Page  12 / 19 

 
 
 

26.12.2011     

                LFM-02-e 

                      Rev Nr: 7 

 

 

 

 

 

 

 

2.6.2 

General maintenance 

 

 

Yenen developed several spare part kits for maintaining the meter. Partial or other repairs should not 
be attempted as this may jeopardize the safety and accuracy of the meter.   
 

 

Only trained, qualified and certified  personnel familiar with handling  liquids under pressure, such 
as LPG, may service Yenen equipment 
 

 

Installation  details  of  the  spare  part  kits  are  provided  with  the  kit  itself.  With  the  meter 
disassembled it is recommended that you perform a visual inspection of the entire meter:  
 

 

Check  the  o-rings.  O-rings  should  be  smooth.  Cracked,  warn  or  dry  o-rings  need  to  be, 
replaced. Also, scratched o-rings may cause inaccuracy of the meter.  

 

Check  the  gaskets.  Gaskets  should  be  firm,  but  flexible.  Cracked,  worn  or  torn  gaskets 
need  to  be  replaced.  Scratched  gaskets  may  cause  internal  leaks,  which  causes  the  
meter to be inaccurate.  

 

Check  fasteners  and  threads.  There  should  be  no  debris  in  threads.  Fasteners,  such  as 
bolts  and  screws,  should  be  straight  and  clean.  Fasteners  that  are  bent,  rusted  or  have 
pulled  threads  should  be  replaced.  If  such  fasteners  are  found,  it  is  recommended  to 
examine the housing and covers for such damage also. 

 

Check  the  paint.  When  removing  fasteners  the  coating  may  be  damaged.  To  prevent 
corrosion re-apply coating and paint. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for LPG Flow Meter

Page 1: ...LPG Flow Meter Installation and Operation Manual Manual LPG Flow Meter IOM Manual code LFM 02 e Number of pages 19 Issue date August 23 2004 Review number 7 Last review date December 26 2018...

Page 2: ...nes The remarks and warnings inform the operator of the hazards involved in working with Yenen meters Reading these instructions and preventing hazardous situations is strictly in the hands of the ope...

Page 3: ...rs Accuracy class 1 0 Environmental class M2 E1 Maximum permissible error 1 0 1 2 Safety precautions Only trained and qualified personnel familiar with handling liquids under pressure such as LPG may...

Page 4: ...e fluid is being submitted into a cylinder through the distribution valve At the same time the fluid ahead of it is being displaced out of the meter through the outlet Four pistons in the cylinders ar...

Page 5: ...ter The serial number is related to a date code YYMM9999 For example a meter with serial number 01101234 is manufactured in October 2001 with serial number 1234 Record the meter serial number and mode...

Page 6: ...nt range and 0 5 in steps of 0 05 Accuracy curve Flow rate liters per minute Pressure drop curve Flow rate liters per minute 2 2 Installation requirements Make sure that all internal pressure is relie...

Page 7: ...It is of vital importance for functionality and accuracy that dirt dust and other debris does not enter the meter Ensure that the entire piping system is free from dirt dust and debris as this may af...

Page 8: ...Page 8 19 26 12 2011 LFM 02 e Rev Nr 7 2 3 Meter dimensions 118 5 118 5 320 238 118 5 153 INLET OUTLET FOR RELIEF VALVE FRONT VIEW OUTLET BOTTOM BOTTOM VIEW Figure 2 Flowmeter General Dimensions...

Page 9: ...ilter should be replaced regularly Especially in the first month of operation the filter should be checked and replaced at least twice a month 1 Nozzle 2 Break away coupling 3 Differential valve 4 Met...

Page 10: ...ground or submersible pump Make sure that the pump can operate against closed valves or with limited flow 2 6 Meter maintenance Make sure that all internal pressure is relieved before disassembly or i...

Page 11: ...te the pressure The pressure value has to be higher than tank pressure with approximately 2 3 bars Run roughly 10 liters of nitrogen through the system to flush all LPG back to the storage tank Close...

Page 12: ...Check the o rings O rings should be smooth Cracked warn or dry o rings need to be replaced Also scratched o rings may cause inaccuracy of the meter Check the gaskets Gaskets should be firm but flexib...

Page 13: ...er The distribution valve has a precision polished surface Even the slightest scratch or unevenness will cause inaccuracy of the meter Recalibration after re assembly of the meter is recommended Meter...

Page 14: ...rities may break and reseal dispensers Remove the seal Unbolt the adjustment cover on the flow meter Figure 5 Adjustment disc with shaft Calibration is accomplished with a series of holes at the adjus...

Page 15: ...ion and shipping Flow meter should not be removed from its packing during transportation and storage packaging Be careful about the directional arrows on the meter box during the transportation Do not...

Page 16: ...any LPG related work on the forecourt DO be aware of vapors and other hazardous conditions DO disconnect and lock power before starting to service the meter and other hydraulic parts DO know the assoc...

Page 17: ...r maintenance is complete DON T allow smoking flame or spark producing devices near the work area DON T place tools or equipment outside the barricaded work area DON T place tools or equipment outside...

Page 18: ...rge valves Check valve Manometer Safety relief valve Common connections on the hydraulic set 3 17 19 metric wrench 3 4 NPT connections Hydraulic connectors Break Away Access Flow Valve Nozzle Differen...

Page 19: ...Page 19 19 26 12 2011 LFM 02 e Rev Nr 7 Ak emsettin Mahallesi Tavuk uyolu Sokak No 23 Sultanbeyli 34925 Istanbul T rkiye T 90 216 487 5924 F 90 216 487 5986 E info yenen com www yenen com...