Individual Functions
6-
125
* The factory setting will change when the control method is changed. The flux vector factory setting is given.
Multi-function Contact Input Functions (H1-01 to H1-10)
Multi-function Contact Output Functions (H2-01 to H2-05)
Multi-function Analog Inputs (H3-05, H3-09)
H3-09
Multi-function
analog input
(terminal A2)
function selec-
tion
Select multi-function analog input
function for terminal A2. Refer to
the next table.
0 to 1F
0
No
A
A
A
A
A
Terminal A2
Sel
H3-10
Gain (terminal
A2)
Sets the input gain (level) when
10 V (20 mA) is input.
Set according to the 100% value
for the function set for H3-09.
0.0 to
1000.0
100.0%
Yes
A
A
A
A
A
Terminal A2
Gain
H3-11
Bias (terminal
A2)
Sets the input gain (level) when 0
V (4 mA) is input.
Set according to the 100% value
for the function set for H3-09.
-100.0
to
+100.0
0.0%
Yes
A
A
A
A
A
Terminal A2
Bias
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
71
Speed/torque control change (ON: Torque control)
No
No
No
Yes
Yes
78
Polarity Reverse Command for external torque reference
No
No
No
Yes
Yes
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
32
Speed control circuit operating for torque control (except when stopped).
The external torque reference will be limited if torque control is selected.
Output when the motor is rotating at the speed limit.
No
No
No
Yes
Yes
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0
Add to terminal A1
Yes
Yes
Yes
Yes
Yes
13
Torque reference/torque limit at speed control
No
No
No
Yes
Yes
14
Torque compensation
No
No
No
Yes
Yes
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector