IM 05P08D31-11EN  page 2/12

4.  Hardware Specifications

WARNING 

This instrument is for Measurement Category No.1.

Do not use it for measurements in locations falling under Measure-

ment Categories No.2, No.3, and No.4.

Internal Wiring

Outlet

Entrance IV

Cable

III

T

O( I )

II

Category

IEC/EN/CSA

/

UL 

61010-1

EN 61010-2-030

Remarks

No.1

Measurement 

Category I

O (Other)

For measurements performed on circuits not direct

-

ly connected to MAINS.

No.2

Measurement 

Category II

Measurement 

Category II

For measurements performed on circuits directly 

connected to the low-voltage installation.

No.3

Measurement 

Category III

Measurement 

Category III

For measurements performed in the building instal-

lation.

No.4

Measurement 

Category IV

Measurement 

Category IV

For measurements performed at the source of the 

low-voltage installation.

  Input Specifications

●Universal Input (Equipped as standard)

•  Number of inputs: 1

•  Input type, instrument range, and measurement accuracy: See the table below,

Input Type

 Instrument Range

Accuracy

ºC

ºF

Thermo-

couple

K

-270.0 to 1370.0ºC -450.0 to 2500.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C 

 

±2% of instrument range ±1 digit for 

less than -200.0°C of thermocouple K 

±1% of instrument range ±1 digit for 

less than -200.0°C of thermocouple T

-270.0 to  1000.0ºC -450.0 to 2300.0ºF

-200.0 to  500.0ºC -200.0 to 1000.0ºF

J

-200.0 to 1200.0ºC -300.0 to 2300.0ºF

T

-270.0 to 400.0ºC

-450.0 to 750.0ºF

0.0 to  400.0ºC

-200.0 to 750.0ºF

B

0.0 to 1800.0ºC

32 to 3300ºF

±0.15% of instrument range ±1 digit 

for 400°C or more

 

±5% of instrument range ±1 digit for 

less than 400°C

S

0.0 to 1700.0ºC

32 to 3100ºF

±0.15% of instrument range ±1 digit 

R

0.0 to 1700.0ºC

32 to 3100ºF

N

-200.0 to 1300.0ºC -300.0 to 2400.0ºF

±0.1% of instrument range ±1 digit

±0.25% of instrument range ±1 digit 

for less than 0°C

E

-270.0 to 1000.0ºC -450.0 to 1800.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C

 

±1.5% of instrument range ±1 digit for 

less than -200.0°C of thermocouple E.

L

-200.0 to 900.0ºC

-300.0 to 1600.0ºF

U

-200.0 to 400.0ºC

-300.0 to 750.0ºF

0.0 to 400.0ºC

-200.0 to 1000.0ºF

W

0.0 to 2300.0ºC

32 to 4200ºF

±0.2% of instrument range ±1 digit 

(Note 2)  

Platinel 2

0.0 to 1390.0ºC

32.0 to 2500.0ºF ±0.1% of instrument range ±1 digit  

PR20-40

0.0 to 1900.0ºC

32 to 3400ºF

±0.5% of instrument range ±1 digit for 

800°C or more 

 

Accuracy is not guaranteed for less 

than 800°C.  

W97Re3-

W75Re25

0.0 to 2000.0ºC

32 to 3600ºF

±0.2% of instrument range ±1 digit  

RTD

JPt100

-200.0 to 500.0ºC

-300.0 to 1000.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-150.00 to  150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Pt100

-200.0 to 850.0ºC

-300.0 to 1560.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-200.0 to 500.0ºC

-300.0 to 1000.0ºF

-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Standard signal

0.400 to 2.000 V

±0.1% of instrument range ±1 digit

1.000 to 5.000 V

4.00 to 20.00 mA

DC voltage/current

0.000 to 2.000 V

0.00 to 10.00 V

0.00 to 20.00 mA

-10.00 to 20.00 mV

0.0 to 100.0 mV

The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power 

frequency at 50/60 Hz.

Note 

1:  ±0.3°C ±1 digit in the range between 0 and 100°C, ±0.5°C ±1 digit in the range 

 

  between -100 and 200°C.

Note 2:  W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988

• Input sampling (control) period: 200 ms

• Burnout detection:

    Functions at TC, RTD, and standard signal.

    Upscale, downscale, and off can be specified.

    For standard signal, burnout is determined to have occurred if it is 0.1 V or 0.4

 

  mA or less.

• Input bias current: 0.05 µA (for TC or RTD)

• Measured current (RTD): About 0.16 mA

• Input resistance:

    TC or mV input: 1 MΩ or more

    V input: About 1 MΩ

    mA input: About 250 Ω

• Allowable signal source resistance:

    TC or mV input: 250 Ω or less

   

Effects of signal source resistance: 0.1 µV/Ω or less

    DC voltage input: 2 kΩ or less

   

Effects of signal source resistance: About 0.01%/100 Ω

•  Allowable wiring resistance:

    RTD input: Max. 150 Ω/wire  (The conductor resistance between the three wires 

 

  shall be equal.)

    Wiring resistance effect: ±0.1ºC/10 Ω

•  Allowable input voltage/current:

    TC, mV, mA and RTD input: ±10 V DC

    V input: ±20 V DC

    mA input: ±40 mA

•  Noise rejection ratio:

    Normal mode: 40 dB or more (at 50/60 Hz)

    Common mode: 120 dB or more (at 50/60 Hz) 

    For 100-240 V AC, the power frequency can be set manually. Automatic

 

  detection is also available.

    For 24 V AC/DC, the power frequency can be set manually.

•  Reference junction compensation error:

    ±1.0ºC (15 to 35ºC), ±1.5ºC (-10 to 15ºC and 35 to 50ºC)

•  Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD

  Contact Input Specifications

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type: No-voltage contact input or transistor contact input

•  Input contact rating: 12 V DC, 10 mA or more

    Use a contact with a minimum on-current of 1 mA or less.

•  ON/OFF detection:

    No-voltage contact input:

   

Contact resistance of 1 kΩ or less is determined as “ON” and contact

   

resistance of 50 kΩ or more as “OFF.”

    Transistor contact input:

   

Input voltage of 2 V or less is determined as “ON” and leakage current must 

   

not exceed 100 µA when “OFF.”

•  Minimum status detection hold time: Control 50 ms

•  Use: SP switch, operation mode switch, and event input

  Analog Output Specifications (OUT, OUT2)

•  Number of outputs:

    Control output: 2

•  Output type: Current output or voltage pulse output

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 Ω or less

•  Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)

    The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

 

  and power frequency at 50/60 Hz.

•  Voltage pulse output:

    Use: Time proportional output

    On-voltage: 12 V or more/load resistance of 600 Ω or more

    Off-voltage: 0.1 V DC or less

    Time resolution: 10 ms or 0.1% of output, whichever is larger

  Relay Contact Output Specifications (OUT, OUT2)

•  Contact type and number of outputs:1a; 2 points (common is independent)

•  Contact rating: 240 V AC, 3A or 30 V DC, 3A (resistance load)

•  Use: Time proportional output, ON/OFF output

•  Time resolution of control output: 10 ms or 0.1% of output, whichever is larger

Note:  The control output should always be used with a load of 10 mA or more.

  Alarm Relay Contact Output Specifications (ALM)

•  Contact type and number of outputs: 3 points (common is independent)

•  Contact rating: 240 V AC, 1A or 30 V DC, 1 A (resistance load)

•  Use: Alarm output, FAIL output, etc.

Note:  The alarm output should always be used with a load of 1 mA or more.

  Heater Break Alarm Specifications (for /HA option)

•  Number of inputs: 2

•  Number of outputs: 2 (transistor contact output)

•  Use: Measures the heater current using an external current transformer (CT) and 

generates a heater break alarm when the measured value is less than the break 

detection value.

•  Current transformer input resistance: About 9.4 Ω

• 

Current transformer input range: 0.0 to 0.1 Arms (0.12 Arms or more cannot be applied.)

•  Heater current setting range: OFF, 0.1 to 300.0 Arms

    Heater current measured value display range: 0.0 to 360.0 Arms

 

Note: The CT ratio can be set. CT ratio setting range: 1 to 3300

•  Recommended CT: CT from U.R.D., Ltd.

    CTL-6-S-H: CT ratio 800, measurable current range: 0.1 to 80.0 Arms

    CTL-12L-30: CT ratio 3000, measurable current range: 0.1 to 180.0 Arms

•  Heater current measurement period: 200 ms

•  Heater current measurement accuracy: ±5% of current transformer input range 

span ± 1digit (CT error is not included.)

• 

Heater current detection resolution: Within 1/250 of current transformer input range span

•  Break detection On-time: Min. 0.2 second (for time proportional output)

■  Safety and EMC Standards

•  Safety: 

  Compliant with IEC/EN 61010-1 (CE), IEC/EN 61010-2-201 (CE), IEC/EN 61010-

2-030 (CE), approved by CAN/CSA C22.2 No. 61010-1 (CSA), approved by UL 

61010-1.

  Installation category: II

  Pollution degree: 2

  Measurement category: I (CAT I) (UL, CSA)

  

 

    

O (Other) (CE)

  Rated measurement input voltage: Max. 10 V DC

  Rated transient overvoltage: 1500 V (*)

 

* This is a reference safety standard value for measurement category I of CSA/UL 61010-

1, and for measurement category O of IEC/EN 61010-2-030. This value is not necessarily a 

guarantee of instrument performance.

•  EMC standards:

  Compliant with CE marking

  EN 61326-1 Class A, Table 2 (For use in industrial locations),

  EN 61326-2-3

 

* The instrument continues to operate at a measurement accuracy of within ±20% of the 

range during testing.

  EN 55011 Class A, Group 1

  EN 61000-3-2 Class A

  EN 61000-3-3

  EMC Regulatory Arrangement in Australia and New Zealand (for all model includ-

ing LL50A)

  EN 55011 Class A, Group 1

•  KC marking:

  Electromagnetic wave interference prevention standard, electromagnetic wave 

protection standard compliance

■  Construction, Installation, and Wiring

•  Dust-proof and drip-proof: IP66 (for front panel) (Not available for side-by-side 

close mounting.)

•  Material: Polycarbonate (Flame retardancy: UL94V-0)

•  Case color: White (Light gray) or Black (Light charcoal gray)

•  Weight: 0.5 kg or less

•  External dimensions (mm): 48 (W) × 96 (H) × 65 (depth from the panel face)

    (Depth except the projection on the rear panel)

•  Installation: Direct panel mounting; mounting bracket, one each for upper and 

lower mounting

•  Panel cutout dimensions (mm): 45

+0.6/0

 (W) × 92

+0.8/0

 (H)

• 

Mounting attitude: Up to 30 degrees above the horizontal. No downward titling allowed.

•  Wiring: M3 screw terminal with square washer (for signal wiring and power wiring)

■  Power Supply Specifications and Isolation 

•  Power supply:

    Rated voltage: 100-240 V AC (+10%/-15%), 50/60 Hz

                  

24 V AC/DC (+10%/-15%) (for /DC option)

•  Power consumption: 15 VA (DC:7 VA, AC: 11 VA if /DC option is specified)

•  Data backup: Nonvolatile memory

•  Power holdup time: 20 ms (for 100 V AC drive)

•  Withstanding voltage

 

Between primary terminals and secondary terminals: 2300 V AC for 1 minute (UL, CSA)

  Between primary terminals and secondary terminals: 3000 V AC for 1 minute (CE)

    Between primary terminals: 1500 V AC for 1 minute

    Between secondary terminals: 500 V AC for 1 minute

          (Primary terminals: Power* and relay output terminals; Secondary terminals: 

 

        Analog I/O signal terminals, contact input terminals, communication terminals 

 

        and functional grounding terminals.)

 

*: Power terminals for 24V AC/DC models are the secondary terminals.

•  Insulation resistance: Between power supply terminals and a grounding terminal 

20 MΩ or more at 500 V DC

•  Isolation specifications

The circuits divided by lines are insulated mutually.

Control (analog) output terminal (OUT, OUT2)

(not isolated between the analog output terminals)

PV1 (universal) input terminal

PV2 (universal) input terminal

Control relay (2 a-contact) output terminal (OUT, OUT2)

Alarm-1 relay (a-contact) output terminal

Alarm-2 relay (a-contact) output terminal

Alarm-3 relay (a-contact) output terminal

Internal 

circuits

Power 

supply

Contact input terminal (3 points)

RS485 communication terminal
Current transformer input terminal

■  Environmental Conditions

Normal Operating Conditions:

•  Ambient temperature: -10 to 50°C (side-by-side mounting: -10 to 40 °C)

•  Ambient humidity: 20 to 90% RH (no condensation allowed)

•  Magnetic field: 400 A/m or less

•  Continuous vibration at 5 to 9 Hz: Half amplitude of 1.5 mm or less, 1oct/min for 90 

minutes each in the three axis directions

  Continuous vibration at 9 to 150 Hz: 4.9 m/s

2

 or less, 1oct/min for 90 minutes each 

in the three axis directions

•  Short-period vibration: 14.7 m/s

2

, 15 seconds or less

•  Shock: 98 m/s

2

 or less, 11 ms

•  Altitude: 2000 m or less above sea level

•  Warm-up time: 30 minutes or more after the power is turned on

•  Startup time: Within 10 seconds

 

*:  The LCD (a liquid crystal display) is used for a display portion of this product.

 

  The LCD has a characteristic that the display action becomes late at the low 

 

  temperature. However, the control function is not affected. 

Transportation and Storage Conditions:

•  Temperature: -25 to 70ºC

•  Temperature change rate: 20ºC/h or less

•  Humidity: 5 to 95% RH (no condensation allowed)

Effects of Operating Conditions

•  Effect of ambient temperature:

    Voltage or TC input: ±1 µV/ºC or ±0.01% of F.S./ºC, whichever is larger

    Current input:  ±0.01% of F.S./ºC

    RTD input: ±0.05ºC/ºC (ambient temperature) or less

    Analog output: ±0.02% of F.S./ºC or less

•  Effect of power supply voltage fluctuation

    Analog input: ±0.05% of F.S. or less

    Analog output: ±0.05% of F.S. or less

     (Each within rated voltage range)

Summary of Contents for UT32A-D

Page 1: ...strument has option S and you are not in the possession of FX1 Model code S or IM Model code S where Model code means for example UT55A Accessories sold separately The following is an accessory sold s...

Page 2: ...Time proportional output ON OFF output Time resolution of control output 10 ms or 0 1 of output whichever is larger Note The control output should always be used with a load of 10 mA or more Alarm Re...

Page 3: ...JIS C 1610 For thermocouple input PV input and remote input with direct input shielded compensating lead wire of cross sectional area less than or equal to 0 75 mm2 is recommended If the cross sectio...

Page 4: ...IM 05P08D31 11EN page 4 12 Intentionally blank Intentionally blank...

Page 5: ...l type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the cont...

Page 6: ...setpoint PV SP or Target SP Hysteresis PV Deviation setpoint SP or Target SP Deviation setpoint PV Hysteresis Hysteresis Open unlit Closed lit SP or Target SP PV Deviation setpoint Hysteresis SP or Ta...

Page 7: ...range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp b...

Page 8: ...rror Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repair Rightmost decimal point on Symbol display blinks Faulty FRAM Data writing storing t...

Page 9: ...eset rate of change The UPR DNR and TMU are used in combination Oper ating conditions 1 MAN AUTO 2 STOP AUTO 3 Power on 4 SP number change 5 SP change OFF ON OFF LP1 LP2 Alarm Function Setting Paramet...

Page 10: ...key to move to the next parameter To change and set the parameter setting press the SET ENTER key to start the set point blinking The blinking state allows you to make changes setting mode Use the Up...

Page 11: ...0 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI Parity NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits...

Page 12: ...s in this manual All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies Authorised Representative in the EEA Yokogawa Europe BV Address...