To drain the condensate easily, the drain hose should be inclined downward (pitched towards drain direction
1/4" per foot).
Figures below from the 2nd to 5th show some incorrect practices.
Drain hose may be extended using the hose coming with the installation list.
STUFF AND SEAL THE HOLE FOR COPPER LINE SET/WIRE CABLE/DRAIN HOSE
Use putty to seal the wall hole.
Use clamp (pipe fastener) to secure the
pipe at specified position.
INSTALLATION-INDOOR UNIT
SHAPE THE DRAIN HOSE
REFIT DRAIN HOSE FROM THE RIGHT TO THE LEFT SIDE
If drain hose needs to be refitted from the original
position (right side) to left side of the indoor unit,
careful handing is very necessary.
Refitting method: remove the drain hose from
original position, without breaking hose. Unplug
the plug at the left side. Apply water-resistant glue
to fit the drain hose and the fitting before securing
it.
Apply water-resistant glue onto the plug and fit it
back into the condensate connection at right side.
NOTES: May use some sort of clamp to double secure connections.
Condensate connection
at left side
Drain hose
HANG INDOOR UNIT
Run copper set/wire cables/drain hose through the
wall hole and hang the indoor unit onto the
mounting plate (place the hook on the mounting
plate into the hanging rib at rear side of plastic
casing).
Snap the plastic casing bottom into the mounting
plate, gently .
Sealed with putty
Secure the piping/
wiring set with clamp
Trim the extra portion.
2 in or less
from floor
>18"
>18"
Brackets
Heavy-Duty PVC Riser
Coated Brackets
W A ccessories
Bracket Accessories
INSTALLATION & PICTURES-WALL MOUNT BRACKET FOR OUTDOOR UNIT(S)
(PART VARIES UPON MODELS/AVAILABILITY)
INSTALLATION-OUTDOOR UNIT
INSTALL OUTDOOR UNIT
Select a secured location where the outdoor unit will be installed properly.
Orient the unit rear side (intake grill) towards wall and front side (discharge grill) away from wall.
For ground installation, use factory-provided riser and accessories. Not to bolt unit feet directly onto ground.
Riser or brackets shall be levelled at outdoor unit foot surfaces. Secure unit foot by tightening bolts, nuts and
anti-vibration pads.
For wall mount installation, use factory-provided brackets, anchors and accessories.
Strongly suggest to install the outdoor unit above the ground either on platform or brackets as shown below.
Heat pump unit must be lift up from ground level, since condensate must be drained out of the drain pan in
condensing unit; othewise, condensate may be iced up to damage the condensing unit.
Suggest to use YMGI-provided brackets and condensate drainage fitting accessories.
(Actual unit/parts looking/installation may vary from the illustrated)