5
-78
Con-
stant
Number
Name
Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
U1-10
Input termi-
nal status
Shows input ON/OFF status.
The ON/OFF status of the fol-
lowing input terminals can be
checked by displaying U1-10
and pressing the Enter Key.
(Press the Enter Key again to
return to the original dis-
play.)
(Cannot be output.)
-
A
A
A
A
A
49H
Input Term
Sts
U1-11
Output ter-
minal status
Shows output ON/OFF status.
(Cannot be output.)
-
A
A
A
A
A
4AH
Output
Term Sts
U1-12
Operation
status
Inverter operating status.
(Cannot be output.)
-
A
A
A
A
A
4BH
Int Ctl Sts 1
1: FWD command
(S1) is ON.
1: REV command
(S2) is ON.
1: Multi input 1
(S3) is ON.
1: Multi input 2
(S4) is ON.
1: Multi input 3
(S5) is ON.
1: Multi input 4
(S6) is ON.
1: Multi input 5
(S7) is ON.
1:Multi input 6
(S8) is ON.
U1-10= 00000000
1: Multi input 7
(S9) is ON.
1: Multi input 8
(S10) is ON.
1: Multi input 9
(S11) is ON.
1: Multi input 10
(S12) is ON.
U1-10= 0000
U1-11= 00000000
1: Multi-function
contact output
(M1-M2) is ON.
1: Multi-funtion
contact output 1
(P1) is ON.
1: Multi-funtion
contact output 2
(P2) is ON.
1: Multi-function
contact output 3
(P3) is ON.
1: Multi-function
contact output 4
(P4) is ON.
Not used (always 0).
1: Error output
(MA/AB-MC) is ON.
1: Run
1: Zero speed
1: Reverse
1: Reset signal
input
1: Speed agree
1: Inverter
ready
1: Minor fault
1: Major fault
U1-12= 00000000