5-14
IM 01B04K02-02E
No.
Parameter Name
Symbol
Description
Setting Range Factory-set
Value
Display
Conditions
E09
Alarm 1 Hysteresis HYSTERESIS1 Sets the hysteresis until the
alarm 1
alarm state is canceled.
Note: Initialized when
- SENSOR TYPE1
- TC TYPE1
- RTD TYPE1
- UNIT1
- INPUT1 H_RNG
- INPUT1 L_RNG
- SCH1 or
- SCL1 is changed.
Setting range is 0 to 100%
of span in engineering unit
(EUS).
0 to 100 % of
span (EUS) in
engineering unit
0.5% of span in
engineering unit
Displayed on all
E10
Alarm 2 Hysteresis HYSTERESIS2 Sets the hysteresis until the
alarm 2
alarm state is canceled.
Note: Initialized when
- SENSOR TYPE1
- TC TYPE1
- RTD TYPE1
- UNIT1
- INPUT1 H_RNG
- INPUT1 L_RNG
- SCH1 or
- SCL1 is changed.
Setting range is 0 to 100%
of span in engineering unit
(EUS).
0 to 100 % of
span (EUS) in
engineering unit
0.5% of span in
engineering unit
Displayed on
SALD-724.
E15
Alarm 1 ON Delay
ON DELAY1
Sets the dead time until the
alarm is output after alarm
1 enters the alarm state.
0 to 999 s
0 s
Displayed on all
E16
Alarm 2 ON Delay
ON DELAY2
Sets the dead time until the
alarm is output after alarm
2 enters the alarm state.
0 to 999 s
0 s
Displayed on
SALD-724
E17
Alarm 1 OFF Delay OFF DELAY1 Sets the dead time until
alarm output is stopped
after alarm 1 is released
from the alarm state.
0 to 999 s
0 s
Displayed on all
D18
Alarm 2 OFF Delay OFF DELAY2 Sets the dead time until
alarm output is stopped
after alarm 2 is released
from the alarm state.
0 to 999 s
0 s
Displayed on
SALD-724
E19
Alarm 1 Relay
Action
RLY1 ACTION Specifies the direction of
alarm 1 relay action.
NRM DE-ENERGIZED:
De-energized during
normal operation
NRM ENERGIZED:
Energized during normal
operation
NRM
DEENERGIZED
NRM
ENERGIZED
NRM
DEENERGIZED
Displayed on all
E20
Alarm2 Relay Action RLY2 ACTION Specifies the direction of
alarm 2 relay action.
NRM DE-ENERGIZED:
De-energized during
normal operation
NRM ENERGIZED:
Energized during normal
operation
NRM
DEENERGIZED
NRM
ENERGIZED
NRM
DEENERGIZED
Displayed on
SALD-724
D60
Self Check
SELF CHK
Displays the result
(GOOD/ERROR) of the self check.
Displayed on
SALD-724
5.4 Parameter List