<6. Wiring>
6-2
IM 01C25K01-01E
6.3.1 Power Supply Wiring Connection
IMPORTANT
Connecting with the commercial AC power
supply will damage the device. Be sure to use
the DC power supply in the predetermined
range.
Connect the power supply wiring to the
and – terminals. When /AL is specified, also refer to
subsection 6.3.5.
Power supply
–
+
Transmitter terminal box
F0601.ai
Load resistance is not
necessary for 1 to 5 V output.
Figure 6.2
Power Supply Wiring Connection
6.3.2 External Indicator Connection
Available only for 4 to 20mA output type and when
/AL is not specified.
Connect wiring for external indicators to the CHECK
(+) and SUPPLY – terminals.
(Note) Use a external indicator whose internal resistance is 10 Ω
or less.
Transmitter terminal box
External indicator
F0602.ai
Power supply
–
+
Figure 6.3
External Indicator Connection
6.3.3 Communicator Connection
■ 4 to 20 mA output, BRAIN / HART
IMPORTANT
Analog output may change temporally in
connecting with BRAIN terminal due to an initial
current flowed to it. To prevent communication
signal affecting the upper system, it is
recommended to install a low-pass filter
(approximately 0.1s)
Connect the BT200 or HART Communicator to the
and – terminals. (Use hooks.)
Transmitter terminal box
BT200
F0603.ai
Power supply
–
+
Ignore the polarity
since the BT200 is
AC-coupled to the
terminal box.
Figure 6.4
BT200 Connection
■ 1 to 5 V output, HART
Connect the HART communicator or
configuration tool to the SUPPLY - and VOUT
(+) terminals. (Use hooks.)
Transmitter terminal box
F0615.ai
Voltmeter
–
+
Power supply
–
+
USB
FieldMate Modem
PC/FieldMate
Figure 6.5
Four wire connection
Transmitter terminal box
F0616.ai
Power supply
–
+
Voltmeter
–
+
USB
FieldMate Modem
PC/FieldMate
Figure 6.6
Three wire connection
6.3.4 Check Meter Connection
Available only for 4 to 20mA output type and when
/AL is not specified.
Connect the check meter to the CHECK (+) and
SUPLLY – terminals. (Use hooks.)
• A 4 to 20 mA DC output signal from the CHECK
A (+) and SUPPLY – terminals.
(Note) Use a check meter whose internal resistance is 10 Ω or
less.
Transmitter terminal box
F0604.ai
Power supply
–
+
Check meter
Figure 6.7
Check Meter Connection