YMGI M2 SERIES Installation Instruction Download Page 13

INST

ALLER'S 

INSTRUCTION

INST

ALLER'S 

INSTRUCTION

P24 OF 44

P23 OF 44

INSTALLATION LOCATIONS & CAUTIONS

All Units Shall Be Installed by Licensed Contractor or Technician.

Read Manuals before Installation.

* The location and structure shall also be convenient for both installation and service.

* The location shall NOT be where discharge air and noise could bother your neighbor.

* The location shall NOT be somewhere drain may cause any damage to property or bother the neighbor.

* The location shall NOT be somewhere soldering or torching work may cause fire or smoke to the 
  materials around.

* The location shall NOT be somewhere near flammable gases.

* The location shall NOT be in or close to corrosive gases.

* The location shall NOT be somewhere children can access.

Check the unit for damage and missed parts or accessories. If damage is found or parts are found missing, call 
the distributor right away.

Spin fan wheels or blades to check if and make sure they can rotate freely. If fan wheel scratches with housing, 
call the distributor right away and do not to proceed with the installation before it is fixed.

Check the unit to make sure no foreign materials has been left in the unit.

Check all the parts and accessories that are needed other than those provided with the unit. 
It is strongly recommended to only use YMGI supplied or recommended parts and accessories.

Be sure a properly sized circuit breaker is for the electric power to the units.

Pre-build the support platform on the ground or bracket for the wall before or during construction and before 
installation. Refer to the table below for footprint dimensions.

Read installation instructions of all units thoroughly.

Ask rep./distributor/us anything you are not sure about.

Get your tools and parts ready for installation.

CAUTION & SUGGESTIONS TO FOLLOW PRIOR TO INSTALLATION

INSTALLATION POSITIONS FOR OUTDOOR UNIT

* To be installed at the position where the air delivered from the unit can reach every comer of the room.

* To avoid being affected by the outdoor air.

* To avoid blockage to the air inlet or outlet of the unit.

* To avoid too much oil smoke or steam.
* To avoid possible generation, inflow, lingering or leakage of flammable gases.

* To avoid high-frequency facilities (such as high frequency arc welders, etc.).

* To avoid the places where acid solutions are frequently used.

* To avoid the places where some special sprayers (sulfides) are frequently used.

* Not to install on top of the musical instruments, TV, computer etc. valuable appliance.

* Not to install a fire alarming device near the air outlet of the unit (during operation, the fire alarm device might 
  be erroneously triggered by the warm air from the unit).

CONNECTION OF PIPES AND WIRES

GET READY FOR INSTALLATION

Note:

* The environment conditions must be taken into consideration when the connections of power cable are made 
  (such as the ambient temperature, direct exposure to heat/dirext exposure to sunlight).

* The specifications for the power cable refer to the minimum values of the metal core wires, taking into 
  consideration the voltage losses, the core wire of power cable must be one size larger than the specifications.

* The grounding wire must be connected to the indoor units and outdoor units.

* The laying of power cables must be done by qualified electricians and comply with the regulations of the local 
  power supply authorities and with the standards of the electric appliance.

1

2

3

4

5

6

7

1

2

3

4

5

1 Pcs.

1 Set

1 Pcs.

2 Pcs.

1 Pcs.

1 Pcs.

1 Pcs.

MISC. ITEMS COMING WITH INDOOR UNIT

Mounting plate

Manuals (User/ Installation/ Wiring/ Diagram)

Remote control

Battery

Drain spout for outdoor drain pain

Warranty registration card

QC Pass

OPTIONAL ACCESSORIES THAT ARE PACKAGED AND MAY BE SOLD SEPARATELY

Installation kit (copper line/wire/drain hose & others)

Power and control and or intercommunication cable

Foot rise or brackets for outdoor unit

Line set covers

Wind baffie

PIPING AND WIRING SIZES-UNITS MADE AFTER 05/2010

Model  Liquid/

Gas Line 

Min/Max.
Length/
+/-Elevation 

Power Wire 

Disconnect Switch Box to 
Outdoor Unit 

Power/ Control Wire 

Outdoor to Indoor Unit 

HVAC Circuit 
Breaker/Fuse AMP 

(to Outdoor Unit) 

09K

12K

18K

24K

30K

36K 

1/4” & 3/8”

1/4” & 1/2”

3/8” & 5/8”

3/8” & 5/8”

3/8” & 5/8”

3/8” & 5/8”

15/70/25/35

15/70/25/35

15/100/30/50

15/100/30/50

15/100/30/50

15/100/30/50

L1/N1/G, 115 or 230/1/60, 14/16AWG 

L1/N1/G, 115 or 230/1/60, 12/14AWG 

L11/L22/G, 208-230/1/60, 14AWG 

L11/L22/G, 208-230/1/60, 12AWG 

L11/L22/G, 208-230/1/60, 10AWG 

L11/L22/G, 208-230/1/60, 8AWG 

AC:1/3, HP:1/3/4, 115 or 230/1/60, 16AWG 

AC:1/3, HP:1/3/4, 115 or 230/1/60, 16AWG 

AC:1/3, HP:1/3/4, 208~230/1/60, 16AWG 

AC:1/3, HP:1/3/4, 208~230/1/60, 16AWG 

AC:1/3, HP:1/3/4, 208~230/1/60, 16AWG 

AC:1/3, HP:1/3/4, 208~230/1/60, 16AWG 

20/10, 25/20 

25/10, 35/15

20, 25

25, 30

30, 40

35, 45

PIPING AND WIRING SIZES-UNITS MADE BY 05/2010

Model  Liquid/

Gas Line 

Min/Max.
Length/
+/-Elevation 

Power Wire 

Disconnect Switch Box to 
Outdoor Unit 

Power/ Control Wire 

Outdoor to Indoor Unit 

HVAC Circuit 
Breaker/Fuse AMP 

(to Outdoor Unit) 

09K

12K

18K

24K

30K

36K 

1/4” & 3/8”

1/4” & 1/2”

3/8” & 5/8”

3/8” & 5/8”

3/8” & 5/8”

3/8” & 5/8”

15/70/25/35

15/70/25/35

15/100/30/50

15/100/30/50

15/100/30/50

15/100/30/50

L1/N1/G, 115 or 230/1/60, 14/16AWG 

L1/N1/G, 115 or 230/1/60, 12/14AWG 

L11/L22/G, 208-230/1/60, 14AWG 

L11/L22/G, 208-230/1/60, 12AWG 

L11/L22/G, 208-230/1/60, 10AWG 

L11/L22/G, 208-230/1/60, 8AWG 

AC:1/2, HP:1/2/3/4, 115 or 230/1/60, 14AWG 

AC:1/2, HP:1/2/3/4, 115 or 230/1/60, 14AWG 

AC:1/2, HP:1/2/3/4, 208~230/1/60, 14AWG 

AC:1/2, HP:1/2/3/4, 208~230/1/60, 14AWG 

AC:1/2, HP:1/2/3/4, 208~230/1/60, 14AWG 

AC:1/2, HP:1/2/3/4, 208~230/1/60, 14AWG 

20/10, 25/20 

25/10, 35/15

20, 25

25, 30

30, 40

35, 45

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Summary of Contents for M2 SERIES

Page 1: ...his product is designed and manufactured free from defects in material and workmanship under the normal use and maintenance Installation operation maintenance and service shall follow professional pra...

Page 2: ...y parts may be new or refurbished All parts are tested and approved before shipping At no time does the YMGI Group warrant labor cost of any type Warranty will start from the date of successful instal...

Page 3: ...nit for condensate leakage and refrigerant leakage before and after connecting them 28 Do you list the working details in the invoice and leave a copy to the customer 19 Did you charge the inter conne...

Page 4: ...roperly can be more expensive than spending the little extra money that hiring the right contractor will cost Protect your investment and warranty eligibility by doing it right the first time THE FOLL...

Page 5: ...e ability to claim freight damage is lost and YMGI will not replace the unit on this basis Contact the distributor or YMGI report the damage by forwarding the marked delivery receipt copy and pictures...

Page 6: ...Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to the YMGI Group 3 Once the form has been completed and sent bac...

Page 7: ...ed to keep from cold air blowing into propeller fan blade against airflow and so help unit work better in both AC cooling and HP heating mode in colder weather ranges IMPORTANT NOTES FOR UNIT OPERATIO...

Page 8: ...n the ground Once stacking or bracket kit is used some outdoor units can be stacked 2 or 3 units high upon unit size and applications Air is discharged horizontally quietly and smoothly These units ar...

Page 9: ...X24K 32B WMMS 2X30K 32B WMMS 09E F 32B WMMS 09 12E F 32B WMMS 12E F 32B WMMS 18E F 32B WMMS 24E F 32B WMMS 30E F 32B WMMS 2X09C 32B WMMS 0912C 32B WMMS 2X12C 32B WMMS 2X18C 32B WMMS 2X24C 32B WMMS 2X3...

Page 10: ...4K 2 30K 3 09K 2 12 18K 3 12K 2 18 24K 2 09 12K 2 09 12 K 2 12 24K 3 12 24K Varies Varies Varies UNIT ENGINEERING SUBMITTALS MECHANIAL 09K 12K W H D 30 9 36 2 10 6 10 6 7 8 7 9 18K 24 36K 40 2 12 4 9...

Page 11: ...thly without any abnormal noise or restriction 4 Fan wheel roration at outdoor unit should rotate freely and smoothly without any abnormal noise or restriction 5 No kinking or other leaking potentials...

Page 12: ...ctricians only following NEC codes and manufacturer instructions CONNECTION OF WIRES SINGLE ZONE WIRING AT INDOOR UNIT AND OUTDOOR UNITS Open the front cover panel Remove screws from electrical box co...

Page 13: ...taken into consideration when the connections of power cable are made such as the ambient temperature direct exposure to heat dirext exposure to sunlight The specifications for the power cable refer...

Page 14: ...CLEARANCE REQUIRED AROUND UNITS SINGLE ZONE CLEARANCE REQUIRED AROUND UNITS DUAL ZONE Indoor unit B Indoor unit A SYSTEM LAYOUT INSTALLATION CLEARANCE YMGI Engineered Comfort Products for A Sustainabl...

Page 15: ...ndoor unit C SYSTEM LAYOUT INSTALLATION CLEARANCE Indoor unit A Indoor unit B Indoor unit C Indoor unit D SYSTEM LAYOUT INSTALLATION CLEARANCE YMGI Engineered Comfort Products for A Sustainable and Ef...

Page 16: ...screws Align mounting plate holes with those holes drilled on the wall and put anchors or screws into the holes to secure mounting plate STEPS TO MOUNT PLATE a b c Drill mounting holes to make sure a...

Page 17: ...rear side of plastic casing Snap the plastic casing bottom into the mounting plate gently Sealed with putty Secure the piping wiring set with clamp Trim the extra portion 2 in or less from floor 18 18...

Page 18: ...35 45 CONNECT REFRIGERANT PIPES BETWEEN INDOOR AND OUTDOOR UNITS Firstly connect copper tubes at indoor unit Bend pipes by tools but not by hands Extra length is needed for future service REFRIGERANT...

Page 19: ...ipes Over length soft pipes will lead to irregular bending Undersize bending will damage the soft pipe Short soft pipes will have them bending undersize it s not allowed INLTS STRT COUP COUP H OFST EL...

Page 20: ...ks 1 Blink lit for 0 5 sec then off for 0 5 sec then lit for 0 5 sec 2 E4 Code Outdoor ambient temperature is too low do not to run unit during severe cold weather Refrigerant at low level users need...

Page 21: ...hnician to make appointment with YMGI tech support and call us while the techician is at job site 4 Better to check the unit get problems and model model and serial ready before calling YMGI tech supp...

Page 22: ...STALLATION OF MULTIPLE ZONE SYSTEMS MULTIPLE COMPRESSORS IMPORTANT NOTES FOR INSTALLATION OF MULTIPLE ZONE SYSTEMS MULTIPLE COMPRESSORS YMGI Engineered Comfort Products for A Sustainable and Efficient...

Page 23: ...original licensed installer or current service contractor should be contacted first of all since they installed the unit and or know more details than anybody else They will check the unit and find o...

Reviews: