IM 05C01E12-41E
15
■
Parameter Lists
(SP value display)
Target
setpoint
Minimum value (SPL) to maximum value (SPH) of target setpoint range
Unit:
°
C/
°
F
SPL
CTL
Control mode
ONF(0): On/off control
PID(1): PID control
SLF(2): Dynamic auto tune control (cannot be set for heating/cooling control)
SLF(2) :for standard type;
PID(1) : for
heating/cooling type
AT
Auto-tuning
OFF(0): Stop auto-tuning
ON(1): Start auto-tuning
OFF(0)
P
Proportional
band
1
°
C/
°
F to the temperature that corresponds to 100% of the
measured input range (scale) span
5% of measured
input range (scale)
span
I
Integral time
1 to 3600 seconds;
OFF(0): no integral action
240 seconds
D
Derivative
time
1 to 3600 seconds;
OFF(0): no derivative action
60 seconds
MR
Manual reset
–100 to 100%
50.0% for standard type;
0.0% for
heating/cooling type
COL
Cooling-side
gain
0.01 to 9.99 times
1.00 times
DB
Deadband
0% of measured
input range (scale)
span
HYS
Hysteresis for
on/off control
0
°
C/
°
F to the temperature that corresponds to 100% of the
measured input range (scale) span
0.5% of measured
input range (scale)
span
CT
Control output
cycle time
1 to 240 seconds
30 seconds
CTC
Cooling-side
control output
cycle time
1 to 240 seconds
30 seconds
SP1
Target
setpoint 1
Minimum value (SPL) to maximum value (SPH) of target
setpoint range
Unit:
°
C/
°
F
There are also optional engineering units for voltage input.
SPL
SP2
Target
setpoint 2
SPL
FL
PV input filter
OFF(0), 1 to 120 seconds
OFF(0)
BS
PV input bias
–100 to 100% of measured input range (scale) span
0% of measured
input range (scale)
span
LOC
Key lock
T1
Timer
setting 1
0.0 to 99.59
Unit: minutes and seconds or hours and minutes
Set the timer time unit using parameter TTU.
For example, 15.25 sets 15 minutes and 25 seconds.
(T1 is for AL1, and T2 is for AL2)
0.00
T2
Timer
setting 2
0.00
(2) Operating Parameters : Parameters changed rather frequently during operation.
HC
Heater disconnection
current measured
value
“HC” is not a parameter to be set. The current value (0 to 80) of heater disconnection
detector is displayed. Unit: A (ampere)
Settings: When the display value is – – – –, the heater current is not being measured.
A1
Alarm 1
setpoint
Max. value of
measured input range
(scale) (PV alarm)
A2
Alarm 2
setpoint
Min. value of
measured input range
(scale) (PV alarm)
0: No key lock
1: Prevents operations from being changed except for the
changing of SP in the operating display
2: Prevents all parameter changing operations
–1: Set
⬙
-1
⬙
to enter the setup parameter setting display.
But if
⬙
LOC=1 or 2
⬙
is already set, the parameter value can
not be changed by setting
⬙
LOC=-1
⬙
only. To change the
parameter value, set
⬙
LOC=0
⬙
at first (for disabling keylock),
then set
⬙
LOC=-1
⬙
once again.
0
(1) Target Setpoint (SP) and Timer Setting 1 and 2
Code
Name
Setting range and unit
Default
User setting
Code
Setting range and unit
Default
User setting
■
PV alarm Unit:
°
C/
°
F
Setting range: minimum value to maximum value of
measured input range (scale)
■
Deviation alarm Unit:
°
C/
°
F
Setting range: –100 to 100% of the measured input range (scale) span
■
Heater disconnection alarm Unit: A (ampere)
Setting range: OFF(0), 1 to 80
(can be set for the alarm 1 setpoint only)
■
PID control Unit:
°
C/
°
F
Setting range: –(proportional band setting) to +(proportional band setting)
■
On/off control Unit:
°
C/
°
F
Setting range: –50 to +50% of measured input range (scale)span
Name
Numbers in ( ) are the parmeter setpoints that apply when the
communication function is used. Ex. OFF(0), ON(1)