background image

However, if the setting is made so that the upper limit < lower 

limit, the unit outputs the upper limit value.

6.8  VJX7-H (Velocity Computation)

This computing unit calculates the input velocity by subtracting 

the input of the last velocity computation (XL) from the present 

input (X). The unit then adds a 50% bias to one-half of the 

obtained velocity and outputs the result (output-1=Y1, output-

2=Y2). The output results is 50% when the input is not changed, 

50% or more when the input increases (100% for X-XL 100%), 

and 50% or less when the input decreases (0% for X-XL –100%). 

When using a first-order lag filter for input (X), set the first-order 

lag time constant (T). 

Y1=Y2=

+50%

X–X

L

2

Set the velocity computation time (L) at % value in 

[H02: 

CONST]

.  The value of 0 to 100.0% corresponds to that of 0 to 

1000 seconds.  For example, enter “6” to set in H02 when setting 

60 seconds.

 •

Setting range of velocity computation time:

 

0 to 320,000 seconds (about 3.7 days) with 4 significant digits

 

Minimum unit is 1 second (however, 0.1 second is possible for 

4 seconds or shorter).  

( e.g. 12345% is impossible, 12340% is possible.)

First-order lag time constant (T) is set at % value in 

[H01: 

CONST]

.  The value of 0 to 100% corresponds to that of 0 to 100 

seconds.

 •

Setting range of time constant: 

 

0 to 799.0 seconds; minimum unit is 0.1 second.

 •

Accuracy of moving average and time constant setting: 

 

(±5.0% of set value) ± 1 second

6.9  VJX7-J (Linearizer)

This computing unit gives an optional relationship between the 

input (X) and output (output-1=Y1, output-2=Y2) signals using an 

optional line-segment function. The line-segment function has 21 

breakpoints, which each gives an input-output relationship as a 

percentage (%). Set the input (X) at % value in 

[H01:CONST]

 to 

[H21:CONST]

, and the output (Y) at % value in 

[H22:CONST]

 to 

[H42:CONST]

.

 •

Breakpoint (21 points) setting conditions:

 

For input: -6.0≤X

0

 (H01) to X

20

 (H21)≤106.0%; minimum unit 

is 0.01% 

X0<X1<X2< ····· <X20

 

For output: -6.0≤Y

0

 (H22) to Y

20

 (H42)≤106.0%; minimum unit 

is 0.01% 

When input≤X

0

 (H01), Y

0

 (H21) is output.

 

When input≥

20

 (H22), Y

20

 (H42) is output.

 

Any number of line segments (1 to 20) can be set in H43.

 

The number of line segments 1 to 20 corresponds 100 to 

2000%.

 •

Computation accuracy: 

 

±0.1 % (when line-segment gain is 1 or less)

6.10 VJX7-K (Ratio Setter)

This computing unit sets the ratio by the following expression.

Y1=Y2=K1 

×

 (X+A1)+A2

where  Y1: 

Output-1 signal (%)

 

Y2: 

Output-2 signal (%)

 

X: 

Input signal (%)

 

K1: 

Ratio (no unit)

 

A1, A2:  Bias (%)

Set the ratio (K1) in 

[H01:CONST]

, and the bias (A1) at % value 

in 

[H02:CONST]

, and the bias (A2) at % value in 

[H03:CONST]

.

 •

Setting range of ratio: 

 

-320 to 320 with 4 significant digits; minimum unit is 0.00001.

 •

Setting range of bias: 

 

-32,000% to 32,000% with 4 significant digits; minimum unit is 

0.001%.

 •

Computation accuracy: 

 

±0.1 % (when K1=1, A1=A2=0%)

7.  LIST OF PARAMETERS 

*3

Parameter Display Item

MODEL

Model

TAG NO

Tag no.

SELF CHK

Self-check result

A

DISPLAY1

Display1

A01

INPUT1

Input value 1

A07

OUTPUT1

Output value 1

A08

OUTPUT2

Output value 2

A19

T1

Temporary memory 1

A20

T2

Temporary memory 2

A21

T3

Temporary memory 3

A22

T4

Temporary memory 4

A26

DO

Digital output

A27

LOAD

Load factor

A54

STATUS

Status

*1

A56

REV NO

Rev. no.

A58

MENU REV

MENU REV

A60

SELF CHK

Self-check result

B

DISPLAY2

Display2

B01

INPUT1

Input value 1

B07

OUTPUT1

Output value 1

B08

OUTPUT2

Output value 2

B19

T1

Temporary memory 1

B20

T2

Temporary memory 2

B21

T3

Temporary memory 3

B22

T4

Temporary memory 4

B26

DO

Digital output

B28

LOAD

Load factor

B60

SELF CHK

Self-check result

D

SET (I/O)

Setting (I/O)

*2

D01

TAG NO.1

Tag no. 1

D02

TAG NO.2

Tag no. 2

D03

COMMENT1

Comment 1

D04

COMMENT2

Comment 2

D12

INP TYPE

Input type

D13

IN RESIST

Input resistor

D32

INPUT1 L_RNG

Input low range

D33

INPUT1 H_RNG

Input high range

D32

OUT1 L_RNG

Output-1 low range

*4

D33

OUT1 H_RNG

Output-1 high range

*4

D34

OUT2 L_RNG

Output-2 low range

*4

D35

OUT2 H_RNG

Output-2 high range

*4

D45

PRGM SELECT

Selection of program

D48

CYCLE TIME

Computing period

D50

OUT1 DR

Direction of output-1 action

D51

OUT2 DR

Direction of output-2 action

D59

NMRR

Frequency setting

*4

D60

SELF CHK

Self-check result

F

SET(COM)

Setting (communication)

*2

F01

PROTOCOL

Communication protocol

F02

ADDRESS

Address

F03

BAUD RATE

Baud rate

F04

PARITY

Parity

F05

DATA LEN

Data Length

F06

STOP BIT

Stop bit

F07

INPUT DEC PT

Decimal point position of input

F60

SELF CHK

Self-check result

G

PROGRAM

Program of computing unit

G01

PROGRAM

Program

G59

PROGRAM

Program

G60

SELF CHK

Self-check result

H

CONST

Fixed constant of computing unit

H01

CONST

Fixed constant

H59

CONST

Fixed constant

H60

SELF CHK

Self-check result

P

ADJUST

Adjustment

*2

P04

IN1 ZERO ADJ

Zero adjustment of input-1

P05

IN1 SPAN ADJ

Span adjustment of input-1

P30

OUT1ZERO ADJ

Zero adjustment of output-1

P31

OUT1SPAN ADJ

Span adjustment of output-1

P32

OUT2ZERO ADJ

Zero adjustment of output-2

P33

OUT2SPAN ADJ

Span adjustment of output-2

P40

RESISTOR ADJ

Adjustment of external input resistance

P60

SELF CHK

Self-check result

Q

TEST

Test

*2

Q04

OUT1 TEST

Forced output (output-1)

Q05

OUT2 TEST

Forced output (output-2)

Q14

RLY1 TEST

Forced output (relay-1)

Q15

RLY2 TEST

Forced output (relay-2)

Q60

SELF  CHK

Self-check result

*1

The Status is displayed for service personnel to see history 

records.

*2

There are items not displayed depending on what output-2 is 

specified.

*3

There are items not displayed depending on what the setting 

of program selection is specified.

*4

The parameters are the items to be set at the factory.

5

IM 77J01X07-01E 4th Edition 