IM 01C25T03-01E
3-9
3. OPERATION
(6) Integral Indicator Scale Setup
The following five displays are available for integral
indicators: input pressure*
1
, % of range, user set scale,
input static pressure, and % of static pressure range*
1
.
A cycle of up to four displays can be shown by
assigning variables to the parameters I10 to I13: DISP
OUT1 to DISP OUT4.
T0306.EPS
Available displays
Input pressure
(PRES)
% of range
(PRES %)
User set scale
(ENGR. PRES)
Input static pressure
(SP)*
1
% of static pressure range
(SP %)*
1
Indicates values of input pressure
with the indication limits
32000 to
32000.
Indicates input pressure in
2.5 to
110% range depending on the
measuring range (C21, C22).
Indicates values depending on the
engineering range (I33, I34) with the
unit (I30).
Indicates input static pressure with
the indication limits –32000 to 32000.
Reference pressure is factory-set in
absolute.
Indicates input static pressure in –10
to 110% range depending on the
measuring range (D33, D34).
A11:PRES
456 kPa
Description
and related parameters
A10:OUTPUT
45.6 %
A16:ENGR.OUTPUT
20.5 m3/min
A17:ENGR.EXP
100
A21:SP
4.000 MPa
A20:SP %
52.6 %
*
1: Available for differential pressure transmitter.
See (a.) through (d.) for each setting procedure.
a. Display Selection
(I10: DISP OUT1)
Select the variable for the parameter I10: DISP OUT1
to display on the integral indicator.
• Example: Change the integral indicator scale
from % of range to input pressure
display.
ESC
SET
I10:DISP OUT1
PRES
FEED
NO
OK
Use the or key
to select
PRES
.
Press the key twice to
enter the setting.
Press the (OK) key.
F0318.EPS
SET
I10:DISP OUT1
PRES %
< PRES >
< PRES % >
< ENGR.PRES >
< SP >
b. Cyclic Display
(I11: DISP OUT2, I12: DISP OUT3, and I13:
DISP OUT4)
In addition to the display set at I10: DISP OUT1,
displays can be set at I11: DISP OUT2, I12: DISP
OUT3, and I13: DISP OUT4 for cyclic display in the
order of the parameter number.
c. User Setting of Engineering Unit and Scale
(I30: ENGR.UNIT, I31: EASY EU SET, I33:
ENGR.LRV, and I34: ENGR.URV)
These parameters allow the entry of the engineering
units and scale to be displayed. The engineering unit
can be selected from the parameter of I31: EASY EU
SET as listed below. Alternately, up to eight alphanu-
merics, spaces, and a slash “/” can be input on keypad
at I30: ENGR.UNIT; only first six are displayed on the
integral indicator.
Select the unit from the list of I31: EASY EU SET.
FX0302.EPS
kPa
MPa
mbar
bar
psi
psia
mmH2O
mmHg
mmHgA
mmAq
mmWG
Torr
inH2O
inHg
inHgA
ftH2O
gf/cm2
kgf/cm2
kg/cm2G
kg/cm2A
atm
kg/h
t/h
m3/h
m3/min
l/h
l/min
kl/h
kl/min
Nl/h
Nl/min
Nm3/h
Nm3/min
ACFH
ACFM
SCFH
SCFM
GPH
GPM
m
mm
in
ft
kg/m3
g/cm3