<Read Me First>
IM 01W02E01-11EN
n
CSA Certification
Caution for CSA Non-incendive Certification
(1) Technical Data
Note 1. Model YFGW510 Field Wireless Access Point with optional code CN17 is applica
-
ble for use in hazardous area.
• Certificate: 2655412
• Applicable standards:
C22.2 No.0-10, CAN/CSA-C22.2 No. 0.4-04,
CAN/CSA-C22.2 No. 94-M91, C22.2 No. 213-M1987
CAN/CSA-C22.2 No. 60079-0:11
CAN/CSA-C22.2 No. 60079-15:12
CAN/CSA-C22.2 No. 61010-1-04
IEC 60529:2001
• Hazardous Location Ratings: Non-Incendive for
Class I, Division 2, Groups A, B, C and D;
Class II , Division 2, Groups F and G;
Class III, Division I
Non-Incendive Field Wiring Connections for Class I , Division 2, Groups A, B, C, D;
Ex nA [nL] IIC T4
• Ambient Temperature: –30 to 65 °C
• Altitude: ≤ 3000m
• Enclosure: Type 4X, IP66
• Power Supply: 10.0 V d.c. to 26.4 V d.c. (Rated voltage: 24.0 V d.c.)
• Power dissipation: ≤ 3.5 W
• RF power: ≤ 60 mW (ISA100.11a; IEEE802.15.4)
≤ 64 mW (Wireless LAN: IEEE802.15.11a/b/g)
• Cable parameters for antenna connection: Ccable: ≤ 4 nF, Lcable: ≤ 20 μH
• Routine Test: The RF power is checked by routine tests.
(2) Specific condition of use
Precautions shall be taken to minimize the risk from electrostatic discharge of painted parts.
(3) Electrical Connection
• The type of electrical connection depends on the marking below on YFGW510.
Marking
The type of electrical connection
Note
M
M20 (ISO)
M20 X 1.5
A
ANSI 1/2 NPT
1/2-14 NPT