8-3
IM 34M6H33-01E
1st Edition : July 1.2004-00
By storing slave contact input data into internal relays as shown below, we can then use
the internal relays as substitutes for the slave contact input relays.
The following program stores slave contact input data into internal relays of the ASi
Master module installed in slot 4.
X
□□□
19
(NORMAL_OPERATION)
Slot
Number
Data
Position
Number
First
Device
Transfer
Size in
Words
READ
4 87 I00001 16
Internal Relay
(Location for storing read
data)
Slave
Address
I/O Number
I00005 to I00008
1A
0 - 3
I00009 to I00012
2A
0 - 3
: :
:
I00249 to I00252
30B
0 - 3
I00253 to I00256
31B
0 - 3
After execution of the READ instruction, we can use internal relays I00005 - I00256 as
substitutes for the slave contact input relays. (Although the first device is specified as
I00001, positions I00001-I00004 and I00129-I00132 contain invalid bits since they map
to no slaves.)