IECEx Certification
(1) Technical Data
a. Caution for IECEx Type n Certification
Note 1. Model YFGW510 Field Wireless Access Point with optional code SN27 is applica
-
ble for use in hazardous area.
• No. IECEx DEK 14.0028
• Applicable standards: IEC60079-0:2011, IEC60079-11:2011, IEC60079-15:2010
• Type of Protection and Marking code: Ex nA [ic] IIC T4 Gc
• Ambient Temperature: –30 °C to +65 °C
• Enclosure: IP66
• Power Supply: 24 V DC (10 to 26.4 V DC at the Power Supply terminals)
• Overvoltage Category: I
• Power dissipation: ≤ 3.5 W
• RF power: ≤ 60 mW (ISA100.11a; IEEE802.15.4)
≤ 64 mW (Wireless LAN: IEEE802.11a/b/g)
• Antenna Connection: The following condition shall be met.
(Total Li of simple apparatuses) + (Total Lc) ≤ 3 mH
(Total Ci of simple apparatuses) + (Total Cc) ≤ 0.8 μF
Note 2. Specfic condition of use
Precautions shall be taken to minimize the risk from electrostatic discharge of painted parts.