GB Modules Installation and User Manual  Page 2 

De-energize  PV  modules  by  removing  them  entirely  from  light  or  by  covering 

their  front  surface  with  an  opaque  material.  Regard  the  safety  regulations  for 

live  electrical  equipment  when  working  with  modules  that  are  exposed  to  any 

light. Use insulated tools and do not wear metallic jewelry while working with PV 

modules.

In  order  to  avoid  arcing  and  electrical  shock,  do  not  disconnect  electrical 

connections  under  load.  Faulty  connections  can  also  result  in  arcing  and 

electrical  shock.  Keep  connectors  dry  and  clean,  and  ensure  that  they  are  in 

proper  working  condition.  Never  insert  metallic  objects  into  the  connectors,  or 

modify them in any way in order to secure an electrical connection.

Do  not  touch  or  handle  PV  modules  with  broken  glass,  separated  frames  or 

a  damaged  backsheet  unless  the  PV  modules  are  first  disconnected  and  you 

are wearing proper PPE. Avoid handling PV modules when they are wet unless 

cleaning  the  PV  modules  as  directed  in  this  manual.  Never  touch  electrical 

connections that are wet without protecting yourself with insulated gloves.

Transport and Handling

Yingli Solar PV modules must be transported in the supplied packaging only and 

kept in the packaging until they are ready to be installed. Protect pallets against 

movement and exposure to damage during transportation. Secure pallets from 

falling  over.  Do  not  exceed  the  maximum  height  of  pallets  to  be  stacked,  as 

indicated on the pallet packaging. Store pallets in a cool and dry location until the 

PV modules are ready to be unpackaged.

Figure 2: Pallet of PV modules

Yingli Solar PV modules are heavy, and should be handled with care. PV modules 

shall be handled at the frame; never use the junction box or cables as a grip. Do 

not exert mechanical stress on the cables. Never step on PV modules or drop 

or place heavy objects on them. Be careful when placing PV modules on hard 

surfaces, and secure them from falling. Broken glass can result in personal injury. 

PV modules with broken glass cannot be repaired and must not be used. Broken 

or damaged PV modules must be handled carefully and disposed of properly.

For unpacking PV modules from the Yingli Solar supplied packaging, first remove 

the pallet lid (after removing securing straps, if provided). Remove PV modules 

one at a time by sliding them up the channel in the package (see Figure 3). You 

may need to secure the remaining PV modules in the pallet packaging to prevent 

them from falling over. 

 
 

Figure 3: Removing PV modules from a pallet

Check PV modules for damage due to transportation before they are installed; 

do not install damaged modules. Contact the company you purchased the Yingli 

Solar  PV  modules  from  in  order  to  obtain  information  on  making  claims  for 

defective PV modules. 

PV module surfaces are susceptible to damage that could affect the performance 

or safety of the PV module; do not damage or scratch the PV module surfaces, 

and do not apply paint or adhesive to any of the surfaces, including the frame. For 

your safety, do not disassemble or modify Yingli Solar PV modules in any way. 

Doing so may degrade performance or cause irreparable damage and will void 

any applicable warranties. 

If it is necessary to store PV modules prior to installation, the PV modules should 

remain inside the packaging and protected from exposure that could compromise 

the durability of the packaging. 

Fire

Yingli Solar PV Modules have a Class C fire resistance rating in accordance with 

the IEC 61730-2 certification. When PV modules are mounted on rooftops, the 

roof must have a fire resistant covering suitable for this application. PV modules 

are electrical generating devices that may affect the fire safety of a building.

The use of improper installation methods and/or defective parts may result in the 

unexpected occurrence of an electrical arc during operation. In order to mitigate 

the risk of fire in this event, PV modules should not be installed near flammable 

liquids, gases, or locations with hazardous materials. 

In the event of a fire, PV modules may continue to produce a dangerous voltage, 

even  if  they  have  been  disconnected  from  the  inverter,  have  been  partly  or 

entirely  destroyed,  or  the  system  wiring  has  been  compromised  or  destroyed. 

In the event of fire, inform the fire crew about the particular hazards from the PV 

system, and stay away from all elements of the PV system during and after a fire 

until the necessary steps have been taken to make the PV system safe.

A P P L I C A T I O N   I N F O R M A T I O N

Application Restrictions

Yingli Solar PV modules must be mounted on appropriate installation structures 

positioned on suitable buildings, the ground, or other structures suitable for PV 

modules (e.g. carports, building facades or PV trackers). PV modules must not 

be mounted on moving vehicles of any kind. Yingli Solar PV modules must not be 

installed in locations where they could be submerged in water. 

Yingli  Solar  PV  modules  must  not  be  sited  in  locations  where  aggressive 

substances such as salt or salt-water, or any other type of corrosive agent, could 

affect the safety and/or performance of the PV modules. Although some types 

of Yingli Solar PV modules have passed the IEC 61701 salt-mist corrosion test 

with a salt concentration of 5% by weight, galvanic corrosion can occur between 

the aluminum frame of the PV module and installation or grounding hardware if 

such hardware is comprised of dissimilar metals. Yingli Solar recommends that 

only stainless steel and aluminum metal directly contact PV modules in seaside 

installations to limit corrosion. 

Artificially concentrated light must not be directed on Yingli Solar PV modules

Design Recommendations

Yingli Solar recommends that PV modules be mounted at a minimum tilt angle of 

10 degrees to allow for proper self-cleaning from normal rain showers.

Partial or complete shading of a PV module or modules can significantly reduce 

system performance. Yingli Solar recommends minimizing the amount of shade 

throughout  the  year  to  increase  the  amount  of  energy  produced  by  the  PV 

modules.

Lightning protection is recommended for PV systems that are to be installed in 

locations with high probability of lightning strikes.

High system voltages could be induced in the event of an indirect lightning 

strike, 

which could cause damage to PV system components. The open area of wire 

loops should be minimized, as shown in Figure 4, in order to reduce the risk of 

lightning induced voltage surges.

Summary of Contents for YLM 144CELL 182PERC

Page 1: ...ication requirements has been verified by an independent certification laboratory This Installation and User Manual is available in different languages In cases of discrepancy between versions the Eng...

Page 2: ...ng so may degrade performance or cause irreparable damage and will void any applicable warranties If it is necessary to store PV modules prior to installation the PV modules should remain inside the p...

Page 3: ...suitable cross sectional areas that are approved for use at the maximum short circuit current of the PV module Yingli Solar recommends installers use only sunlight resistant cables qualified for dire...

Page 4: ...ult in galvanic corrosion An addendum to UL Standard 1703 Flat Plate Photovoltaic Modules and Panels recommends metal combinations not exceed an electrochemical potential difference of 0 5 Volts The f...

Page 5: ...hment Figure 12 Installation rails The large size modules are mounted with four outer holes with max mechanical loads of 5400 Pa snow front and 2400 Pa wind back Top down Clamps Third party clamps tha...

Page 6: ...e materials that could scratch or damage the glass surface Failure to comply with these requirements may adversely affect the PV module performance Yingli Solar PV modules are designed to withstand hi...

Page 7: ...l characteristics are within 10 percent of the indicated values of Isc Voc and Pmax under Standard Test Conditions irradiance of 1000 W m2 AM 1 5 spectrum and a cell temperature of 25 Refer to module...

Page 8: ...f 14 20 N m The tightening steps as follows use torque wrench to tighten nut to target torque nut loosen 90 180 degrees finally tighten the nut to the target torque and reduce the torque attenuation 2...

Page 9: ...ashers of minimum 1 4 mm thickness with an minimum outer diameter of 15 57 mm Modules can be attached using the mounting holes the number of mounting holes used for a single long side frame 2 includin...

Page 10: ...when it is pressed down L represents the length of the long side of the module the described distances are from the module edge to the middle of the clamp The long side frames of the module are fixed...

Page 11: ...ropes are required to secure the modules to the forklift with a tensile strength greater than 2000 kgf 2 Pass the forearm of the anti tilting bracket through the pallet insert the two bolts into the...