IM 05P01C31-15EN   page 9/12

Operation Parameters

Hold down the PARAMETER key or PARA key for 3 seconds to move from the Opera-

tion Display to the Operation Parameter Setting Display. Press the DISPLAY key or 

DISP key once to return to the Operation Display.

Menu

Hold down PARAMETER key or PARA key

for 3 sec.

DISPLAY key

or DISP key

SET/ENTER key

PARAMETER key

or PARA key

key

key

key

key

key

The parameter groups can be switched using     ,      keys.

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

Parameter

END

Menu

END

Menu

END

END

Menu Display and 

Parameter Setting 

Display are changed 

in a circular pattern.

Move to the Setup Parameter Setting Display: 

     Hold down the PARAMETER key or PARA key and the Left arrow key simultaneously 

     for 3 sec.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

·  To change and set the parameter setting, press the SET/ENTER key to start the set-

point blinking. The blinking state allows you to make changes (setting mode). Use the 

Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to 

register the setting.

Note that there are some parameters which are not displayed depending on the model and suffix 

codes, control mode (CTLM), control type (CNT), etc. The parameters for professional setting 

mode (LEVL: PRO) are not described in this manual. See User’s Manual (IM 05P01C31-01EN).

 Operation Mode

Menu symbol: 

 

(MODE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(S.R)

STOP/RUN switch

STOP: Stop mode

RUN: Run mode

Preset output (PO) is generated in 

STOP mode.

Default: Not displayed. STOP/RUN 

switch is assigned to contact input.

RUN

EASY

(R.L)

REMOTE/LOCAL switch

LCL: Local mode

REM: Remote mode

Select a remote input method for 

acquiring the target setpoint from 

remote input or communication using 

the parameter RMS.

LCL

(AT)

AUTO-tuning switch

OFF: Disable

1 to 8: Perform auto-tuning. Tuning 

result is stored in the specified num-

bered PID.

R: Tuning result is stored in the PID 

for reference deviation.

OFF

(SPNO.)

SP number selection

1 to 8 (Depends on the setup param-

eter SPGR. setting.)

1

(PID)

PID number

The PID group number being selected 

is displayed.

1 to 8, R: PID group for reference 

deviation

1

 SELECT Parameter

Menu symbol: 

 (CS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

Registered 

parameter 

symbol

SELECT parameter 10 

to 19

Setting range of a registered parame-

ter. For details, see User's Manual (IM 

05P01C31-01EN).

Table 

below

EASY

Parameter 

n=10

n=11

n=12

n=13

n=14

n=15

n=16

n=17

n=18

n=19

CSn

For the registration of SELECT parameters, see User's Manual (IM 05P01C31-01EN).

 SP and Alarm Setpoint Setting Parameter

Menu symbol: 

 (SP)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SP)

Target setpoint

0.0 to 100.0% of PV input range (EU) 

(Setting range: SPL to SPH)

SPL

Table 

below

EASY

(SUB)

Sub-target setpoint (in 

Two-position two-level 

control)

Set the offset from SP.

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % 

of PV 

input 

range 

span

(PIDN)

PID number selection

Set a PID group number to use.

1 to 8 (Depends on the setup param-

eter PIDG. setting.)

1 to 8

 to 

(A1 to A8)

Alarm-1 to -8 setpoint

Set a display value of setpoint of PV 

alarm, SP alarm, deviation alarm, 

output alarm, or velocity alarm.

-19999 to 30000 (Set a value within the 

input range.)

Decimal point position depends on the 

input type

0

For the parameter SP (target setpoint), 8 groups are displayed for the factory default. 

The number of groups can be changed by the setup parameter SPGR. (number of SP 

groups). For the alarm setpoint parameter, alarm-1 to -4 are displayed for the factory 

default. The number of alarms can be changed using the setup parameter ALNO. 

(number of alarms). To change the number of SP groups or alarms, see User's Manual 

(IM 05P01C31-01EN).

Use the following table to record SP and alarm setpoints.

Parameter

n=1

n=2

n=3

n=4

n=5

n=6

n=7

n=8

SP

SUB

PIDN

A1
A2
A3
A4
A5
A6
A7
A8

n: group number

 SP-related Setting Parameter 

Menu symbol: 

 (SPS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(RMS)

Remote input method

RSP: Via remote (auxiliary analog) 

input

COM: Via communication.

RSP

STD

(RFL)

Remote input filter

OFF, 1 to 120 s

OFF

(RT)

Remote input ratio

SP = Remote input x RT + Remote 

input bias

0.001 to 9.999

1.000

(RBS)

Remote input bias

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % 

of PV 

input 

range 

span

(UPR)

SP ramp-up rate

Used to prevent SP from changing 

suddenly.

Set a ramp-up rate or ramp-down rate 

per hour or minute. Set a time unit 

using the parameter TMU.

OFF, 0.0 + 1 digit to 100.0% of PV 

input range span (EUS)

OFF

EASY

(DNR)

SP ramp-down rate

OFF

(TMU)

SP ramp-rate time unit

HOUR: Ramp-up rate or ramp-down 

rate per hour

MIN: Ramp-up rate or ramp-down 

rate per minute

HOUR

(SPT)

SP tracking selection

Tracking is performed when the mode 

changes from Remote to Local. (The 

local setpoint keeps track of the 

remote setpoint.)

OFF, ON

ON

STD

(PVT)

PV tracking selection

Causes the setpoint to keep track of 

the PV so the setpoint automatically 

reverts to its original value at a preset 

rate of change. The UPR, DNR, and 

TMU are used in combination.Operat-

ing conditions: 1) MAN → AUTO, 2) 

STOP → AUTO, 3) Power-on, 4) SP 

number change, 5) SP change

OFF, ON

OFF

 

 Alarm Function Setting Parameter

Menu symbol: 

 (ALRM)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(AL1 to AL8)

Alarm-1 to 8 type

Example: Alarm-1

Stand-by 

action

Latch action

Energized/

De-energize

Alarm 

type

Set a 5-digit value in the following 

order.

[Latch action (0/1/2/3/4)] + [Energized 

(0) or De-energized (1)] + [Without (0) 

or With (1) Stand-by action] + [Alarm 

type: 2 digits (see below)]

For latch action, see User's Manual 

(IM 05P01C31-01EN). 

AL1, 

 

AL3, 

 

AL5, 

 

AL7: 

 

Latch 

action 

(0)

 

Ener-

gized 

(0) 

 

Without 

Stand-

by 

action 

(0)

 

PV high 

limit (01)

 

AL2, 

AL4,

 

AL6,

 

AL8: 

Latch 

action 

(0)

 

Ener-

gized 

(0)

 

Without 

Stand-

by 

action 

(0)

 

PV low 

limit (02) 

AL5 to  

AL8: not 

displayed 

for 

factory 

default

Table 

below

EASY

Alarm type: 2 digits

00: Disable

01: PV high limit

02: PV low limit

03: SP high limit

04: SP low limit

05: Deviation high limit

06: Deviation low limit

07: Deviation high and low limits

08: Deviation within high and low limits

09: Target SP high limit

10: Target SP low limit

11: Target SP deviation high limit

12: Target SP deviation low limit

13: Target SP deviation high and low limits

14: Target SP deviation within high 

and low limits

15: OUT high limit

16: OUT low limit

17: Cooling-side OUT high limit

18: Cooling-side OUT low limit

19: Analog input PV high limit

20: Analog input PV low limit

21: Analog input RSP high limit

22: Analog input RSP low limit

23: Analog input AIN2 high limit

24: Analog input AIN2 low limit

25: Analog input AIN4 high limit

26: Analog input AIN4 low limit

27: Feedback input high limit

28: Feedback input low limit

29: PV velocity

30: Fault diagnosis

31: FAIL

32: Deviation(%) high limit

33: Deviation(%) low limit

34: Deviation(%) high and low limits

35: Deviation(%) within high and low 

limits

36: Target SP deviation(%) high limit

37: Target SP deviation(%) low limit

38: Target SP deviation(%) high and 

low limits

39: Target SP deviation(%) within high 

and low limits

 to 

(VT1 to VT8)

PV velocity alarm time 

setpoint 1 to 8

0.01 to 99.59 (minute.second)

1.00

 to 

(HY1 to HY8)

Alarm-1 to -8 hysteresis

Set a display value of setpoint of 

hysteresis.

-19999 to 30000 (Set a value within 

the input range.)

Decimal point position depends on the 

input type. When the decimal point 

position for the input type is set to "1", 

the initial value of the hysteresis is 

"1.0".

10

 to 

(DYN1 to DYN8)

Alarm-1 to -8 On-delay 

timer

An alarm output is ON when the delay 

timer expires after the alarm setpoint 

is reached.

0.00 to 99.59 (minute.second)

0.00

STD

(AMD)

Alarm mode

0: Always active

1: Not active in STOP mode

2: Not active in STOP or MAN mode

0

For the alarm function setting parameter, 4 alarms are displayed for the factory default. 

The number of alarms can be changed by the setup parameter ALNO. (number of 

alarms). To change the number of alarms, see User's Manual (IM 05P01C31-01EN). 

Parameter

n=1

n=2

n=3

n=4

n=5

n=6

n=7

n=8

ALn
VTn

HYn

DYNn

n: alarm number

 PV-related Setting Parameter 

Menu symbol: 

 (PVS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BS)

PV input bias

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % 

of PV 

input 

range 

span

EASY

(FL)

PV input filter

OFF, 1 to 120 s

OFF

 

 PID Setting Parameter

Menu symbol: 

 (PID)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(P)

Proportional band

 

Heating-side proportion-

al band (in Heating/cool-

ing control)

0.0 to 999.9%

 

When 0.0% is set, it operates as 

0.1%.

 

Heating-side ON/OFF control applies 

when 0.0% in Heating/cooling control

5.0%

EASY

(I)

Integral time

 

Heating-side integral time 

(in Heating/cooling control)

OFF: Disable

 

1 to 6000 s

240 s

(D)

Derivative time

 

Heating-side derivative time 

(in Heating/cooling control)

OFF: Disable

 

1 to 6000 s

60 s

(OH)

Control output high limit

 

Heating-side control 

output high limit (in 

Heating/cooling control)

-4.9 to 105.0%, (OL<OH)

 

In Heating/cooling control: 0.1 to 

105.0% (OL<OH)

100.0%

(OL)

Control output low limit

 

Heating-side control 

output low limit (in Heat-

ing/cooling control)

-5.0 to 104.9%, (OL<OH), SD: Tight 

shut 

In Heating/cooling control: 0.0 to 

104.9% (OL<OH)

0.0%

(MR)

Manual reset

Enabled when integral time is OFF.

 

The manual reset value equals the 

output value when PV = SP.

 

-5.0 to 105.0%

50.0%

(HYS)

Hysteresis (in ON/OFF 

control, Position 

proportional control, or 

Two-position two-level 

control)

 

Heating-side ON/OFF 

control hysteresis (in 

Heating/cooling control)

In ON/OFF control or Two-position 

two-level control: 0.0 to 100.0% of 

PV input range span (EUS)

 

In Heating/cooling control or Position 

proportional control: 0.0 to 100.0%

In 

ON/OFF 

control 

or 

Two-

position 

two-level 

control: 

0.5 % of 

PV input 

range 

span 

In Heat

-

ing/

cooling 

control

or

Position

proportional

control: 

0.5 %

(SU.HY)

Sub-hysteresis (in 

Two-position two-level 

control)

0.0 to 100.0% of PV input range 

span (EUS)

0.5 % 

of PV 

input 

range 

span

(HY.UP)

Upper-side hysteresis 

(in ON/OFF control)

0.5 % 

of PV 

input 

range 

span

(HY.LO)

Lower-side hysteresis 

(in ON/OFF control)

0.5 % 

of PV 

input 

range 

span

(DR)

Direct/reverse action 

switch

RVS: Reverse action

DIR: Direct action

RVS

STD

(SU.DR)

Sub-direct/reverse 

action switch (in Two-

position two-level 

control)

DIR

(Pc)

Cooling-side propor-

tional band

0.0 to 999.9%

(Cooling-side ON/OFF control ap-

plies when 0.0% in Heating/cooling 

control)

5.0%

EASY

(Ic)

Cooling-side integral 

time

OFF: Disable

1 to 6000 s

240 s

(Dc)

Cooling-side derivative 

time

OFF: Disable

1 to 6000 s

60 s

(OHc)

Cooling-side control 

output high limit

0.1 to 105.0%, (OLc<OHc) 

100.0%

(OLc)

Cooling-side control 

output low limit

0.0 to 104.9%, (OLc<OHc) 

0.0%

(HYSc)

Cooling-side ON/OFF 

control hysteresis

0.0 to 100.0%

0.5%

(DB)

Output dead band (in 

Heating/cooling control 

or Position proportional 

control)

In Heating/cooling control: -100.0 to 

50.0% 

In Position proportional control: 1.0 

to 10.0%

3.0%

(PO)

Preset output 

Heating-side preset 

output (in Heating/cool-

ing control)

In STOP mode, fixed control output 

can be generated. In Position propor-

tional control, Valve opening can be 

set; -5.0 to 105.0%

0.0%

(SU.PO)

Sub-preset output (in 

Two-position two-level 

control)

In STOP mode, fixed sub-control 

output can be generated.

0%, 100%

0%

(POc)

Cooling-side preset 

output

In STOP mode, cooling-side fixed 

control output can be generated.

-5.0 to 105.0%

0.0%

For the PID setting parameter, 8 groups are displayed for the factory default. 

The number of groups can be changed by the setup parameter PIDG. (number of PID 

groups). To change the number of PID groups, see User's Manual (IM 05P01C31-01EN).

Operation

Guide

UT55A, UT52A

Digital Indicating Controller 

(Panel Mounting Type)

Operation Guide for Single-loop Control

Yokogawa Electric Corporation

Parameters

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

This operation guide describes the functions of parameters briefly. The parameter 

symbols listed are in the order shown on the display in each group of menu symbols. 

In addition, each parameter table has a “User Setting” column, where you can record 

your setpoints when setting them in the controller. The scrolling guide is displayed on PV 

display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.

«Detailed Code Model»

Summary of Contents for UTAdvanced UT52A

Page 1: ...ish are available for the guide display 2 For heating cooling output both Output 1 and Output 2 should be specified Not available when Output 2 is N For position proportional output specify P for Outp...

Page 2: ...o 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrument range 1 digit DC voltage for high input impedance 0 000 to 1 250...

Page 3: ...208 Can be used for retransmission output or 15 V DC loop power supply when current voltage pulse output is not used for control output Current output range can be changed In Position proportional ty...

Page 4: ...nal contact output Transistor contact rating 24 V DC 50 mA DO22 DO21 DO23 DO24 DO25 COM Alarm 4 PV low limit Common UT Option code Y2 307 308 309 310 311 312 Function can be assigned to the terminals...

Page 5: ...ting Software is on the top of the unit 2 Setup Procedure The following flowchart shows the setup procedure for UT55A and UT52A Install and wire a controller Monitoring and control of regular operatio...

Page 6: ...type is displayed Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY...

Page 7: ...int has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual IM 05P01C31 01EN The MAN lamp goes off which means that the auto t...

Page 8: ...function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized...

Page 9: ...4 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP devia...

Page 10: ...king state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters whic...

Page 11: ...ge O1RS Retransmission output type of OUT current output Same as RTS OFF STD O1RH Maximum value of retransmission output scale of OUT current output When O1RS PV1 SP1 PV2 SP2 TSP1 TSP2 PV RSP AIN2 or...

Page 12: ...ion Set an I relay number For the items other than below see Communication User s Manual Ex Set the number 4353 for AL1 S to use the alarm 1 Set OFF to disable the function No function OFF Alarm 1 435...

Reviews: