<2. Handling Cautions>
2-7
IM 01C25K01-01E
F0204-2.ai
Pressure Transmitters
Supply
Hazardous Location
Nonhazardous Location
+
–
+
–
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class III, Division 1.
Not Use
Safety Barrier
[Nonincendive]
CSA Certified
Equipment
([nL] or
nonincendive)
Group IIC, Zone 2
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. EJX/EJA-E Series pressure transmitters
with optional code /CF1 are applicable for
use in hazardous locations:
• Certificate: 2014354
•
Applicable Standard: C22.2 No.0,
C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25,
C22.2 No.30, C22.2 No.94,
C22.2 No.61010-1, C22.2 No.60079-0,
C22.2 No.61010-2-030, C22.2 No.60079-1
•
Explosion-proof for Class I, Groups B, C and
D.
•
Dustignition-proof for Class II/III, Groups E, F
and G.
• Enclosure: Type 4X
•
Temperature Code: T6...T4
•
Ex d IIC T6...T4
•
Enclosure: IP66/IP67
•
Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
•
Ambient Temperature: –50* to 75°C (T4),
–50* to 80°C (T5), –50* to 75°C (T6)
* –15°C when /HE is specified.
•
Supply Voltage: 42 V dc max.
32 V dc max. (F
OUNDATION
Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
•
Output Signal: 4 to 20 mA dc
15 mA (F
OUNDATION
Fieldbus and
PROFIBUS PA type)
1 to 5 V (Low Power type)
Note 2. Wiring
•
All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
•
In hazardous location, wiring shall be in
conduit as shown in the figure.
•
WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
•
WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Conduit
Transmitter
F0205-1.ai
Non-Hazardous
Locations
Hazardous Locations Division 2
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
Transmitter
F0205-2.ai
• All wiring shall comply with local installation
requirements and local electrical code.
• In hazardous locations, the cable entry
devices shall be of a certified flameproof
type, suitable for the conditions of use and
correctly installed.
• Unused apertures shall be closed with
suitable flameproof certified blanking
elements. (The plug attached is flameproof
certified.)
•
Wiring connection for output signal code Q
(Low Power type) shall follow the diagram
below.