APPENDIX 3
CONSTANTS LIST
63
Table A-
7
Constant List
Constant
Name
Setting Range Factory
Change
during
Access
Description
Constant
No.
Display
Setting Range Factory
Setting
during
Operation
Access
Level
Description
A1-00
Language selection for
operator display,
0, 1
0
f
A
0 : English
1 : Japanese
A1-00
[Select Language]
0, 1
0
f
A
1 : Japanese
A1 01
Constant access level
0 to 9999
4
f
A
0 : Monitoring only
A1-01
[Access Level]
0 to 9999
4
f
A
0 : Monitoring only
4 : Advanced (A)
A1 03
Initialize
0000 to 9999
0000
×
A
2220:Initializes using the User Constants
A1-03
[Init Parameters]
0000 to 9999
0000
×
A
2220:Initializes using the User Constants
A1 04
Password 1 (Input)
0000 to 9999
0
×
A
A1-04
[Enter Password]
0000 to 9999
0
×
A
B1 02
Operation method selection
0 1
1
×
A
0 : Digital Operator
B1-02
[Run Source]
0, 1
1
×
A
0 : Digital Operator
1 : Control circuit terminals
B1 06
Read sequence input twice
0 1
1
×
A
0 : Two scans every 500
µ
sec
B1-06
[Cntl Input Scans]
0, 1
1
×
A
0 : Two scans every 500
µ
sec
1 : Two scans every 5 ms
C8-17
Automatic operation stop
current
10 to 100 %
50
×
A
C8-17
[Autorun Iout]
10 to 100 %
50
×
A
C8 18
Bias voltage at operation start
0 0 to 50 0 V
2 0
×
A
For 400 V class power regenerative units,
C8-18
[V Bias of Run]
0.0 to 50.0 V
2.0
×
A
For 400 V class power regenerative units,
double the initial setting and setting range.
C8-19
Hysteresis voltage width at
operation start/stop
0.5 to 50.0 V
3.0
×
A
For 400 V class power regenerative units,
double the initial setting and setting range.
C8-19
[V Width of Stop]
0.5 to 50.0 V
3.0
×
A
double the initial setting and setting range.
C8 20
Min. operating time
0 0 to 600 0 sec
1 0
×
A
C8-20
[Minimum Run Time]
0.0 to 600.0 sec
1.0
×
A
F1-10
Excessive frequency
deviation detection level
1.0 to 10.0 Hz
3.0
×
A
F1-10
[FDEV DetectLevel]
1.0 to 10.0 Hz
3.0
×
A
F1-11
Excessive frequency devi-
ation detection delay time
0.0 to 255.0 sec
70.0
×
A
F1-11
[FDEV Detect Time]
0.0 to 255.0 sec
70.0
×
A
H1-01
Multi-function input
(terminal S3)
0 to 2F
24
f
A
24 : External fault
(NO contact, stop)
H1-01
[Terminal S3 Sel]
0 to 2F
24
f
A
(NO contact, stop)
Refer to Table A-8.
H1-02
Mlti-function input
(terminal S4)
0 to 2F
14
f
A
14 : Fault reset
Refer to Table A-8.
H1-02
[Terminal S4 Sel]
0 to 2F
14
f
A
Refer to Table A 8.
H2-02
Multi-function input
(terminal M1-M2)
0 to 20
6
f
A
6 : Regenerative unit ready
Refer to Table A-9.
H2-02
[Terminal M1 Sel]
0 to 20
6
f
A
Refer to Table A 9.
H2-03
Multi-function input
(terminal M3-M4)
0 to 20
0
f
A
0 : During Run
Refer to Table A-9.
H2-03
[Terminal M3 Sel]
0 to 20
0
f
A
Refer to Table A 9.
H4-01
Multi-function AO
(terminal AM-AC)
0 to 21
5
f
A
0 : Not used
2 : DC bus voltage (U1-02)
4 : Power supply voltage (U1-04)
5 : Current at power side (U1-05)
7 : Power at power side (U1 07)
H4-01
[Terminal AM Sel]
0 to 21
5
f
A
7 : Power at power side (U1-07)
8 : Power supply frequency (U1-08)
21 : Voltage deviation input (U1-21)
Refer to Table A-10.
H4 02
Gain (terminal AM-AC)
0 00 to 2 50
0 50
f
A
H4-02
[Terminal AM Gain]
0.00 to 2.50
0.50
f
A
H4 03
Bias (terminal AM-AC)
−
10.0 to
0 0
f
A
H4-03
[Terminal AM Bias]
−
10.0 to
+10.0 %
0.0
f
A
H4-07
Analog output signal polarity
selection
0, 1
1
f
A
0 : Without sign
1 : With sign
H4-07
[AO Level Select]
0, 1
1
f
A
1 : With sign