background image

IM 05D01D02-01E (2)

UT350 Standard Type (Model UT350-0

 or UT350-3

) or Heating/Cooling type(Model UT350-2

)

1

2

Relay contact output 

3

Control output

NC

NO

COM

Contact rating: 250 V AC, 3 A 
 

 30 V DC, 3 A (resistance load) 

Note: Select this option from 

the OT parameter.

Time proportional PID 

   relay contact output is 
   configured at factory
   before shipment. 

23

24

RS-485 communication 

Wiring can only be carried out

   for controllers with 
   communication  functions. 
   Maximum baud rate: 9600 bps 

25

26

27

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

24 V DC loop 

power supply

Wiring can only  be carried 

   out for controllers with 
   24 V DC loop power supply. 

21.6-28.0VDC
(30 mA DC max.) 

21

22

+

-

12

13

 TC input

11

12

RTD input

13

12

13

mV/V input

A

b

B

-

+

-

+

Initial Settings User’s Manual

12

13

Note: Connecting a 250 

 resistor to the terminals is 

          optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal 
            lugs)

When receiving 4-20 mA DC current signals, 

   set the PV input type to 1-5 V DC (setpoint “41”).

 Receiving 4-20 mA DC Current 

    Signals with the Controller

250 

4-20mA

PV input

Not configured at factory before shipment

   See                                                           , 

       for more information.

-

+

14

15

Retransmission output 

4-20 mA DC

14

15

 15 V DC loop power supply 

14.5-18.0VDC
(21 mA DC max.) 

PV retransmission is configured at factory

   before shipment. 

Load resistance: 600 

 or less

*

 If 15 V DC loop power supply is used, 

   retransmission output cannot be used.

-

+

-

+

16

17

Current / voltage 

pulse output 

4-20 mA DC, 
voltage pulse 
(12 V)

Control output 

+

-

Note:Select this 

option from the 
OT parameter.

6

5

Alarm output

4

7

AL1

AL2

AL3

COM

Relay contact rating: 240 V AC, 1 A 
 

30 V DC, 1 A (resistance load) 

Relay

Alarm-1 output

Alarm-2 output

Alarm-3 output 

Common

UT

8

9

Power supply 

10

L

N

Allowable range: 100 to 240 V AC (

10%)

(free voltage) 
50/60 Hz shared 

Power supply 

CAUTION

21

22

23

24

25

26

27

28

29

30

11

12

13

14

15

16

17

18

19

20

1

2

3

4

5

6

7

8

9

10

Before carrying out wiring, turn off the power to 
the controller and check that cables to be connected 
are not alive with a tester or the like because 
there is a possibility of electric shock. 

OT=0 (factory-set default)

Time proportional control

Relay output  (terminals    ,     and    )

OT=1

Correspondence between parameter OT and control output types

Time proportional control

Voltage pulse output (terminals     and     )

OT=2

Current output 

(terminals     and     )

OT=3

On-off control

Relay output (terminals    ,     and    )

*

 OT is a setup parameter. You can change the settings of the parameter OT to change the control output type.  

   See                                                         , for more information.

Initial Settings User’s Manual

1

2

3

16

17

16

17

1

2

3

When switching target

 setpoints 1 to 4:

DI1

DI2

1.SP 2.SP3.SP 4.SP

OFF

OFF

OFF

ON

ON

ON

OFF

ON

Contact rating: 12 V DC, 10 mA or more

Correspondence between parameter DIS and external contact input functions

When DIS=4 

DI1

DI2

COM

Common 

When DIS=3

2.SP when DI1=ON 
1.SP when DI1=OFF

STOP when DI2=ON 
RUN when DI2=OFF 

Common 

When DIS=2

Hides the LOCK parameter when DI1=ON.

Shows the LOCK parameter when DI1=OFF.

Common 

When DIS=1 (Factory-set default) 

2.SP when DI1=ON 
1.SP when DI1=OFF

AUTO when DI2=ON
MAN when DI2=OFF

Common 

When DIS=OFF

No function

No function

Common 

DI1

DI2

COM

+5V

+5V

Contact

Transistor contact 

 *

 DIS is a setup parameter. 

Changing DIS setpoint allows you to change the function of external contact input. 

*

 This wiring is only 

   possible for a controller 
   with a heater burnout 
   alarm. 

29

28

Heater current 
detection input

30

CT2

CT1

COM

CT

CT

No function

19

18

20

UT

19

18

20

Note: External Contact Input

If the power is turned on when the external contact input is OFF, 
the mode (SP.no or A/M) existing before the power is turned 
off will be continued. (except for RUN/STOP)

UT350 Heating/Cooling Type (Model UT350-2

)

Heating-side control output 

1

2

3

NC

NO

COM

Relay contact output 

Time proportional PID relay contact output 

   is configured at factory before shipment.

Available if 4, 7 or 10 is set in the OT 

   (Control Output Type) setup parameter.  

Contact rating: 250 V AC, 3 A 
 

 30 V DC, 3 A (resistance load) 

23

24

25

26

27

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

Wiring can only be carried out

   for controllers with communication 
   functions. 
   Maximum baud rate: 9600 bps 

RS-485 communication 

12

13

11

12

13

12

13

A

b

B

+

-

+

-

 TC input

RTD input

mV/V input

12

13

When receiving 4-20 mA DC current signals, 

   set the PV input type to 1-5 V DC (setpoint “41”).

 Receiving 4-20 mA DC Current 

    Signals with the Controller

250 

4-20mA

-

+

Note: Connecting a 250 

 resistor to the terminals is 

          optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal 
            lugs)

Initial Settings User’s Manual

PV input

Not configured at factory before shipment

   See                                                           , 

       for more information.

Heating-side control output

16

17

Current / voltage 

pulse output 

4-20 mA DC, 
voltage pulse
(12 V) 

+

-

Available if 5, 6, 8, 9, 11 

   or 12 is set in the OT 
   (Control Output Type) 
   setup parameter.

14

15

14

15

+

-

+

-

Retransmission output 

4-20 mA DC

 15 V DC loop power supply 

14.5-18.0VDC
(21 mA DC max.) 

14

15

+

-

Cooling-side control output

4-20 mA DC,
voltage pulse (12 V) 

8

9

10

L

N

CAUTION

Before carrying out wiring, turn off the power to the 
controller and check that cables to be connected 
are not alive with a tester or the like because there 
is a possibility of electric shock. 

Power supply 

Power supply 

Allowable range: 100 to 240 V AC (

10%)

(free voltage) 
50/60 Hz shared 

6

5

4

7

AL1

AL2

AL3

COM

Relay

Alarm output/cooling-side control output

Alarm-1 output

Alarm-2 output

Alarm-3 output 

or cooling-side control 

output (Note) 

Common

Relay contact rating: 240 V AC, 1 A 
 

30 V DC, 1 A (resistance load) 

UT

When switching target

 setpoints 1 to 4:

DI1

DI2

1.SP 2.SP3.SP 4.SP

OFF

OFF

OFF

ON

ON

ON

OFF

ON

Contact rating: 12 V DC, 10 mA or more

Correspondence between parameter DIS and external contact input functions

When DIS=4 

DI1

DI2

COM

Common 

When DIS=3

2.SP when DI1=ON 
1.SP when DI1=OFF

STOP when DI2=ON 
RUN when DI2=OFF 

Common 

When DIS=2

Hides the LOCK parameter when DI1=ON.

Shows the LOCK parameter when DI1=OFF.

Common 

When DIS=1 (Factory-set default) 

2.SP when DI1=ON 
1.SP when DI1=OFF

AUTO when DI2=ON
MAN when DI2=OFF

Common 

When DIS=OFF

No function

No function

Common 

DI1

DI2

COM

+5V

+5V

Contact

Transistor contact 

 *

 DIS is a setup parameter. 

Changing DIS setpoint allows you to change the function of external contact input. 

No function

19

18

20

UT

19

18

20

OT=4 (factory-set default)

OT=5

Correspondence between parameter OT and heating-side/cooling-side output types 

OT=6

OT=7

OT=8

OT=9

OT=10

OT=11

OT=12

*

 OT is a setup parameter. You can change the settings of the parameter OT to change the control output type.  

   See                                                        , for more information.

The control output types, “relay output” and “voltage pulse output” shown in the table above refer to those of time proportional control.  
To change the type to a relay output for on-off control, select “Relay Terminals” and change the setpoint of the proportional band to “0.”

Heating side: Relay output

(terminals    ,    and    )

Cooling side: Relay output

(terminals    and    )

1

2

3

Heating side: Voltage pulse output

(terminals    and    )

Cooling side: Relay output

(terminals    and    )

16

17

Heating side: Current output

(terminals    and    )

Cooling side: Relay output

(terminals    and    )

16

17

14

15

14

15

14

15

14

15

14

15

14

15

Heating side: Relay output

(terminals    ,    and    )

Cooling side: Voltage pulse output

(terminals    and    )

1

2

3

Heating side: Relay output

(terminals    ,    and    )

Cooling side: Current output

(terminals    and    )

1

2

3

Heating side: Voltage pulse output

(terminals    and    )

Cooling side: Voltage pulse output

(terminals    and    )

16

17

Heating side: Current output

(terminals    and    )

Cooling side: Voltage pulse output

(terminals    and    )

16

17

Heating side: Voltage pulse output

(terminals    and    )

Cooling side: Current output

(terminals    and    )

16

17

Heating side: Current output

(terminals    and    )

Cooling side: Current output

(terminals    and    )

16

17

Initial Settings User’s Manual

4

7

4

7

4

7

21

22

23

24

25

26

27

28

29

30

11

12

13

14

15

16

17

18

19

20

1

2

3

4

5

6

7

8

9

10

Note: The cooling-side control output is selected if 4, 5 or 

6 is set in the OT (Control Output Type) setup 
parameter. The alarm-3 output is not available. 
The controller is factory-set to the cooling-side control 
output (time proportional PID relay contact output).

PV retransmission is configured at factory before shipment. 

If 15 V DC loop power supply is used, 

   retransmission output cannot be used.

The retransmission output and 15 V DC 

   loop power supply are not available 
   if the cooling-side control output is set to 
   “current output” and “voltage pulse output.” 

29

28

Heater current 
detection input

30

CT2

CT1

COM

CT

CT

*

This wiring is only possible 

for a controller with a heater 
burnout alarm.

Note: External Contact Input

If the power is turned on when 
the external contact input is OFF, 
the mode (SP.no or A/M) existing 
before the power is turned off will 
be continued. (except for RUN/
STOP)

6. Terminal Wiring Diagrams

UT320 Standard Type (Model UT320-0

 or UT320-3

) or Heating/Cooling type(Model UT320-2

)

1

2

Relay contact output 

3

Control output

NC

NO

COM

Contact rating: 250 V AC, 3 A 
 

 30 V DC, 3 A (resistance load) 

Note: Select this option from 

the OT parameter.

Time proportional PID 

   relay contact output is 
   configured at factory
   before shipment. 

23

24

RS-485 communication 

Wiring can only be carried out

   for controllers with 

communication functions. 

   Maximum baud rate: 9600 bps 

25

26

27

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

24 V DC loop
power supply

Wiring can only  be carried 

   out for controllers with 
   24 V DC loop power supply. 

21.6-28.0VDC
(30 mA DC max.) 

21

22

+

-

8

9

Power supply 

10

L

N

Allowable range: 100 to 240 V AC (

10%)

(free voltage) 
50/60 Hz shared 

Power supply 

CAUTION

Before carrying out wiring, turn off the power 
to the controller and check that cables to be 
connected are not alive with a tester or the like 
because there is a possibility of electric shock. 

6

5

Alarm output

4

7

AL1

AL2

AL3

COM

Relay contact rating: 240 V AC, 1 A 
 

30 V DC, 1 A (resistance load) 

Relay

Alarm-1 output

Alarm-2 output

Alarm-3 output 

Common

UT

16

17

Current / voltage 

pulse output 

4-20 mA DC, 
voltage pulse 
(12 V)

Control output 

+

-

Note:Select this option 

from the OT 
parameter.

12

13

 TC input

11

12

RTD input

13

12

13

mV/V input

A

b

B

-

+

-

+

Initial Settings User’s Manual

12

13

Note: Connecting a 250 

 resistor to the terminals is 

          optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal 
            lugs)

When receiving 4-20 mA DC current signals, 

   set the PV input type to 1-5 V DC (setpoint “41”).

 Receiving 4-20 mA DC Current 

    Signals with the Controller

250 

4-20mA

PV input

Not configured at factory before shipment

   See                                                           , 

       for more information.

-

+

14

15

Retransmission output 

4-20 mA DC

14

15

 15 V DC loop power supply 

14.5-18.0VDC
(21 mA DC max.) 

PV retransmission is configured at factory

   before shipment. 

Load resistance: 600 

 

or less

*

 If 15 V DC loop power supply is used, 

   retransmission output cannot be used.

-

+

-

+

*

 This wiring is only 

   possible for a controller 
   with a heater burnout 
   alarm. 

29

28

Heater current 
detection input

30

CT2

CT1

COM

CT

CT

OT=0 (factory-set default)

Time proportional control

Relay output  (terminals    ,     and    )

OT=1

Correspondence between parameter OT and the control output types

Time proportional control

Voltage pulse output (terminals     and     )

OT=2

Current output 

(terminals     and     )

OT=3

On-off control

Relay output (terminals    ,     and    )

*

 OT is a setup parameter. You can change the settings of the parameter OT to change the control output type.  

   See                                                         , for more information.

Initial Settings User’s Manual

1

2

3

16

17

16

17

1

2

3

When switching target

 setpoints 1 to 4:

DI1

DI2

1.SP 2.SP3.SP 4.SP

OFF

OFF

OFF

ON

ON

ON

OFF

ON

Contact rating: 12 V DC, 10 mA or more

Correspondence between parameter DIS and external contact input functions

When DIS=4 

DI1

DI2

COM

Common 

When DIS=3

2.SP when DI1=ON 
1.SP when DI1=OFF

STOP when DI2=ON 
RUN when DI2=OFF 

Common 

When DIS=2

Hides the LOCK parameter when DI1=ON.

Shows the LOCK parameter when DI1=OFF.

Common 

When DIS=1 (Factory-set default) 

2.SP when DI1=ON 
1.SP when DI1=OFF

AUTO when DI2=ON
MAN when DI2=OFF

Common 

When DIS=OFF

No function

No function

Common 

DI1

DI2

COM

+5V

+5V

Contact

Transistor contact 

 *

 DIS is a setup parameter. 

Changing DIS setpoint allows you to change the function of external contact input. 

No function

19

18

20

UT

19

18

20

1

2

3

4

5

6

7

8

9

10

21

22

23

24

25

26

27

28

29

30

11

12

13

14

15

16

17

18

19

20

Note: External Contact Input

If the power is turned on when the external contact input is OFF, 
the mode (SP.no or A/M) existing before the power is turned 
off will be continued. (except for RUN/STOP)

UT320 Heating/Cooling Type (Model UT320-2

)

Heating-side control output 

1

2

3

NC

NO

COM

Relay contact output 

Time proportional PID relay contact 

   output is configured at factory
   before shipment. 

Available if 4, 7 or 10 is set in the OT 

   (Control Output Type) setup parameter.

Contact rating: 250 V AC, 3 A 
 

 30 V DC, 3 A (resistance load) 

23

24

25

26

27

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

Wiring can only be carried out

   for controllers with communication 
   functions. 
   Maximum baud rate: 9600 bps 

RS-485 communication 

12

13

11

12

13

12

13

A

b

B

+

-

+

-

 TC input

RTD input

mV/V input

12

13

When receiving 4-20 mA DC current signals, 

   set the PV input type to 1-5 V DC (setpoint “41”).

 Receiving 4-20 mA DC Current 

    Signals with the Controller

250 

4-20mA

-

+

Note: Connecting a 250 

 resistor to the terminals is 

          optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal 
            lugs)

Initial Settings User’s Manual

PV input

Not configured at factory before shipment

   See                                                           , 

       for more information.

14

15

14

15

+

-

+

-

Retransmission output 

4-20 mA DC

 15 V DC loop power supply 

14.5-18.0VDC
(21 mA DC max.) 

Cooling-side control output

4-20 mA DC,
voltage pulse (12 V)

PV retransmission is configured at factory before shipment. 

If 15 V DC loop power supply is used, 

   retransmission output cannot be used.

The retransmission output and 15 V DC 

   loop power supply are not available 
   if the cooling-side control output is set to 
   “current output” and “voltage pulse output.” 

Heating-side control output

16

17

Current / voltage 

pulse output 

4-20 mA DC, 
voltage pulse
(12 V) 

+

-

Available if 5, 6, 8, 9, 

  11 or 12 is set in the OT 
  (Control Output Type) 
  setup parameter. 

When switching target

 setpoins 1 to 4:

DI1

DI2

1.SP 2.SP3.SP 4.SP

OFF

OFF

OFF

ON

ON

ON

OFF

ON

Contact rating: 12 V DC, 10 mA or more

Correspondence between parameter DIS and external contact input functions

When DIS=4 

DI1

DI2

COM

Common 

When DIS=3

2.SP when DI1=ON 
1.SP when DI1=OFF

STOP when DI2=ON 
RUN when DI2=OFF 

Common 

When DIS=2

Hides the LOCK parameter when DI1=ON.

Shows the LOCK parameter when DI1=OFF.

Common 

When DIS=1 (Factory-set default) 

2.SP when DI1=ON 
1.SP when DI1=OFF

AUTO when DI2=ON
MAN when DI2=OFF

Common 

When DIS=OFF

No function

No function

Common 

DI1

DI2

COM

+5V

+5V

Contact

Transistor contact 

 *

 DIS is a setup parameter. 

Changing DIS setpoint allows you to change the function of external contact input. 

No function

19

18

20

UT

19

18

20

Note: The cooling-side control output 

is selected if 4, 5 or 6 is set in 
the OT (Control Output 
Type) setup parameter. 
The alarm-3 output is not 
available. The controller is 
factory-set to the cooling-side 
control output (time proportional 
PID relay contact output).

8

9

10

L

N

CAUTION

Before carrying out wiring, turn off the power 
to the controller and check that cables to be 
connected are not alive with a tester or the like 
because there is a possibility of electric shock. 

Power supply 

Power supply 

Allowable range: 100 to 240 V AC (

10%)

(free voltage) 
50/60 Hz shared 

29

28

Heater current 
detection input

30

CT2

CT1

COM

CT

CT

*

This wiring is only possible 

for a controller with a 

 heater burnout alarm.

OT=4 (factory-set default)

OT=5

OT=6

*

 OT is a setup parameter.  

   You can change the settings of the parameter OT to change the control output type.  
   See                                                        , for more information.

Heating side: Relay output

(terminals    ,    and    )

Cooling side: Relay output

(terminals    and    )

1

2

3

Heating side: Voltage pulse output

(terminals    and    )

Cooling side: Relay output

(terminals    and    )

16

17

Heating side: Current output

(terminals    and    )

Cooling side: Relay output

(terminals    and    )

16

17

Initial Settings User’s Manual

Correspondence between parameter OT and heating-side/cooling-side output types

OT=7

OT=8

OT=9

Heating side: Relay output

(terminals    ,    and    )

Cooling side: Voltage pulse output

(terminals    and    )

1

2

3

Heating side: Voltage pulse output

(terminals    and    )

Cooling side: Voltage pulse output

(terminals    and    )

16

17

Heating side: Current output

(terminals    and    )

Cooling side: Voltage pulse output

(terminals    and    )

16

17

OT=10

OT=11

OT=12

The control output types, “relay output” and “voltage pulse output” shown in the table above refer to those of time proportional control.  
To change the type to a relay output for on-off control, select “Relay Terminals” and change the setpoint of the proportional band to “0.”

Heating side: Relay output

(terminals    ,    and    )

Cooling side: Current output

(terminals    and    )

1

2

3

Heating side: Voltage pulse output

(terminals    and    )

Cooling side: Current output

(terminals    and    )

16

17

Heating side: Current output

(terminals    and    )

Cooling side: Current output

(terminals    and    )

16

17

12

13

14

15

100

Two-wire transmitter

PV input 

   0.4 to 2.0 V DC signal 

Loop power 

supply 

   14.5 to 

18.0 V DC 

External 
resistor 
(Note) 

Note: Connecting a 100 

 resistor to the terminals is optional. 

  Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs) 

15 V DC Power Supply Wiring to Two-wire Sensor 

4-20mADC

12

13

21

22

250

Two-wire transmitter

PV input 

   1 to 5 V DC signal 

Loop power 

supply

 21.6 to 

28.0 V DC

External
 resistor
 (Note) 

Note: Connecting a 250 

 resistor to the terminals is optional. 

  Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) 

24 V DC Power Supply Wiring to Two-wire Sensor 

*

 Wiring can only be carried out for controllers with 24 V DC 

   loop power supply. 

4-20mADC

1

2

3

4

5

6

7

8

9

10

21

22

23

24

25

26

27

28

29

30

11

12

13

14

15

16

17

18

19

20

6

5

4

7

AL1

AL2

AL3

COM

Relay

Alarm output/cooling-side control output

Alarm-1 output

Alarm-2 output

Alarm-3 output 

or cooling-side control 

output (Note) 

Common

Relay contact rating: 240 V AC, 1 A 
 

30 V DC, 1 A (resistance load) 

UT

4

7

4

7

4

7

14

15

14

15

14

15

14

15

14

15

14

15

Note: External Contact Input

If the power is turned on when 
the external contact input is OFF, 
the mode (SP.no or A/M) existing 
before the power is turned off will 
be continued. (except for RUN/
STOP)

14

15

+

-

NOTE

Do not use unassigned terminals as relay terminals.

Summary of Contents for UT320

Page 1: ... RTD input Maximum 150 wire Conductor resistance between three wires should be equal However 10 wire for a maximum range of 150 0 to 150 0 C Wire resistance effect 0 1 C 10 Allowable input voltage 10 V DC for thermocouple mV or RTD input 20 V DC for DC voltage input Noise rejection ratio 40 dB 50 60 Hz or more in normal mode 120 dB 50 60 Hz or more in common mode Reference junction compensation er...

Page 2: ...roportional PID relay contact output is configured at factory before shipment 23 24 RS 485 communication Wiring can only be carried out for controllers with communication functions Maximum baud rate 9600 bps 25 26 27 SDB SDA RDB RDA SG 24 V DC loop power supply Wiring can only be carried out for controllers with 24 V DC loop power supply 21 6 28 0VDC 30 mA DC max 21 22 8 9 Power supply 10 L N Allo...

Page 3: ...300 F 300 to 750 F 199 9 to 750 0 F 32 to 4200 F 32 to 2500 F 32 to 3400 F 32 to 3600 F 199 9 to 999 9 F 199 9 to 300 0 F 300 to 1560 F 199 9 to 999 9 F 0 1 of instrument range 1 digit Note1 Note2 RTD Pt100 37 150 0 to 150 0 C 199 9 to 300 0 F 0 2 of instrument range 1 digit Note1 0 4 to 2 V 40 Standard signal 1 to 5 V 41 0 to 2 V 50 0 to 10 V 51 0 400 to 2 000 V 1 000 to 5 000 V 0 000 to 2 000 V ...

Page 4: ... 2 3 4 SET ENT PV MAN A M SP AL1 2 3 SP 2 3 4 SET ENT PV MAN A M SP AL1 2 3 SP 2 3 4 SET ENT Displays PV Displays target setpoint Displays target setpoint MAN lamp ON Displays output value Displays output value symbol o MAN lamp OFF 8 Manipulating the Control Output in Manual Operation NOTE Control output cannot be changed if the controller is stopped In this case the preset output value setup par...

Page 5: ...mit alarm Deviation setpoint Target SP Open lit Hysteresis PV Closed unlit 6 16 Closed lit Open unlit Open unlit Closed lit Closed lit Open unlit Open unlit Closed lit Closed lit Hysteresis Open unlit Alarm setpoint PV 2 12 Deviation high and low limits Target SP PV Hysteresis Hysteresis Deviation setpoint Closed lit Open unlit Closed lit 7 17 Deviation high limit Hysteresis PV Open unlit Target S...

Page 6: ...1 4 communi cation function 0 0 of PV input range 0 0 to 100 0 of PV input range where SPL SPH Places a limit on the range within which the target setpoint is changed SPH SPL Control output cycle time Heating side control output cycle time in heating cooling control Cooling side control output cycle time 1 to 1000 second 30 second 1 to 1000 second 30 second CT CTc Preset output Heating side preset...

Reviews: