5612272-UTG-H-1221
Johnson Controls Ducted Systems
3
‡ The adapter fitting must be field installed for the required 1 1/8 in. refrigeration pip-
ing.
Notes:
•
All dimensions are in inches and are subject to change without notice.
•
The overall height is from the bottom of the base pan to the top of fan
guard.
•
The overall length and width include screw heads.
PHYSICAL AND ELECTRICAL DATA
Model
RHP14L18B
23S
RHP14L24B
23S
RHP14L30B
23S
RHP14L35B
23S
RHP14L36B
23S
RHP14L42B
24S
RHP14L48B
23S
RHP14L60B
23S
Unit supply voltage
208 V to 230 V, 1
60 Hz
Normal voltage range
1
(V)
1. Rated in accordance with AHRI Standard 110-2012, utilization range A.
187 V to 252 V
Minimum circuit ampacity (A)
12.0
15.4
18.1
20.5
22.0
26.8
30.8
31.7
Maximum overcurrent device (A)
2
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
20
25
30
35
35
45
50
50
Minimum overcurrent device (A)
3
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
15
20
20
25
25
30
35
35
Compressor
Type
4
4. Rotary compressor models are limited to an equivalent length of refrigeration piping of 100 ft with no exceptions.
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Rated load (A)
9.0
11.7
13.4
15.4
15.4
19.2
23.6
24.3
Locked rotor (A)
56.3
61.6
72.5
83.9
83.9
123.9
130
144.2
Crankcase heater
No
No
No
No
No
No
No
No
Factory external discharge muffler
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Hard start kit required with TXV
5
5. Refer to the
Hard Start Kit Accessory Installation Manual
for the hard start kit part number for each model. The hard start kit is a field installed accessory.
No
No
No
No
No
No
No
No
Hard start kit part number
(S1-2SA067*****)
10106
10106
10106
10106
10106
10106
10106
10106
Fan diameter (in.)
22
22
24
24
26
26
26
26
Fan motor
Type
PSC
PSC
PSC
PSC
ECM
ECM
PSC
PSC
Rated HP
1/8
1/8
1/4
1/4
1/3
1/3
1/4
1/4
Rated load (A)
0.80
0.80
1.30
1.30
2.8
2.8
1.30
1.30
Nominal RPM
1075
1075
850
850
834
834
850
850
Nominal CFM
2850
2850
2995
2995
3715
4000
4000
4100
Coil
Face area (sq ft)
16.15
17.94
23.82
23.82
26.40
26.40
26.40
28.80
Rows deep
1
1
1
1
1
1
2
2
Fins per inch
22
22
22
22
22
22
18
18
Liquid refrigeration piping outdoor (field
installed)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor refrigeration piping outdoor (field
Installed)
6
6. For applications with non-standard vapor line sizes, see the
APPLICATIONS AND ACCESSORIES
section.
3/4
3/4
3/4
3/4
3/4
7/8
7/8
1 1/8
‡
Unit charge (lb - oz)
7
7. The unit charge is correct for the outdoor unit, smallest matched indoor unit, and 15 ft of refrigerant tubing. For tubing lengths other than 15 ft, add or subtract refrigerant, using the
difference in actual refrigeration piping length multiplied by the per foot value.
‡ The adapter fitting must be field installed for the required 1 1/8 in. refrigeration piping.
5 - 3
5 - 6
6 - 12
8 - 1
8 - 15
8 - 11
13 - 3
13 - 13
Charge (oz/ft)
0.62
0.62
0.62
0.62
0.62
0.67
0.67
0.75
Operating weight (lb)
120
131
176
176
230
230
235
256
&
%
$
$
DIMENSIONS
Unit
model
Dimensions
(in.)
Refrigerant connection
service valve size (in.)
A
B
C
Liquid
Vapor
RHP14L18B23S
33 1/4
29 1/4
29 1/4
3/8
3/4
RHP14L24B23S
36 1/4
29 1/4
29 1/4
RHP14L30B23S
39 1/2
35 1/4
31 3/4
RHP14L35B23S
39 1/2
35 1/4
31 3/4
RHP14L36B23S
39 1/2
38
34 1/4
RHP14L42B24S
39 1/2
38
34 1/4
7/8
RHP14L48B23S
39 1/2
38
34 1/4
RHP14L60B23S
42 3/4
38
34 1/4
7/8
‡