![YOKOGAWA XS550 User Manual Download Page 23](http://html1.mh-extra.com/html/yokogawa/xs550/xs550_user-manual_3518743023.webp)
5-2
<Wiring>
IM 01W06F02-01EN
n
Applicable Cables
Insulated cables for industrial equipment such as;
• 600 V polyvinyl chloride insulated wires (IV): JIS C3307
• Polyvinyl chloride insulated wires for electrical apparatus (KIV): JIS C3316
• 600 V grade heat-resistant polyvinyl chloride insulated wires (HIV): JIS
C3317
• Heatproof vinyl insulated wires VW-1 (UL 1015/UL 1007)
Wire size
• Core: AWG 14 to 13 (2 to 2.6 mm
2
)
Termination
• Use a round crimp terminal for M4 terminals with an insulation sleeve
5.3 Connecting Cables to Terminals
5.3.1 Connection of the input terminal
F09.ai
Ground terminal
Figure 5-1 Input Terminal Connections
If the cable has a screen for shielding, connect the screen to the ground
terminal shown in Figure 5-1. Be careful not to make the screen as a multi-
point grounding. Connect the thermocouple as shown in Figure 5-2. Pay
attention to the connection terminal because this product does not detect
polarity misconnection.