18
IM 04L51B01-18EN
I/O Messages
System Configuration on PLC
An I/O message is also called an Implicit message. An I/O message is used to transmit pre-
specified I/O data at intervals. An I/O message is exchanged via a connection path which is
first set in RSLinx and read into RSLogix. A connection path defines the IP address of the
recorder, communication port of the PLC, and distinction of input/output.
A device, once configured in RSLinx, can be downloaded into an RSLogix project. The
recorder is configured as a “Generic Ethernet Module” in RSLogix.
Instance ID
Each data on the recorder corresponds to the instance ID of an Assembly object. Each data
value can be accessed as an INT32 or FLOAT type. In an I/O message, use an instance
ID to code the data on the recorder to be accessed. The following table lists instance IDs,
sizes, and data types.
• INT32
Type
Number
Operation type
Instance ID
Size
Data type
Input/Output channel
(GX/GP main unit)
(GM main unit)
0001 to 0050,
0101 to 0150
Producer
101
400 (4 x 100) INT32
0201 to 0250,
0301 to 0350
Producer
102
400 (4 x 100) INT32
0401 to 0450,
0501 to 0550
Producer
103
400 (4 x 100) INT32
0601 to 0650,
0701 to 0750
Producer
104
400 (4 x 100) INT32
0801 to 0850,
0901 to 0950
Producer
105
400 (4 x 100) INT32
(GX/GP expandable I/O 1)
(GM sub unit 1)
1001 to 1050,
1101 to 1150
Producer
106
400 (4 x 100) INT32
1201 to 1250,
1301 to 1350
Producer
107
400 (4 x 100) INT32
1401 to 1450,
1501 to 1550
Producer
108
400 (4 x 100) INT32
(GX/GP expandable I/O 2)
(GM sub unit 2)
2001 to 2050,
2101 to 2150
Producer
111
400 (4 x 100) INT32
2201 to 2250,
2301 to 2350
Producer
112
400 (4 x 100) INT32
2401 to 2450,
2501 to 2550
Producer
113
400 (4 x 100) INT32
(GX/GP expandable I/O 3)
(GM sub unit 3)
3001 to 3050,
3101 to 3150
Producer
116
400 (4 x 100) INT32
3201 to 3250,
3301 to 3350
Producer
117
400 (4 x 100) INT32
3401 to 3450,
3501 to 3550
Producer
118
400 (4 x 100) INT32
(GX/GP expandable I/O 4)
(GM sub unit 4)
4001 to 4050,
4101 to 4150
Producer
121
400 (4 x 100) INT32
4201 to 4250,
4301 to 4350
Producer
122
400 (4 x 100) INT32
4401 to 4450,
4501 to 4550
Producer
123
400 (4 x 100) INT32
Input/Output channel
(GX/GP expandable I/O 5)
(GM sub unit 5)
5001 to 5050,
5101 to 5150
Producer
126
400 (4 x 100) INT32
5201 to 5250,
5301 to 5350
Producer
127
400 (4 x 100) INT32
5401 to 5450,
5501 to 5550
Producer
128
400 (4 x 100) INT32
Continued on next page