IM 01C25F01-01E
2-11
2. HANDLING CAUTIONS
• Unused apertures shall be closed with suitable
flameproof certified blanking elements.
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5 MINUTES
BEFORE OPENING.
• WARNING:
WHEN AMBIENT TEMPERATURE
≥
65
°
C,
USE THE HEAT-RESISTING CABLES
≥
90
°
C.
• Take care not to generate mechanical sparking
when accessing to the instrument and peripheral
devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void IECEx Certification.
2.10 EMC Conformity Standards
EN61326, AS/NZS CISPR11
CAUTION
To meet EMC regulations, Yokogawa recom-
mends that customers run signal wiring through
metal conduits or use shielded twisted-pair
cabling when installing EJX series transmitters in
a plant.
2.11 Pressure Equipment
Directive (PED)
(1) General
• EJX series pressure transmitters are categorized as
pressure accessories under the vessel section of
directive 97/23/EC, which corresponds to Article 3,
Paragraph 3 of PED, denoted as Sound Engineering
Practice (SEP).
• EJX110A-
M, EJX110A-
H, EJX130A,
EJX440A, EJX510A-
D, and EJX530A-
D can
be used above 200 bar and therefore considered as
a part of a pressure retaining vessel where category
III, Module H applies. These models with option
code /PE3 conform to that category.
(2) Technical Data
• Models without /PE3
Article 3, Paragraph 3 of PED, denoted as Sound
Engineering Practice (SEP).
• Models with /PE3
Module : H
Type of Equipment :Pressure Accessory - Vessel
Type of fluid : Liquid and Gas
Group of fluid : 1 and 2
Model
EJX110A
EJX110A
with code /PE3
EJX130A
EJX130A
with code /PE3
EJX310A
EJX430A
EJX440A
EJX440A
with code /PE3
EJX510A
EJX510A
with code /PE3
EJX530A
EJX510A
with code /PE3
Category
*2
Article 3, Paragraph 3
(SEP)
III
Article 3, Paragraph 3
(SEP)
III
Article 3, Paragraph 3
(SEP)
Article 3, Paragraph 3
(SEP)
Article 3, Paragraph 3
(SEP)
III
Article 3, Paragraph 3
(SEP)
III
Article 3, Paragraph 3
(SEP)
III
PS.V
(bar.L)
1.6
2.5
2.5
5.0
5.0
1.6
1.6
5.0
5.0
10
70
70
10
70
70
V(L)
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
PS
(bar)
*1
160
250
250
500
500
160
160
500
500
100
700
700
100
700
700
*1: PS is maximum allowable pressure for vessel itself.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC
T0202.EPS
Capsule
code
L
M, H
M, H
M, H
M, H
M, A, B
H, A, B
C, D
C, D
A, B, C
D
D
A, B, C
D
D
(3) Operation
CAUTION
• The temperature and pressure of fluid should
be maintained at levels that are consistent with
normal operating conditions.
• The ambient temperature should be maintained
at a level that is consistent with normal
operating conditions.
• Please take care to prevent water hammer and
the like from inducing excessive pressures in
pipes and valves. If phenomena are likely,
install a safety valve or take some other
appropriate measure to prevent pressure from
exceeding PS.
• Take appq“Ärg˙Le measures at the device or
system level to protect transmitters if they are
to be operated near an external heat source.