810753-UTG-A-0313
20
Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. RHP13J604S21
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1800
2000
2200
ID DB (°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID WB (°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
57.5
60.5
60.5
66.0
72.0
59.4
61.6
61.6
67.1
73.0
61.2
62.7
62.6
68.2
74.0
S.C.
57.1
52.5
44.9
44.2
35.6
58.9
55.6
46.8
46.2
36.7
60.8
58.6
48.8
48.2
37.7
KW
3.59
3.62
3.62
3.68
3.75
3.68
3.70
3.71
3.76
3.83
3.78
3.79
3.79
3.85
3.92
75
T.C.
55.4
57.7
57.7
63.0
68.8
57.1
58.6
58.6
64.0
69.7
58.8
59.6
59.5
65.0
70.7
S.C.
55.0
51.3
43.6
42.9
34.2
56.7
54.0
45.5
44.9
35.3
58.4
56.8
47.4
46.8
36.4
KW
4.02
4.05
4.05
4.11
4.18
4.11
4.13
4.13
4.19
4.27
4.21
4.22
4.21
4.28
4.36
85
T.C.
53.3
54.8
54.9
60.1
65.6
54.9
55.7
55.6
61.0
66.5
56.5
56.5
56.3
61.8
67.4
S.C.
52.9
50.0
42.2
41.6
32.8
54.5
52.5
44.1
43.6
33.9
56.1
54.9
46.1
45.5
35.0
KW
4.45
4.47
4.47
4.54
4.61
4.55
4.56
4.56
4.62
4.70
4.64
4.64
4.64
4.71
4.79
95
T.C.
51.2
51.9
52.0
57.1
62.4
52.6
52.7
52.6
57.9
63.2
54.1
53.5
53.1
58.6
64.0
S.C.
50.8
48.8
40.9
40.4
31.4
52.3
50.9
42.8
42.2
32.5
53.7
53.1
44.7
44.1
33.7
KW
4.89
4.90
4.90
4.97
5.05
4.98
4.98
4.98
5.06
5.14
5.07
5.07
5.06
5.14
5.23
105
T.C.
48.5
48.3
48.6
53.4
58.5
49.8
49.5
49.1
54.0
59.1
51.2
50.6
49.5
54.6
59.7
S.C.
48.1
46.6
39.4
38.8
29.9
49.5
48.4
41.3
40.7
31.0
50.8
50.2
43.1
42.6
32.1
KW
5.43
5.42
5.43
5.50
5.58
5.52
5.52
5.51
5.59
5.67
5.62
5.62
5.60
5.68
5.76
115
T.C.
45.8
44.8
45.2
49.6
54.6
47.0
46.3
45.5
50.1
55.0
48.3
47.7
45.9
50.6
55.5
S.C.
45.5
44.5
37.9
37.3
28.5
46.7
45.9
39.7
39.2
29.5
47.9
47.4
41.6
41.1
30.5
KW
5.97
5.95
5.97
6.04
6.12
6.07
6.06
6.05
6.12
6.21
6.17
6.16
6.13
6.21
6.29
125
T.C.
43.1
41.2
41.7
45.9
50.7
44.2
43.0
42.0
46.2
50.9
45.4
44.9
42.3
46.5
51.2
S.C.
42.8
41.2
36.3
35.7
27.0
43.9
43.0
38.2
37.6
28.0
45.0
44.5
40.0
39.5
28.9
KW
6.51
6.48
6.50
6.57
6.65
6.62
6.59
6.58
6.66
6.74
6.72
6.71
6.66
6.74
6.82
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC62
0.99
0.97
0.96
–
FC64
0.98
1.01
0.99
RFCX60DE
–
1.01
0.97
0.94
RFCX60DP
–
1.00
1.00
1.00
MX20D
FC/MC62D
1.01
0.97
0.93
MX20D
FC64D
0.98
1.01
0.94
Furnaces
Coils
T.C.
S.C.
KW
R*L*CE20
FC/MC62D
0.99
0.95
0.91
R*L*CE20
FC64D
0.97
0.97
0.93
R*9*CE20
FC/MC62D
0.99
0.95
0.91
R*9*CE20
FC64D
0.96
0.95
0.93
R*9*DE20
FC/MC62D
0.99
0.95
0.92
R*9*DE20
FC64D
0.97
0.96
0.94