominal
Airflow
Cabinet Width
Total Unit
Amps
AFUE
High Fire
Air Temp. Rise
MBH
kW
MBH
kW
CFM
m
3
/min
in.
cm
%
°F °C
40/26
12/8
38/25
11/7
1000
28.3
14-1/2
36.8
9.5
96
25-55
14-31
60/39
18/11
58/37
17/11
1200
34
17-1/2
44.4
9.5
96
35-65
19-36
80/52
23/15
77/50
22/14
1200
34
17-1/2
44.4
9.5
96
45-75
25-42
80/52
23/15
77/50
22/14
1600
45.3
21
53.3
9.5
96
40-70
22-39
100/65
29/19
96/62
28/18
1600
45.3
21
53.3
9.5
96
50-80
28-45
100/65
29/19
96/62
28/18
2000
56.6
21
53.3
10.9
96
45-75
25-42
120/78
35/23
115/75
33/22
2000
56.6
24-1/2
62.2
10.9
96
50-80
28-45
Low Fire
Air Temp. Rise
Max. Outlet
Air Temp.
Blower
Blower Size
Max.
Over-current
Protect
Min. Wire Size
(awg) @ 75 ft.
One Way
Operating
Weight
°F °C °F
°C
HP
Amps in.
cm
Lbs.
Kg.
25-55
14-30
190
88
1/2
6.8
11 x 8
27.9 x 20.3
15
14
113
51.2
35-65
19-36
190
88
1/2
6.8
11 x 8
27.9 x 20.3
15
14
119
54.0
35-65
19-36
190
88
1/2
6.8
11 x 8
27.9 x 20.3
15
14
123
57.1
25-55
14-30
190
88
1/2
6.8
11 x 10
27.9 x 25.4
15
14
130
59.0
30-60
17-33
190
88
1/2
6.8
11 x 10
27.9 x 25.4
15
14
136
61.6
30-60
17-33
190
88
3/4
8.4
11 x 11
27.9 x 27.9
15
14
143
64.8
45-75
25-42
190
88
3/4
8.4
11 x 11
27.9 x 27.9
15
14
154
69.8
FIGURE 17:
Electrical Wiring
Electrical Entry
Junction
Box
L1-Hot
Neutral
Connect ground
lead to screw
BLK
WHT
IMPORTANT
The power connection leads and wiring box may be relocated to the
opposite side of the furnace. Remove the screws and cut wire tie
holding excess wiring. Reposition on the opposite side of the furnace
and fasten using holes provided.
IMPORTANT
Set the heat anticipator in the room thermostat to 0.4 amps. Setting it
lower will cause short cycles. Setting it higher will cause the room
temperature to exceed the set points.
IMPORTANT
Some electronic thermostats do not have adjus
table
heat anticipa-
tors. They should be set to six cycles per hour. Follow the thermostat
manufacturer's instructions.