1. Use 1:1 with an inverter. Do not connect more than one inverter to one power
regenerative unit.
2. Use the power regenerative unit whose capacity is equal to one exceeding
the inverter capacity to be combined.
3. Do not use this unit with single-phase power. Use three-phase power.
Table
17
200 V Class Specifications
Model CIMR-R5U
j
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
g
Rated Capacity
kW
3.7
5.5
7.5
11
15
18.5
22
30
37
ating
Rated DC Current
A
13
19
26
37
51
64
77
102
126
R
a
Rated Current on
Power Side
A
10
15
20
30
40
50
60
80
100
Regenerative Torque
100 % for 1 minute, 25 % ED, 80 % continuous
er
Voltage Frequency
200 to 220 VAC 50 Hz, 200 to 230 VAC 60 Hz
ut
Powe
ply
Allowable Voltage
Fluctuation
+10 to
−
15 % (Imbalance rate between phases: within 2 %)
Input
Sup
p
Allowable Frequency
Fluctuation
¦
3 Hz (Free phase rotation)
stics
Control Method
120
°
current conduction
trol
racteris
Input Power Factor
0.9 or more (Rated current)
Contr
Char
a
Overload Capacity
Stops in 30 seconds at approx. 150 % of rated current.
Operation Input
External terminals
Fault
1C contact output
S
tatus
O
utput
Running, READY
Signal
Photocoupler output
S
t
O
Analog Output
Analog output: 1 point can be selected (current monitor)
Instantaneous
Overcurrent
Stops at approx. 200 % of the current on power side
Blown Fuse
Motor stops by blown fuse.
Overload
Stops after 30 seconds at 150 % of rated current
ction
Undervoltage
(DC Voltage)
Stops at approx. 190 VDC or less.
ve
Func
t
Undervoltage
(Power Side Voltage)
Stops at approx. 150 VAC or less.
ectiv
e
Overload
Stops at approx. 400 VDC or more.
P
rote
c
Fin Overheat
Protected by thermister
P
r
Power Supply Open
Phase
Stops at power supply open phase detection.
Power Frequency Error
Stops by fluctuation more than
±
3 Hz of rated input frequency.
Power Charge
Indication
Indicated until main output voltage is approx. 50 V or less.
NOT
E