background image

 

10 

SHUTDOWN 

The  fluids  within  the  chiller-heater  itself 

need  no  preparation  for  freezing  conditions.  
Only  the  fluids  in  the  chilled  water  and 
cooling  water  circuits  need  to  be  addressed 
during potentially freezing conditions. 

 When the equipment is located outdoors 

in climates subject to freezing, cooling water 
should  be  drained  from  the  chiller-heater, 
fluid  circuit  piping,  and  cooling  tower  at  the 
end  of  the  cooling  season.    Use  glycol  of 
adequate  concentration  in  the  chilled  water 
and  heat  medium  circuits  to  prevent  freeze 
damage.    The  glycol  will  reduce  the  cooling 
and  heating  capacity  but  this  may  be  offset 
somewhat by increasing the circuit fluid flow 
rate.    If  in  doubt  about  potential  freeze 
damage  in  your  area,  discuss  it  with  your 
ASP.  Damage to the unit due to freezing is 
not covered by the product warranty. 

If a unit is to be shut down for the winter, 

but  no  fluid  circuits  are  to  be  drained,  then 
simply  Disable  the  chiller-heater  and  allow 
the  unit  to  complete  its  Post  Dilution  Cycle.  
Once  completed,  it  is  safe  to  leave  the  unit 
as  it  sits  for  the  off-season.    Take 

appropriate measures to ensure the fluids in 
all  fluid  circuits  are  protected  from  freezing 

(glycol, heat tape, etc.)

If a chiller-heater is to be shut down long-

term,  then  fluid  circuits  should  be  drained.  
Disable  the  chiller-heater  and  allow  the  unit 
to  complete  its  Post  Dilution  Cycle.    Once 
completed,  turn  off  the  breaker  on  the  unit 
control  panel.    Then  drain  each  fluid  circuit.  
Once  drained,  make  sure  to  blow  in  both 
directions 

through 

each 

circuit 

with 

compressed  air 

(or  similar)

  to  make  sure  no 

significant  amount  of  liquid  remains  inside 
them.    Close  all  isolation  valves  so  as  to 
isolate the unit from the rest of the respective 
fluid  circuit.    Pressurize  each  fluid  circuit  in 
the  chiller-heater  with  dry  nitrogen  to  a 
pressure of 1-2 PSI (7-14 kPa) to help inhibit 
corrosion in the circuit during storage.  It may 
be  desirable  to  break  the  vacuum  in  the 
chiller-heater  itself  as  well.    If  doing  so, 
pressurize  the  unit  to  the  same  pressure  as 
the  circuits  using  nitrogen.    See  the  Service 
Manual for further details. 

TROUBLESHOOTING 

SYMPTOM:  Chiller-heater does not operate.

 

Possible Cause 

REMEDY 

No High Voltage 

Check the LED for the Power indication on the Control Panel.  If it is not illuminated, check the 
main power disconnect, fuses, and breakers. 

Solution Pump Not 
Running 

Check the THRP overload switch.  Check the GP temperature.  Until the GP temperature rises 
above 190°F 

(88°C)

, the solution pump may remain off until the GP temperature warms up.   

Chiller-heater is not 
running but WTO 
temperature is above 
set point. 

Nothing may be wrong.  If the system chilled water loop has satisfied by reaching the desired set 
point, the unit will shut down until the WTO sensor reads a temperature 3.6°F 

(2°C)

 above the set 

point temperature, no matter how long that may take.  To force operation, turn off power to the 
chiller-heater, leave power off for 10 seconds, and then restore power.  The chiller-heater should 
start up if the WTO sensor reading is above the set point. 

 

SYMPTOM:  Poor cooling capacity.

 

Possible Cause 

REMEDY 

Poor Vacuum 

Evacuate the machine per normal maintenance procedure.  A leak check may also be necessary. 

High Inlet Cooling 
Water Temperature 

Check the cooling tower fan.  Check the cooling tower fluid level. 

Low Cooling Water 
Flow Rate 

Check the cooling tower sump and cooling water circuit strainers. 

Condenser/Absorber 
Fouling, Scale Buildup 

Check the cooling water circuit strainers.  A chemical de-scaling procedure will be necessary.   

Everything appears 
normal but the leaving 
chilled water 
temperature is too 
high. 

Nothing may be wrong.  If the load of the chilled water circuit exceeds the capacity of the chiller-
heater, the system will find equilibrium at a higher leaving chilled water temperature.  If the 
temperature drop through the chilled water loop is approximately 8-12°F 

(4-6°C)

, then the unit 

may actually be giving its full capacity and its capacity simply may not be enough.  Check for 
reasons that the load may have artificially increased 

(open doors, new equipment, leaking valves, etc.)

 

Summary of Contents for CH-K100

Page 1: ...UCTIONS and properly maintained it can provide many years of trouble free operation CONTENTS GENERAL Page ABSORPTION PRINCIPLE 2 COOLING OPERATION 2 HEATING OPERATION 3 CONTROLS GENERAL INFORMATION 4...

Page 2: ...cooled and heat is normally rejected to a cooling tower though ground loop is also an option COOLING OPERATION High Temperature Generator HGE The gas burner heats a dilute lithium bromide solution in...

Page 3: ...nd semi concentrated solution flow into the primary separator in exactly the same manner as in the cooling cycle Low Temperature Generator LGE In Heat mode the changeover valve opens a path for the se...

Page 4: ...y also be supervised and controlled by external control systems to a limited degree when the necessary interconnections are installed Additional controls and interlocks can be explained by your ASP On...

Page 5: ...2 10 Rated 300vac F4 2 Fuji Model FGAO 2 Rated 250vac F11 F12 2 Fuji Model FGAO 2 Rated 250vac F31 F32 1 Fuji Model FGAO 2 Rated 250vac FB11 FB12 2 Fuji Model FGAO 2 Rated 250vac FB21 FB22 15 Nagasaw...

Page 6: ...on the I O Board to ON The leaving chilled water temperature can be adjusted using the TC potentiometer on the CPU Board The leaving chilled water set point can be set in a range of 40 1 F 4 5 C to 59...

Page 7: ...ress the alarm RESET button to restart the cooling or heating operation If Error Code 52 is amongst the codes being displayed it will also be necessary to press the RESET button on the burner controll...

Page 8: ...Gas Pressure Check Supply and Manifold Inhibitor Check If required For the K Series an inhibitor charge is needed every 3 years on average Palladium Cell Heater Check Flow Rate Check Solution Pump Rot...

Page 9: ...s vacuum section Just because the vacuum pump has stopped producing bubbles in the water bucket does NOT mean the vacuum level is adequate A digital vacuum gauge MUST be used in order to determine the...

Page 10: ...iller heater itself as well If doing so pressurize the unit to the same pressure as the circuits using nitrogen See the Service Manual for further details TROUBLESHOOTING SYMPTOM Chiller heater does n...

Page 11: ...iption Notes Reset Type FS Flow switch alarm Chilled hot water flow switch FS1 open but for less than 10 minutes After 10 minutes this changes automatically to error code 27 Auto 01 DCP power error Op...

Page 12: ...10 C or above 212 F 100 C Ignored for first 10 minutes of P2 operation Manual 36 CND sensor error CND sensor reads below 14 F 10 C or above 212 F 100 C Auto 40 Loss of cooling capacity LT temperature...

Page 13: ...13 Please send a copy of any maintenance data sheets to Yazaki Energy Systems Inc at the address FAX number and or email address listed on the last page of this document...

Page 14: ...Labor Charges for warranty service can be obtained by an authorized service provider upon written request to YESI 7 LIMITATION OF WARRANTY AND LIMITATION OF REMEDY CUSTOMER s remedies shall be limite...

Page 15: ......

Page 16: ...MS INC 701 E PLANO PKWY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web http www yazakienergy com This symbol on the product s name plate means i...

Reviews: