Password 2

(default: 20)

Access to 

parameters

Password 4

(default: 300)

To Code configuration

mode

 (

cod1

cod2

 

tables on the front page)

Increase the displayed value 

or select the next element

Confirm and go to 

Next parameter

Decrease the displayed value 

or select the previous element

To exit the parameter setting 
procedure press the       key (for 3 s) 
or wait until the timeout expiration 
(about 30 seconds).

Parameters setting

Press the       key 
for 3 seconds 

h854

248.0

C045

248.0

sp4

PARAMETERS SETTING

CONTROLLER OPERATION

Increase value

Decrease value

Set Point Change

Operative

Set Point

Changed 

operative

Set Point

248.0

sp

250.0

sp

248.0

sp

Confirm/Next

Confirm/Next

Confirm/Next

nsp

 > 1

nsp

 > 2

nsp

 > 3

Operator Command

Increase
Decrease

Active

Set Point 

selection

1

a.sp

If more than 

1 Set Point 

active 

(

nsp

 > 1)

Confirm/Next

1

st

 SP

value 

change

340.0

225.0

sp3

120.0

sp2

250

AL1

If  AL1 is active

Back to the

first parameter

Press the       key (3 s) or 

wait for the 10s time out to 

store the new Set Point 

and return to Normal Mode

Start

Auto-tune

started

Auto-tune

in progress

tunE

248.0

248.0

248.0.

Note:

 

The        key could be assigned by 
the user to other functions using 
the 

Usrb

 parameter setting

Dot flashes 

while the 

Auto-tune

is in progress

To return to the Normal Mode, press the       key for 3 seconds or wait for the 10s timeout

Press the       key for 3 s

Additional Information

Output Value %

(e.g.  heating = 35%, 

 

cooling = 45%)

If active

To return to the Normal Mode, press the       key for 3 seconds or wait for the 10s timeout

H035

248.0

d854

248.0

U854

248.0

EVOTUNE

 

is a fast and fully automatic 

procedure that can be started 

in any condition, regardless 

the deviation from  SP.

The controller selects 

automatically the best tune 

method and computes the 

optimum PID parameters.

Heating

Cooling

Worked time (days) 

Worked time (hours) 

Power (kW) 

or Energy (Wh)

Depending on 

Cod2

 digit 

S

 setting

Parameters List (

PASS

: 20) 

(in gray the parameters related to optional features)

Group

Param.

Description

Range value or selection list elements Default

User 

value

Note

Commands

oPEr

Operative Mode Selection

reg = Auto, 

oplo = Manual, 

stdy = Standby

a.sp

Set Point Selection

0 = SP, 1 = SP2, 2 = SP3, 3 = SP4

0 = SP

tune

Start Auto Tune

0 = oFF, 1 = start

0 = OFF

evoTUNE

Control

Pb

Proportional Band

1 to 9999 (Engineering Units = E.U.)

20

Cod1

 Digit 

N

 = 

1

ti

Integral Time

0 to 10000 s

200

td

Derivative Time

0 to 1000 s

50

HSEt

Hysteresis ON/OFF Control

0 to 9999 (E.U.)

1

Cod1

 Digit 

N

 = 

0

tc.H

Heating output cycle time

0.1 to 130 s

20.0

Cod1

 Digit 

N

 = 

1

rcg

Relative Cooling Gain

0.01 to 99.99

1.00

Cod1

 Digit 

N

 = 

Cod1

 Digit 

O

 > 

4

tcc

Cooling output cycle time

0.1 to 130 s

20.0

Cod1

 Digit 

N

 = 

Cod1

 Digit 

O

 > 

1

Set Point

SP

Set Point 1

-1999 to +9999 (E.U.)

SP2

Set Point 2

-1999 to +9999 (E.U.)

If 

nSP

 

> 1

SP3

Set Point 3

If 

nSP

 

> 2

SP4

Set Point 4

If 

nSP

 

> 3

SPLL

Set Point min. Value

-1999 to  SPHL (E.U.) 

SPHL

Set Point max. Value

SPLL to  9999 (E.U.)

nSP

No. of Set Points

1 to 4

1

Alarms

AL1

Alarm 1 threshold

AL1L to AL1H

If digit 

P

 of  

Cod2

 is > 

1

al1l

Alarm 1 low threshold/Low limit

-1999 to +9999 (E.U.)

-1999

al1H

Alarm 1 high threshold/High limit

9999

HAL1

AL1 hysteresis

1 to 9999 (E.U.)

1

AL2

Alarm 2 threshold

AL2L to AL2H

If digit 

Q

 of  

Cod2

 is > 

1

al2l

Alarm 2 low threshold/Low limit

-1999 to +9999 (E.U.)

-1999

al2H

Alarm 2 high threshold/High limit

9999

HAL2

AL2 hysteresis

1 to 9999 (E.U.)

1

AL3

Alarm 3 threshold

AL3L to AL3H

If digit 

R

 of  

Cod2

 is > 

1

al3l

Alarm 3 low threshold/Low limit

-1999 to +9999 (E.U.)

-1999

al3H

Alarm 3 high threshold/High limit

9999

HAL3

AL3 hysteresis

1 to 9999 (E.U.)

1

Soft Start

stp

Soft Start Output value

-100 to 100%

0

Sst

Soft Start Time

0.00 to 8.00 (hh.mm)

0

Input

ssc

Low Scale readout

-1999 to 9999

-1999

For linear Input 

types only

fsc

High Scale readout

-1999 to 9999

9999

dP

Number of decimals

0 to 3 (linear inputs); 0 to 1 (other inputs) 0

FiL

Measured value Digital filter

OFF; 0.1 to 20.0 s

0 = OFF

I/O

io4.F

I/O 4 Function

ON = Transmitter Power Supply 

OUT4 = SSR out 

Di2C = Dig. In. from contact 

Di2U = 24 VDC Digital Input

ON

Digital 

Inputs

diF.1

Digital Input 1 Function

0 to 21

0

See the DI1, DI2 

functions table

diF.2

Digital Input 2 Function

0 to 21

0

di.A

Digital Inputs Action

0 = DI1 direct action, DI2 direct action

1 =  DI1 reverse action, DI2 direct action

2 =  DI1 direct action, DI2 reverse action

3 =  DI1 reverse action, DI2 reverse action

0

DI2 only  

if configured

usrb

Key 

 Function

nonE, tunE, oplo, aac, asi, chsp,  

st.by, str.t

tunE

See the 

 Key 

function table

Display

di.cl

Colour of the Process Value 

display

0 = Change 

1 =  Red 

2 =  Green 

3 =  Orange

2

If Change, the co-

lour is 

green

 if PV 

differs from SP less 

than 

Ade

red

 if 

higher than 

Ade

 

and 

orange

 if is 

lower than 

Ade

ade

Display change color threshold  

(when 

di.Cl

 = 0)

0 (OFF) to 9999 (e.u.)

dis.t

Display Power OFF time (mm.ss) oFF (display ON) 0.1 to 99.59

oFF

Serial 

communi-

cations

Add

Instrument Address

1 to 254

1

Modbus RTU slave 

protocol

bAud

Baud rate

1200, 2400, 9600 baud,  

19.2, 38.4 kbaud

9600

Wattmeter

Uolt

Load Voltage

1 to 999 (V)

230

If digit 

S

 of  

Cod2

 is > 

1

cur

Load Current

1 to 9999 (A)

Password

PAS4

Configuration access Password

0 to 999

300

PAS2

Parameters access Password

0 to 999

20

Note: 

To access all the instrument features, please see the “

Complete configuration procedure

” in the “

Engineering Manual

”.

Complete Configuration and Parameter setting can be easily uploaded from the controller and downloaded to other controllers using the: 

Configuration Key and Communication Adapter model: TCS10.

dif$

 Digital Inputs DI1 and DI2 Functions

Code displayed

Description

 0

Disabled (OFF) (default)

 1

Alarm Reset

 2

Alarm Acknowledge (ACK)

 3

Hold of the measured value

 4

Stand by mode

 5

Manual Mode

 6

Heat with “SP” and CooL with “SP2”

 7

 to 

17

Reserved

18

Sequential Set Point selection [on transition]

19

SP/SP2 selection

20

Binary coding for Set Point selection on DI1 and DI2 

(00 = SP, 01 = SP2, 10 = SP3, 11 = SP4)

21

Digital inputs in parallel to the UP and Down keys  

(DI1 = UP key, DI2 = DOWN key)

usrb

 Key 

 Function

Code displayed

Description

nonE

Not used

tune

Starts auto tuning functions (default)

oplo

Manual mode

aac

Alarm Reset

asi

Alarm Acknowledge

chsp

Circular Set Point Selection (shows SP, SP2, SP3)

st.by

Stand-by mode