Setting the Data Storage
Setup Example 5: Continuously Record Measured Data and Automatically Save
In this example, we will continuously record and save the measured data of channel 1
and 2.
For the procedure to set the channel, see “Setting the Input Range and Alarm” on page
28.
For the procedure to set groups, see “Setting the Display” on page 30.
Channel 1
Automatically save to
the CF card periodically.
Channel 2
Setup Item
Description
Number in the Figure
Source channels
Channel 1 (TI-001) and channel 2 (FI-002)
1
Data to be recorded
Continuously record the display data from the start of the
measurement.
2
Data storage method
Automatically store every 24 hours.
3
Sampling interval
4 seconds. Set using the trend interval.
Sampling interval = (trend interval setting)/30 dots
*
* 40 dots when the trend interval is set to 5 or 10 seconds.
4
Data file name
Add “sample” to the file name.
5
Example: 000123_sampleYYMMDD_HHMMSS.DAD
↑
↑
Sequential number Date/Time of the first recorded data
Save Destination
Directory
DATA-101
6
(1) Data to be Recorded
Press
MENU
(to switch to setting mode), hold down
FUNC
for 3 s (to switch to basic
setting mode).
Select the
Menu
tab >
A/D, Memory.
2