< 1. Overview >
6
TI 34P02K71-01E
4th Edition: Jun. 6, 2018-00
TIP
The combination of PLC type and processor type is shown in the table below.
PLC type
Processer
type
Controller
Remark
IPC_33
FCX
FCX_A
NFCP100 (*2)
NFJT100 (FCJ)
FCN/FCJ simulator
R1.01 or later (FCX_A: R1.11 or later)
IPC_33
R1.30 or later
IPC_40
R1.50 or later
IPC_40
FCX_B
NFCP501/NFCP502
FCN/FCJ simulator
R4.02 or later
IPC_40
FCX_C
NFCP501/NFCP502
FCN/FCJ simulator
R4.20 or later
*1: FCX: For NFJT100 or NFCP100 (not use NFLF111/NFGS813/NFGP813
/NFLP121/NFLC121)
FCX_A: For NFCP100 (use NFLF111/NFGS813/NFGP813/NFLP121
/NFLC121)
FCX_B: For NFCP501/NFCP502, retain data area extended version of FCX_A
FCX_C: For NFCP501/NFCP502 with three or more extension units and
NFLF111/NFLP121/NFLC121, device label extended version of FCX_B
*2: If the PLC type is IPC_40, the project for NFCP100 can be used by re-compiling
without changing itself.
If the PLC type is IPC_32 / IPC_33, re-create the resource with IPC_40.
If you want to change the processor type to FCX_B/FCX_C, re-create the
resource with IPC_40.
● Using the RS-232-C port on the FCJ
Change the port name used in the application program.
COM1: If you are migrating to COM1 of NFCP501/NFCP502, the application program
about the communication of the COM1 port is not changed.
If you are migrating to a port of the RS-232C communication module, change in
the same manner as the COM2 in the next section.
COM2: Migrate to a port of the RS-232C communication module.
Set the Port name of RS-232C communication module (e.g.) RS02 in the
resource configurator.
Change “COM2” to (e.g.) “RS02” in the application program.