7
Troubleshooting Guide
*UL Certified Rates to ARI Standard 740
-
2016
Other Refrigerants
-
The
RecoverXLT
®
is approved for use with other refrigerants which have not
been certified for a particular recovery rate including: R
-
32, R
-
401A, R401B, R
-
402A, R
-
402B,
R
-
404A, R
-
406A, R
-
407A, R
-
407B, R
-
407C, R
-
407D, R
-
408A, R
-
409A, R
-
411A and R
-
411B.
RecoverXLT
®
R
-
12
R
-
134a
R
-
22
R
-
500
R
-
502
R
-
410A
Vapor lbs./min
.37
.37
.37
.37
.66
.42
Liquid lbs./min
1.98
1.98
1.98
1.98
2.65
1.68
Push
-
Pull lbs./min
12.81
12.81
12.81
12.81
12.9
11.6
Vacuum Level
15 inHg
15 inHg
15 inHg
15 inHg
15 inHg
15 inHg
*If the attached power cord is damaged (95215)
it must be replaced by the manufacturer or its author-
ized service center in order to avoid hazard.
TECHNICAL DATA
Condition
Possible Problem
Possible Solution
Unit will not turn ON
Unit not properly plugged in or
no power at power source
Check power cord to ensure properly
plugged into power source and IEC inlet
Defective Power Switch or PCB
Replace defective electrical component
Recovery process is slow
Clogged Filter
Check INLET port filter, clean or replace
Valve core on system being
recovered not fully depressed
Check core depressor on connecting
hoses
Compressor seals are worn
Rebuild compressor, replace piston seal
Unit does not pull a vacuum
Loose hose connections on Inlet
Side
Tighten hose connections
Compressor seals are worn
Rebuild compressor, replace piston seal
Hoses are not tight
Tighten hoses
Leak in HVAC/R system
Find and repair leak in system
Unit running sluggish
Low voltage to unit
Check power supply
Unit runs but shuts off after
short time
Restriction on discharge side
tripping the high pressure
switch
Check for restrictions
1) Tank valves
2) Schrader cores
Selector valve in correct position
Vacuum switch won’t reset
Switch needs to reset
Pressurize inlet port
RED LED Code
Fault Indicated
Possible Solution
2 Flashes
Optional Tank Over-
fill
Sensor has been
activated
Tank overfill sensor has activated, recovery tank is full and needs to be replaced.
Tank overfill sensor cord not connected. Either connect to a recovery tank
equipped with overfill sensor or install a shorting plug on the end of the Tank
Overfill Sensor cord.
3 Flashes
High Pressure Switch
has
been activated
Pressure on the discharge of the unit exceeded 517 PSIG. Check to make sure all
valves in the discharge pathway are open. Once corrected, the pressure switch
will reset.
Excessive pressure in recovery tank. Replace recovery tank.
4 Flashes
Motor Overload
Let cool down for 15 minutes and restart.
Compressor Mechanism is jammed. Repair will be required to fix the compres-
sor mechanism.
5 Flashes
Low Voltage
Detected
Check to see if power source is in the range of the nameplate rating.
6 Flashes
High Voltage
Detected
Check to see if power source is in the range of the nameplate rating.