<6. Operation>
6-1
IM 01W03D02-01EN
6. Operation
6.1 Preparation for Starting
Operation
NOTE
• Before using FN310, connect FN110. For
detail on how to install the FN110, refer to
subsection 4.2.1 “Installation of FN110”.
• It is required to set security and network
information to enable this product to be
connected to the field wireless network.
For more details, refer to subsection 6.3
“Connecting to the Field Wireless Network”.
(1) Setting the Modbus Device
Set the parameters of the Modbus device. For
details about the settings, refer to Section 9
“Connection Device Type”. Refer to the user
manual of the Modbus device for the setting
method.
(2) Checking Installation and Wiring
Ensure that the FN310, FN110 and the Modbus
device are installed correctly according to the
procedures described in section 4 “Installation”, and
section 5 “Wiring”.
(3) Power On and Connecting to the Field
Wireless Network
Insert batteries into the battery case, and install
to the FN310. For details of installation of battery,
refer to subsection 8.3 “Replacing the Battery
Pack” and subsection 8.4 “Replacing the Batteries”.
Provisioning is to set the security and network
information. For details of provisioning, refer to
section 6.3 “Connecting to the Field Wireless
Network”.
(4) Checking parameter of the FN310 and the
Modbus device
Use the device configuration tool and confirm
that the Modbus device and the FN310 operate
properly. Check parameter values or change the
setpoints as necessary.
The integral indicator can be used to confirm
that this product is operating properly. For details
on how to confirm this, refer to subsection 7.4
“Self-Diagnostics”. ISA100 devices display self-
diagnostic information in an easy-to-understand
manner using four categories (Function check,
Maintenance required, Failure, and Out of
specification) according to NAMUR NE107*
*: NAMUR NE107 “Self-Monitoring and Diagnosis of Field
Devices”
Confirm operation status by integral indicator
If the FN310 is faulty, an error code is displayed.
F0601.ai
Figure 6.1
Integral Indicator with Error Code
NOTE
If any of the above errors are indicated on the
display of the integral indicator or the device
configuration tool, refer to subsection 8.10.3
“Errors and Countermeasures” for the corrective
action.
Verify and Change the FN310 Setting and
Values
The followings are the required settings of the
FN310. These parameters must be set before
starting operation. Parameters to be set in advance
depending on the connection device type. Refer to
section 9 “Connection Device Type”.
• TRANSDUCER block: Sensor Type
Select the type of sensor to be connected to
FN310. Select “Not Used” when using as a routing
device without the Modbus device.
6.2 Starting Operation
Ensure that the installation, the wiring, the network
connection, and the behavior of the FN310 are
correct before starting operation.
IMPORTANT
Close the front panel. Tighten each screws to a
torque of 0.7 N•m.