IM 01C25T03-01E
3-8
3. OPERATION
(4) Output Mode and Integral Indicator Dis-
play Mode Setup (C40: OUTPUT MODE,
I20: P DISP MODE)
The mode setting for the output signal and the integral
indicator can be performed independently.
This mode is set as specified in the order when the
instrument is shipped. Follow the procedure below to
change the mode.
If the instrument is equipped with an integral indicator
and the display mode is
SQUARE ROOT
, “
” is
displayed on the integral indicator.
• Output mode for 4-20 mA output
• Example: Set output mode from
Linear
to
Square root
.
ESC
SET
C40:OUTPUT MODE
SQUARE ROOT
FEED
NO
OK
SET
C40:OUTPUT MODE
LINEAR
< LINEAR >
< SQUARE ROOT >
Use the or key
to select
SQUARE ROOT
.
Press the key twice to
enter the setting.
Press the (OK) key.
F0314.EPS
• Integral indicator display mode
• Example: Set display mode from
Linear
to
Square root
.
ESC
SET
I20:P DISP MODE
SQUARE ROOT
FEED
NO
OK
SET
I20:P DISP MODE
LINEAR
< LINEAR >
< SQUARE ROOT >
Use the or key
to select
SQUARE ROOT
.
Press the key twice to
enter the setting.
Press the (OK) key.
F0315.EPS
(5) Output Signal Low Cut Mode Setup
(D10: LOW CUT, D11: LOW CUT MODE)
Low cut mode can be used to stabilize the output
signal near the zero point. The low cut point can be set
in a range from 0 to 20%, the direct ratio correspond-
ing to the output signal of 4 to 20 mA. (Hysteresis:
±
10% of the cut point)
Either
LINEAR
or
ZERO
can be selected as the low
cut mode. Unless otherwise specified, the cut mode is
set to LINEAR at the factory.
Note that when the output modes of the output signal
and the integral indicator are selected as
SQUARE
ROOT
and
LINEAR
accordingly, the low cut function
is not available for the integral indicator display.
• Example: Change the low cut setting range
from 10% to 20%, and the low
cut mode from
LINEAR
to
ZERO
in
the SQUARE ROOT output mode.
FEED
NO
OK
SET
D11:LOW CUT MODE
ZERO
Use the or key
to select
ZERO
.
Press the key twice to
enter the setting.
Press the (OK) key.
F0317.EPS
FEED
NO
OK
SET
D10:LOW CUT
20.00 %
ESC
SET
D11:LOW CUT MODE
LINEAR
< LINEAR >
< ZERO >
DATA
DIAG
PRNT
ESC
PARAM
D10:LOW CUT
20.0 %
D11:LOW CUT MODE
ZERO
D15:H/L SWAP
NORMAL
CLR
ESC
SET
D10:LOW CUT
10.00 %
+ 20.00
Set
20
.
Press the key twice to
enter the setting.
Press the (OK) key.
Next, the [D11: LOW CUT MODE]
setting panel is displayed.
(%)
50
20
0
50 (%)
Output
Low cut mode “LINEAR”
Input
(%)
50
20
0
50 (%)
Low cut mode “ZERO”
LOW CUT at 20%
Input