4.3.1 Configuring VZ20X Settings
1. Configure the Ethernet settings.
IP address: 192.168.1.2
Subnet mask: 255.255.255.0
Default gateway: 0.0.0.0
2. Although the fastest communication
interval setting for the GX20 Modbus
client function is 100 ms, specify [1 ms],
[10 ms], or [50 ms] for the VZ20X [Data
acquisition interval] setting.
In this example, [1 ms] is selected.
Also, select [1-5 V] for [Input type], enter
"5.0000" for [Max. value of input scale],
enter "1.0000" for [Min. value of input scale],
and select [4] for [Input scale decimal point
position].
4.3.2 Creating the GA10 Modbus Definition File
Setting item
Setting value
Remarks
Device Name
VZ20X_8CH
This is the name displayed
in GA10.
Port number
502
Command Delay
0
Register
See the next
page when
setting this item.
Command
Read
Data type
INT32_B
Dec. Point
4
Set the VZ20X input scale
decimal point position.
MIN
1.0000
Set the VZ20X input scale
minimum value.
MAX
5.0000
Set the VZ20X input scale
maximum value.
1. Create the GA10 Modbus definition file.
Specify the [Device Name], [Port number],
[Command Delay], [Channel name],
[Register], [Command], [Data type], [Dec.
Point], [MIN], and [MAX] settings.
Read
INT32_B
Set the decimal point
position, minimum value, and
maximum value according to
the scale settings for each
channel on the VZ20X.
Set the VZ20X
register number.
45
TI 77V01B01-11EN
Oct.18, 2021-00