<4. Wiring>
47
IM 01E24A01-01EN
(2) Input signals
Input signal type
Specification
Status input
[Sin]:
[Si11 or Si12]:
IMPORTANT
The status input detects a signal without voltage.
Loading voltage during the switching status "Close" may result in damage on the electrical
circuit.
The status input is used for connecting to the following no-voltage contacts.
Switching status
Resistance
Closed
200 Ω or less
Open
100 kΩ or more
Transmitter
Sin-
Sin+
F0456.ai
Figure 4.6.9 Connection diagram: Status input [Sin]
W
iring
4