To Remove the Air Filter 

By holding onto the bottom slot of the air filter slightly push the filter in an upward at a slight angle and pull 
downward carefully. 
 

Cleaning 

To clean the dust adhering to the filters, you can either use a vacuum cleaner, or wash them with warm water and a 
neutral detergent, the water should be below 113°F. When the filters have been cleaned, dry them air dry 
completely out of direct sunlight.  

 
NOTE: 

Never use water hotter than 113°F to wash the unit or the filters as this can discolor and/or deform 

the unit. Never dry the filters by a fire or open flame as this can be dangerous. Always air dry the filters. 
 

Reinsert the filters 

Reinsert the filters aligning with the arrow head, then cover the surface panel and clasp it. 

 

CHECKING BEFORE COOLING/HEATING SEASON COMES: 

1.  If the unit is still connected to the correct electric power V/Ph/Hz. 
2.  If the unit is still securely fastened. 
3.  If the batteries of remote control are good. 
4.  If the filter is loaded and clean 

5. 

If the intake and discharge vents are clear from any obstructions.

 

 

MAINTENANCE AFTER USING 

1.  Turn main power off, by disconnecting electrical power disconnect switch. 
2.  Clean filter and unit. 

3. 

Cover the unit to keep dust or moisture out of the unit.

 

 

PROTECTION AND ERROR CODES 

 

Error 
Code 

Content 

Error 
Code 

Content 

Error 
Code 

Content 

L0 

Indoor Unit Error 

L9 

Quantity of Group Control 

Indoor Units Setting Error 

d8 

Water Temperature Sensor 

Error 

L1 

Indoor Fan Protection 

LA 

Indoor Units Incompatibility 

Error 

d9 

Jumper Cap Error 

L2 

E-heater Protection 

LH 

Low Air Quality Warning 

dA 

Indoor Unit 

Network Address Error

 

L3 

Water Full Protection 

LC 

Outdoor-Indoor 

Incompatibility Error 

dH

 

Wired Controller Circuit 

Board Error 

L4 

Wired Controller Power 

Supply Error 

D1 

Indoor Unit Circuit Board 

Error 

dC

 

Capacity DIP Switch Setting 

Error 

L5 

Anti-freezing Protection 

D3 

Ambient Temperature Sensor 

Error 

dE

 

Indoor Unit CO

Sensor Error 

L7 

No Master Indoor Unit Error 

D4 

Inlet Pipe Temperature 

Sensor Error 

C0 

Communication Error 

L8 

Power Insufficiency 

Protection

 

D6 

Outlet Pipe Temperature 

Sensor Error 

AJ 

Filter Cleaning Reminding 

db 

Special Code: 

Project Debugging Code

 

dL 

Outlet Air Temperature 

Sensor Error 

 

 

 

 
CHECKING UNITS PRIOR TO CONTACTING YOUR TECHNICIAN 

 

 

 

Do not repair the air conditioner yourself. An Incorrect repair may cause electric shock or fire, so please 
contact an authorized service center for professional repair. 
 
 
 

Summary of Contents for VRFI-07EW-D2B(55)5

Page 1: ...des and all related documents manuals provided by YMGI Failure to follow and adhere to all codes and documentation can cause damage to equipment property even personal injury Installer Must be current...

Page 2: ...Unit Diagram 13 Specification Sheet 14 Unit Dimensions Mounting Bracket Clearance 15 Wiring Diagrams 16 Recommended Tools for Installation 17 System Layout Installation Clearance 18 Installation Locat...

Page 3: ...nsible management of refrigerants HVAC R technicians must know the applicable laws and follow them Disposal Notice Do not dispose this product or its components as unsorted municipal waste as they con...

Page 4: ...void personal injury or property damage do not disassemble the unit yourself If disassembly is required to check the unit contact your authorized system installer or HVAC professional as they have the...

Page 5: ...and licensed personnel to install Reading and following YMGI Group recommendations and requirements contained in the following pages and other documents is the first step to help ensure a smooth insta...

Page 6: ...ures at time of installation 2 Not installing an oil P trap in the copper suction line where the indoor unit is located 18 feet or more below the outdoor unit 3 Cross piping and or cross wiring of any...

Page 7: ...d wiring cable sets to keep from cross piping or cross wiring in multiple zone installations or where pipes for different single zone systems are close to one another 13 Secure the wiring cables that...

Page 8: ...I Group whichever comes first This is a standard limited liability warranty and DOES NOT cover the following Any damage or repairs to properties or persons as an incident of or consequence of improper...

Page 9: ...ip the parts ASAP Expedited shipping is available at the customer s expense 4 Replacement parts that have an approved warranty registration are to be warranted for the remainder of the 1 year on parts...

Page 10: ...ed certified HVAC installation professional to prevent any unexpected charges because of unethical business practices 5 Check their references verify they provide professional service for their custom...

Page 11: ...door units room temperature too low keeping the temperature difference between indoor and outdoor unit within 41 5 18 YMGI Group recommends that only properly trained and authorized personnel be allow...

Page 12: ...f all circuits prior to inspecting or servicing the unit Inspecting and servicing the unit while the power supply is connected and the circuits are switched on could cause an electrical shock or fire...

Page 13: ...Operating Condition Indoor Side Condition Outdoor Side Condition Dry Bulb Temp C F Wet Bulb Temp C F Dry Bulb Temp C F Wet Bulb Temp C F Rated Cooling 27 80 6 19 66 2 35 95 24 75 2 Rated Heating 20 6...

Page 14: ...iquid Connecting Pipe Dia In 1 4 1 4 1 4 1 4 3 8 Gas Connecting Pipe Dia In 3 8 3 8 3 8 3 8 5 8 Drain Pipe External Dia In 11 16 11 16 11 16 11 16 1 1 16 Drain Pipe Thickness In 1 16 1 16 1 16 1 16 1...

Page 15: ...ay appear differently than what is the above illustration Electrical Installation Model Power Supply MCA A MOP A VRFI 07EW D2B 55 5 208 230V 1ph 60Hz 1 15 VRFI 09EW D2B 55 5 1 15 VRFI 12EW D2B 55 5 1...

Page 16: ...Knife Scissors Goggled Glasses Mask Gloves Ladder 2 Refrigeration Related Work Flat Surface Wrench Two Flare Nut Tool Set Hex Head Key Set Torch for AC Application Heat Absorption Flux Nitrogen Soap...

Page 17: ...SYSTEM LAYOUT INSTALLATION CLEARANCE...

Page 18: ...SYSTEM LAYOUT INSTALLATION CLEARANCE...

Page 19: ......

Page 20: ......

Page 21: ...t for the wall before or during construction and before installation Read installation instructions for all units thoroughly Ask rep distributor YMGI Group anything you are not sure about Get your too...

Page 22: ...ngth ft Max Length ft Max Rise Height ft Max Drop Height ft 07K 12K 15 50 20 28 18K 24K 15 75 25 35 30K 36K 15 100 35 50 INSTALL THE WALL MOUNTING PLATE Prior to installing the mounting plate check th...

Page 23: ...he bottom side facing the front of indoor unit of the indoor unit snap off portion 2 on plastic casing If pipes need to come out of the left side facing the front of indoor unit of the indoor unit sna...

Page 24: ...ecure the connections HANG INDOOR UNIT Run copper set wire cables drain hose through the wall hole and hang the indoor unit onto the mounting plate place the hook on the mounting plate into the hangin...

Page 25: ...1 2 24K 1 4 5 8 1 4 5 8 3 8 5 8 Running Interconnecting Refrigerant Lines Use clean refrigeration grade copper pipe only Keep the copper lines from kinking and transmitting any noise to walls cabinet...

Page 26: ...Pipes Sweat Connection In this case wrap a wet rag around the pipe to protect the valves or other components from being overheated When using flux rub the tube surface using steel wool to any oxidatio...

Page 27: ...d shot pipes REMOTE CONTROL BUTTON NAME AND FUNCTIONS NOTE 1 This is a general use remote control that can be used for numerous air conditioning model numbers There may be some buttons on the remote t...

Page 28: ...ear from the remote screen ON OFF BUTTON Press this button to turn the unit on Press once more to turn the unit off When turning the unit ON OFF the TIMER and SLEEP functions will be canceled The pres...

Page 29: ...mperature When the TEMP button is pushed twice the indoor unit will display the room temperature for approximately 5 seconds before going back to the set temp SWITCH BETWEEN F AND C The remote default...

Page 30: ...e is located as its target temperature control Once you do so you will notice a figure of a person surrounded by stars appear on the remote Once the I FEEL stars appear the remote will send a signal f...

Page 31: ...frost mode is enacted the indoor unit will stop running and display an H1 code Once the defrost cycle is finished and the outdoor coil is defrosted the indoor unit will start to run again in the mode...

Page 32: ...l enter AUTO RUN mode The microcomputer will acquire the room temperature to select the COOL HEAT FAN mode automatically to obtain the correct setting Stopping When the unit is running press the ON OF...

Page 33: ...wash the panel or it could cause deformation or discoloration Install front panel Place two supports of the front panel into the slots along the direction of arrows to cover and clasp the front panel...

Page 34: ...disconnecting electrical power disconnect switch 2 Clean filter and unit 3 Cover the unit to keep dust or moisture out of the unit PROTECTION AND ERROR CODES Error Code Content Error Code Content Erro...

Page 35: ...the remote control pointing at sunshine or bright lights 3 Is the remote control signal blocked 4 Is the remote control too far away from indoor unit 5 Is the fuse on indoor unit blown 6 Is the indoor...

Page 36: ...llowing situations 1 Harsh sound is heard 2 Bad odor is detected 3 Water is leaking out of the indoor unit 4 Circuit breaker trips or fuse is blown a few times 5 Wires or connections are very hot 6 Oi...

Page 37: ...Help Did You Ask YMGI Tech for Help USER NOTES Put down whatever questions you have or problems you have seen as a unit history No Date Installation Company Name Technician Name Phone HCAC License Job...

Reviews: