21
IM 04L51B01-18EN
I/O Messages
Type
Number
Operation type
Instance ID
Size
Data type
Communication channel
(Read/Write)
C001 to C100 Producer /
Consumer
185
400 (4 x 100) FLOAT
C101 to C200 Producer /
Consumer
186
400 (4 x 100) FLOAT
C201 to C300 Producer /
Consumer
187
400 (4 x 100) FLOAT
C301 to C400 Producer /
Consumer
188
400 (4 x 100) FLOAT
C401 to C500 Producer /
Consumer
189
400 (4 x 100) FLOAT
-
Configuration
195
0
-
-
Producer /
Consumer
196
0
-
* The “continuous channel data area” is a special area that enables continuous reading by limiting
the number of channels of each module to 10.
For only the I/O channels on a GX/GP main unit or I/O channels on a GM main unit, this area
can be used to read data consecutively.
Explanation
• The recorder data can be accessed using the INT32 or FLOAT type. Data can be
accessed by the type based on the specified instance ID.
• The operation type “Producer” indicates a read-only instance and “Producer/Consumer”
indicates a read/write instance.
Data on the Recorder
See the explanation in the previous section on Explicit messages.