<APPENDIX 3. OPERATION OF EACH PARAMETER IN FAILURE MODE>
A3-15
IM 01F06F00-01EN
Alarm Reset Switch Settings
Some alarms can be disabled and enabled using switches in parameter ALARM_PERFORM inside the
transducer block as explained below.
(1) Setting
As shown in the following table, the individual bits of ALARM_PERFORM at relative index 45 act as
switches to disable and enable particular alarms. Write zeros to the respective bits to disable desired
alarms, or write ones to enable them.
(2) Default Values
Bit in
ALARM_PERFORM
Corresponding Alarms
Factory Default
(0 = Disable; 1 = Enable)
Bit 15
AL-84 to AL-93 (alarms pertaining to AR)
0
Bit 14
AL-80 to AL-83 (alarms pertaining to IT)
0
Bit 13
AL-77 to AL-79 (alarms pertaining to AI3)
0
Bit 12
AL-62 to AL-64 (alarms pertaining to AI1)
1
Bit 11
AL-65 to AL-67 (alarms pertaining to AI2)
0
Bit 10
AL-68 to AL-70 (alarms pertaining to DI1)
0
Bit 9
AL-71 to AL-73 (alarms pertaining to DI2)
0
Bit 8
AL-74 to AL-76 (alarms pertaining to PID)
0
Bit 7
Not used.
Bit 6
Corresponds to parameter K45 in a non-Fieldbus type digitalYEWFLO.
Selects the output action upon occurrence of “High Vibration” in self-diagnostics.
1
Bit 5
AL-05 (flow sensor fault)
1
Bit 4
AL-06 (failure of amplifier’s input circuit)
1
Bit 3
AL-51 (transient excessive vibration [transient disturbance])
0
Bit 2
AL-52 (excessive vibration)
0
Bit 1
AL-53 (flow anomaly [clogging])
0
Bit 0
AL-54 (flow anomaly [excessive output fluctuations])
0
These default bit statuses comprise 0x1070 as the default value of ALARM_PERFORM.