background image

 

water  is  cooled  to  44.6°F 

(7°C)

  while  the 

refrigerant 

vapor 

is 

attracted 

to  the 

concentrated  solution  dripping  over  the 
absorber tubing bundle. 

Absorber 

 A  deep  vacuum  in  the  absorber  is 

maintained by the affinity of the concentrated 
solution  from  the  LGE  for  the  refrigerant 
vapor formed in the evaporator.  Refrigerant 
vapor  is  absorbed  by  the  concentrated 
lithium  bromide  solution  flowing  across  the 
surface  of  the  absorber  tube  bundle.    The 
heat  of  condensation  and  dilution  are 
removed by the cooling water and rejected to 
a cooling tower.  The resulting dilute solution 
is preheated through heat exchangers before 
the  solution  pump  returns  it  to  the  HGE 
where the cycle is repeated.  

 

 

Figure 1 

– DOUBLE-EFFECT 

ABSORPTION CYCLE (COOLING) 

HEATING OPERATION 

High Temperature Generator 

(HGE)

 

The  solution  boils  in  the  HGE  and 

superheated  refrigerant  vapor  and  semi-
concentrated  solution  flow  into  the  primary 
separator  in  exactly  the  same  manner  as  in 
the cooling cycle. 

Low Temperature Generator 

(LGE) 

In  Heat  mode,  the  changeover  valve 

opens  a  path  for  the  semi-concentrated 
solution  to  flow  out  of  the  primary  separator 
directly  into  the  Absorber/Evaporator  sump.  
Therefore, 

the 

LGE 

and 

both 

heat 

exchangers  are  completely  bypassed  while 
in Heat mode. 

Condenser/Absorber 

 

It  is  imperative  that  there  be  NO 

COOLING WATER FLOW in the Heat mode.  
As  such,  neither  the  Condenser  nor  the 
Absorber have any function in Heat mode. 

Evaporator 

Since  the  Evaporator  acts  as  the 

Condenser  in  Heat  mode,  hot  refrigerant 
vapor  condenses  on  the  surface  of  the 
evaporator  coil  and  heat,  equivalent  to  the 
latent heat of the refrigerant, is transferred to 

the  hot  water  circuit,  heating  it  to  a  leaving 
temperature of 131°F 

(55°C)

.  The condensed 

refrigerant  drips  off  the  evaporator  and  into 
the  absorber  sump  where  it  mixes  with  the 
semi-concentrated  solution,  diluting  it  once 
again. 

 

Figure 2 

– DOUBLE-EFFECT 

ABSORPTION CYCLE (HEATING) 

Summary of Contents for CH-K100

Page 1: ...UCTIONS and properly maintained it can provide many years of trouble free operation CONTENTS GENERAL Page ABSORPTION PRINCIPLE 2 COOLING OPERATION 2 HEATING OPERATION 3 CONTROLS GENERAL INFORMATION 4...

Page 2: ...cooled and heat is normally rejected to a cooling tower though ground loop is also an option COOLING OPERATION High Temperature Generator HGE The gas burner heats a dilute lithium bromide solution in...

Page 3: ...nd semi concentrated solution flow into the primary separator in exactly the same manner as in the cooling cycle Low Temperature Generator LGE In Heat mode the changeover valve opens a path for the se...

Page 4: ...y also be supervised and controlled by external control systems to a limited degree when the necessary interconnections are installed Additional controls and interlocks can be explained by your ASP On...

Page 5: ...2 10 Rated 300vac F4 2 Fuji Model FGAO 2 Rated 250vac F11 F12 2 Fuji Model FGAO 2 Rated 250vac F31 F32 1 Fuji Model FGAO 2 Rated 250vac FB11 FB12 2 Fuji Model FGAO 2 Rated 250vac FB21 FB22 15 Nagasaw...

Page 6: ...on the I O Board to ON The leaving chilled water temperature can be adjusted using the TC potentiometer on the CPU Board The leaving chilled water set point can be set in a range of 40 1 F 4 5 C to 59...

Page 7: ...ress the alarm RESET button to restart the cooling or heating operation If Error Code 52 is amongst the codes being displayed it will also be necessary to press the RESET button on the burner controll...

Page 8: ...Gas Pressure Check Supply and Manifold Inhibitor Check If required For the K Series an inhibitor charge is needed every 3 years on average Palladium Cell Heater Check Flow Rate Check Solution Pump Rot...

Page 9: ...s vacuum section Just because the vacuum pump has stopped producing bubbles in the water bucket does NOT mean the vacuum level is adequate A digital vacuum gauge MUST be used in order to determine the...

Page 10: ...iller heater itself as well If doing so pressurize the unit to the same pressure as the circuits using nitrogen See the Service Manual for further details TROUBLESHOOTING SYMPTOM Chiller heater does n...

Page 11: ...iption Notes Reset Type FS Flow switch alarm Chilled hot water flow switch FS1 open but for less than 10 minutes After 10 minutes this changes automatically to error code 27 Auto 01 DCP power error Op...

Page 12: ...10 C or above 212 F 100 C Ignored for first 10 minutes of P2 operation Manual 36 CND sensor error CND sensor reads below 14 F 10 C or above 212 F 100 C Auto 40 Loss of cooling capacity LT temperature...

Page 13: ...13 Please send a copy of any maintenance data sheets to Yazaki Energy Systems Inc at the address FAX number and or email address listed on the last page of this document...

Page 14: ...Labor Charges for warranty service can be obtained by an authorized service provider upon written request to YESI 7 LIMITATION OF WARRANTY AND LIMITATION OF REMEDY CUSTOMER s remedies shall be limite...

Page 15: ......

Page 16: ...MS INC 701 E PLANO PKWY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web http www yazakienergy com This symbol on the product s name plate means i...

Reviews: