IM 05C01F12-41E
12
Setting
value
(PRG=0)
(PRG=1)
PRG
Press the
key
to move
between items.
Note
Note
CTL=ONF
(on/off
control)
Displayed when
the operation mode
is “RUN”.
Displayed when
the operation mode
is “RUN”.
CTL=PID
(PID control)
LOC=
When
–1
When LOC=–1,
transfers to the
setup parameter
setting display
Press the
key
to move
between items.
When “In” appears, press the
key to display the measured input
range code you want to use, then
press the key to register it.
After this operation, the controller
shows the operating display 1 .
When input range code has been already set, the
operating display 1 shown below appears.
Operating display
1
Press the
key for
at least 3 seconds.
(To operating
display 1 )
Press the
key for
at least 3 seconds.
(To operating
display 1 )
Note: If no key is pressed for a period of
two minutes or more while in the
operating, setup or program
parameter setting display, the
controller automatically returns to
operating display 1 .
Displayed when the
operation mode is “Reset”.
To program parameter
setting display
Measured input
value(PV)
Press the
key
for at least
3 seconds.
Target setpoint(SP)
Key
Key
Key
is displayed
?
Yes
No
Power ON
A
Operating Parameter Setting Display
Setup Parameter Setting Display
HOLD
ADV
CTL
HYS
Displayed for time-
proportional PID control
CT
Displayed when I=OFF
MR
Displayed for the /EX option.
DIS
Displayed when DC voltage
input range code is set.
DP
RH
RL
Displayed for the /RET option.
RTH
RTL
AT
P
I
D
FL
BS
LOC
IN
SPH
SPL
TMU
Not displayed when CTL=ONF
(on/off control)
SC
DR
Displayed for the /RS option
PSL
ADR
BPS
PRI
STP
DLN
NOTE
Set
⬙
-1
⬙
to enter the setup parameter setting
display. But if
⬙
LOC=2
⬙
is already set, the
parameter value can not be changed by setting
⬙
LOC=-1
⬙
only. To change the parameter value,
set
⬙
LOC=0 or 1
⬙
at first (for disabling keylock),
then set
⬙
LOC=-1
⬙
once again.
NOTE
SEG lamp is lit
Operating display
2
Measured input
value(PV)
Segment No.
at present
Operating display
3
Measured input
value(PV)
Remaining
segment time
"hour,minute" or
"minute,second"
A
1
Operating Display
At first
EV
RUN
SEG lamp is lit
EV
RUN
EV
RUN
EV
RUN
Changing certain setup parameters may
automatically initialize the operating
parameters. Therefore, after you change the
setup parameters, always check the operating
parameter settings to find out if appropriate
values have been set for them. If the operation
parameters have been initialized, set them to
their appropriate values.
NOTE