5-10
IM 01B04K02-02E
5.4 Parameter List
BRAIN communication parameters for SALD are as follows.
On the SALD-xx4, only the input value can be displayed, and the alarm set point can be
display/set on the display setter on the front panel. Other, parameters are display/set using
the Handy Terminal.
No.
Parameter
Name
Symbol
Description
Display
Conditions
Initial
display
01
Model Name
MODEL
Displays the model name.
Displayed
on all
02
Tag Number
TAG NO
Displays the tag number that is set.
03
Self Check
SELF CHK
Displays the result (GOOD/ERROR) of the self check.
A
Display 1
DISPLAY1
A03
PV1
PV1
Input value (engineering unit) after input processing (square
root or scaling)
Displayed
on all
A15
Alarm 1 Relay
Display
RLY1 STATUS
Displays the state of the alarm 1 relay.
DE-ENERGIZED: De-energized
ENERGIZED: Energized
A16
Alarm 2 Relay
Display
RLY2 STATUS
Displays the state of the alarm 2 relay.
DE-ENERGIZED: De-energized
ENERGIZED: Energized
Displayed on
SALD-724
A54
Status Display
STATUS
Displays the value added to the value (Hex) indicating
the self check result.
0000: Normal
0001: EEPROM error
0002: EEPROMSUM error
0008:Input range exceeded
0010: Setting error
0020: Input burnout
0040: Power interruption during operation
0080: RJC error
1000: A/D conversion error
Displayed
on all
A55
Parameter Write
Protect
WRT PROTECT Displays the state of the Parameter Write Protect jumper.
OFF: Setting of parameters enabled
ON: Setting of parameters disabled
A56
REV NO.
REV NO.
Displays the device revision No.
A58
MENU REV
MENU REV
Displays the revision No. of the parameter group.
A60
Self Check
SELF CHK
Displays the result (GOOD/ERROR) of the self check.
B
Display 2
DISPLAY2
B03
PV1
Same as item A
B15
Alarm 1 Relay
Display
B16
Alarm 2 Relay
Display
B60
Self Check