9. GENERAL SPECIFICATIONS
9.
GENERAL SPECIFICATIONS
9.1 Standard Specifications
Refer to IM 01C25T02-01E for FOUNDATION Fieldbus
communication type marked with “
.”
Performance Specifications
See General Specifications sheet, GS 01C25F01-01E.
Functional Specifications
Span & Range Limits
EJX530A
T0901.EPS
Span
Span
Range
Range
Range
Range
Span
–1 to 20
1 to 50
–1 to 100
2 to 100
0.4 to 20
145 to 7200
10 to 500
8 to 200 kPa
–0.1 to 10
–0.1 to 2
0.04 to 2
–100 to 200 kPa
–14.5 to 1450
0.2 to 10
1.16 to 29
–14.5 to 29
5.8 to 290
–14.5 to 290
29 to 1450
Span
–1 to 2
10 to 500
–1 to 500
–14.5 to 7200
–0.1 to 50
–1 to 500
2 to 100
–1 to 2
kgf/cm
2
(/D4)
0.08 to 2
0.4 to 20
–1 to 20
–1 to 100
MPa
Measurement
Span/Range
psi (/D1)
A
D
0.08 to 2
bar (/D3)
C
B
EJX510A (Values are absolute pressure)
T0902.EPS
Span
Span
Range
Range
Range
Range
Span
0 to 20
1 to 50
0 to 100
2 to 100
0.4 to 20
145 to 7200
10 to 500
8 to 200 kPa
0 to 10
0 to 2
0.04 to 2
0 to 200 kPa
0 to 1450
0.2 to 10
1.16 to 29
0 to 29
5.8 to 290
0 to 290
29 to 1450
Span
0 to 2
10 to 500
0 to 500
0 to 7200
0 to 50
0 to 500
2 to 100
0 to 2
kgf/cm
2
(/D4)
0.08 to 2
0.4 to 20
0 to 20
0 to 100
MPa
Measurement
Span/Range
psi (/D1)
A
D
0.08 to 2
bar (/D3)
C
B
Output “
”
Two wire 4 to 20 mA DC output with digital communica-
tions, linear or square root programmable. BRAIN or
HART FSK protocol are superimposed on the 4 to 20 mA
signal.
Output range: 3.6 mA to 21.6 mA
Output limits conform to NAMUR NE43 can be pre-set by
option C2 or C3.
Failure Alarm “
”
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: –5%, 3.2 mA DC or less
Note: Applicable for Output signal code D and E
Damping Time Constant (1st order)
Amplifier damping time constant is adjustable from 0 to
100.00 seconds and added to response time.
Note: For BRAIN protocol type, when amplifier
damping is set to less than 0.5 seconds, communi-
cation may occasionally be unavailable during the
operation, especially while output changes
dynamically. The default setting of damping
ensures stable communication.
Update Period “
”
45 msec
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the lower
and upper range limits of the capsule.
External Zero Adjustment “
”
External Zero is continuously adjustable with 0.01%
incremental resolution of span. Re-range can be done
locally using the digital indicator with range-setting switch.
Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display and Bar
graph.
The indicator is configurable to display one or up to four of
the following variables periodically.;
Pressure in %, Scaled pressure, pressure in Engineering
unit.
See “Setting When Shipped” for factory setting.
Burst Pressure Limits
Capsule
Pressure
A, B, C
30 MPa (4350 psi)
D
132 MPa (19100 psi)
NORMAL OPERATING CONDITION
(Optional features or approval codes may affect
limits.)
Ambient Temperature Limits
–40 to 85
°
C (–40 to 185
°
F)
–30 to 80
°
C (–22 to 176
°
F) with LCD display
Process Temperature Limits
–40 to 120
°
C (–40 to 248
°
F)
Ambient Humidity Limits
0 to 100% RH
Working Pressure Limits (Silicone oil)
Maximum Pressure Limits
Pressure
Capsule
EJX510A
EJX530A
A
200 kPa abs (29 psia)
200 kPa (29 psig)
B
2 MPa abs (290 psia)
2 MPa (290 psig)
C
10 MPa abs (1450 psia)
10 MPa (1450 psig)
D
50 MPa abs (7200 psia)
50 MPa (7200 psig)