Manual VIPA System 300S SPEED7
Chapter 1 Assembly and installation guidelines
HB140E - PS - RE_307-1FB70 - Rev. 13/43
1-11
General data
Conformity and approval
Conformity
CE 2006/95/EC
Low-voltage
directive
2004/108/EC
EMC
directive
Approval
UL
UL 508
Approval for USA and Canada
others
RoHS
2011/65/EU
Product is lead-free; Restriction of the use of
certain hazardous substances in electrical and
electronic equipment
Protection of persons and device protection
Type of protection
-
IP20
Electrical isolation
to the field bus
-
electrically isolated
to the process level
-
electrically isolated
Insulation resistance
EN 61131-2
-
Insulation voltage to reference earth
Inputs / outputs
-
AC / DC 50V, test voltage AC 500V
Protective measures
-
against short circuit
Environmental conditions to EN 61131-2
Climatic
Storage / transport
EN 60068-2-14
-25…+70°C
Operation
Horizontal installation
EN 61131-2
0…+60°C
Vertical installation
EN 61131-2
0…+60°C
Air humidity
EN 60068-2-30
RH1 (without condensation, rel. humidity 10…95%)
Pollution
EN 61131-2
Degree of pollution 2
Mechanical
Oscillation
EN 60068-2-6
1g, 9Hz ... 150Hz
Shock
EN 60068-2-27
15g, 11ms
Mounting conditions
Mounting place
-
In the control cabinet
Mounting position
-
Horizontal and vertical
EMC
Standard
Comment
Emitted
interference
EN 61000-6-4
Class A (Industrial area)
EN 61000-6-2
Industrial area
EN 61000-4-2
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity 2)
EN 61000-4-3
HF irradiation (casing)
80MHz … 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
EN 61000-4-6
HF conducted
150kHz … 80MHz, 10V, 80% AM (1kHz)
EN 61000-4-4
Burst, degree of severity 3
Noise immunity
zone B
EN 61000-4-5
Surge, installation class 3 *
)
*
)
Due to the high-energetic single pulses with Surge an appropriate external protective circuit with
lightning protection elements like conductors for lightning and overvoltage is necessary.
All manuals and user guides at all-guides.com