YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
YMGI: Your Modern Green Idea
20
Fan Motor
Model
-
B-SWZ150A
SWZ150D
Drive Type
-
Direct Drive
Direct Drive
Speed (H/M/L)*
rpm
700
800
Power Output
PH
0.2
1/5X2
Full Load Amp(FLA)
A
/
/
Insulation class
-
B
B
Safe class
-
IP44
IP44
Capacitor
uF
/
/
Fan
Type
-
Axial-flow
Axial-flow
Quantity
-
1
2
Diameter-Height
inch
φ21.65-7
φ20.47-6
Condenser
Material
-
Inner Groove Copper Tube-
Aluminum Fin
Inner Groove Copper Tube-
Aluminum Fin
Face Area
sq.ft
1.7
1.7
m
2
4.6
4.6
Pipe Diameter
in.
Φ 5/16
φ5/16
Number of rows
2
3
Tube pitch(a)x row pitch(b)
in.
55/64 × 3/4
55/64 × 3/4
Fins per Inch(FPI)
-
18
17
Fin type
-
Ripple
Ripple
Number of circuits
-
5
9
Length(L) x Height(H) x Width(W)
In.
45 7/16 × 31 3/16 × 1 1/2
37 61/64 × 51 31/32 × 2 1/4
Permissible Excessive Operating Pressure for Discharge Side
Mpa
3.8
3.8
Permissible Excessive Operating Pressure for Suction Side
Mpa
1.7
1.7
Operation temp
Cooling
°F
5 ~ 129.2
5 ~ 129.2
Heating
°F
-22 ~ 75.2
-22 ~ 75.2
Defrosting Method
-
Automatic Defrosting
Automatic Defrosting
Isolation
-
I
I
Moisture Protection
-
IPX4
IPX4
Overload Protector
-
/
/
Dimension
Outline dimension (W×D×H)
In.
37 1/64
” × 18 7/64” ×
32 9/32
”
39 3/8
” × 14 9/16” × 53 47/64”
Package dimension (L×W×H)
In.
42 41/64
” × 22 9/16” ×
38 5/16
”
45 25/64
” × 19 13/32” × 59 1/4"
Weight
Net Weight
lbs.
217.16
308.65
Gross Weight
lbs.
240.3
337.31
Connection Pipe
Valve Connection Type
-
Screw Connection or Solder
Connection
Screw Connection or Solder
Connection
Length
ft.
25
25
Gas additional charge
g/m
30
30
Outer Diameter
Liquid Pipe
Inch
3/8"
3/8"
Gas Pipe
Inch
3/4"
3/4"
Max Distance
Height
ft.
49.21
49.21
Length
ft.
98.4
98.4
Notes:
1.
The cooling capacity stated above is measured under following conditions:
Indoor Condition: 27°C
(
81°F
)
DB/19°C
(
66.6°F
)
WB.
Outdoor Condition: 35°C
(
95.4°F
)
DB/24°C
(
75.6°F
)
WB.
2.
Noise is tested in the semi-anechoic room, so it will be slightly higher in operation due to environmental change.
3.
"1" is tested under standard conditions.
"2" is tested under rated conditions according to CE/Eurovent standard:
4.
* Fan different speed